1 of 1

B&R X20AIA744 X20 System Analog Input Module

B&R X20AIA744 X20 System Analog Input Module

Only 10 item(s) left in stock
  • Manufacturer: B&R

  • Product No.: X20AIA744

  • Country of origin:United States

  • Product Type: Analog inputs

  • Payment: T/T, Western Union

  • Weight: 1500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Technical Overview

The B&R X20AIA744 (X20AIA744) is a high-performance analog input module engineered for precise strain gauge measurements within the standard X20 system architecture. Designed for seamless deployment in heavy industrial environments like automated manufacturing plants, mining equipment, and structural monitoring systems, this module plays a critical role in weight and force evaluation to eliminate process bottlenecks and reduce system downtime. The hardware features a specialized input stage that directly evaluates full-bridge strain gauges using a differential measurement method. Integrating a 24-bit digital converter resolution with an ultra-fast 200 us conversion time, the unit delivers high-speed data acquisition up to 5000 samples per second per channel, ensuring precise monitoring of dynamic load profiles in high-stress machinery applications.

Technical Configuration

The internal architecture and signal processing path of the module are optimized for low-noise industrial telemetry. The hardware layout incorporates the following characteristics:

  • Software-Configurable Gain: Accommodates strain gauge factors ranging from 2 to 256 mV/V via software settings, eliminating the need for manual hardware calibration or physical jumpers.

  • 4-Wire Interface: Utilizes robust 4-wire connections to ensure stable transmission and accurate differential voltage evaluation directly at the bridge.

  • Advanced Filtering Stage: Includes an integrated hardware input filter with a dedicated 2.5 kHz cutoff frequency to suppress high-frequency EMI and switching noise from adjacent industrial drives.

  • High-Density X20 Slice Design: Features a compact IP20 rated housing that snaps directly onto the X20 backplane, minimizing control cabinet space while maintaining complete electrical isolation between channels and the internal bus.

Technical Specifications

Parameter Specification
Model X20AIA744
Brand B&R
Origin Austria
Product Type Analog Input System
Input Topology Differential Full-Bridge Strain Gauge
Digital Converter Resolution 24-bit
Conversion Time 200 us
Data Output Rate (fDATA) 5000 samples per second per channel
Strain Gauge Factor Range 2 to 256 mV/V (Software Configurable)
Connection Technology 4-wire Connection
Integrated Filter Cutoff 2.5 kHz
Protection Rating IP20
Operating Temperature Range 0 to 55 deg C
Weight 1.5 kg

Industrial Application FAQs

  • How does the X20AIA744 handle line resistance over long cable runs?

    The module uses a differential 4-wire connection method to monitor full-bridge configurations. For applications with extremely long cable lengths where line resistance causes a significant voltage drop, proper calibration via the B&R Automation Studio software is required to compensate for the excitation loss and maintain 24-bit precision.

  • Can this module evaluate half-bridge or quarter-bridge strain gauges?

    The input circuitry is natively designed to evaluate a full-bridge strain gauge configuration. To use half-bridge or quarter-bridge sensors, external completion resistors must be wired into the circuit before connecting to the module terminals to emulate a complete full-bridge differential signal.

  • What is the benefit of the 5000 samples per second data output rate?

    The high sampling rate (fDATA = 5000 samples/s per channel) allows the control system to capture transient forces, rapid weight fluctuations, and high-frequency vibrations. This makes the module suitable for dynamic web tension controls, high-speed bottling lines, and material destruction testing rigs.


Field Engineering and Installation Directives

ELECTROSTATIC DISCHARGE WARNING: The X20 module contains sensitive electronic components that can be damaged by ESD. Ensure field technicians wear a properly grounded ESD wrist strap and isolate all field power supplies before inserting or removing the module from the X20 base block.

Wiring Guide and Signal Integrity

Keep the analog strain gauge signal lines strictly separated from high-voltage AC power cables and variable frequency drive (VFD) motor leads inside the wire duct. Use twisted-pair, shielded instrument cables for all 4-wire connections. Connect the cable shield directly to the functional ground (FE) rail using the X20 shield termination block to prevent industrial noise from corrupting the 24-bit measurement.

Environmental and Thermal Guidelines

The module features an IP20 open-type rating and must be installed inside a clean, dry, lockable industrial control enclosure. Maintain a minimum of 10 mm clearance above and below the X20 slice stack to ensure natural convection cooling. In environments where dust or conductive contaminants are present, the control cabinet must be equipped with an air conditioner or heat exchanger to prevent internal tracking currents.

 

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Blue
Country of origin
United States

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Сұйықтық қуат жүйелерін ауыстыруға арналған электрлік актуаторлар: Практикалық өнеркәсіптік автоматтандыру нұсқаулығы

Бұл мақала SMC компаниясының e-Actuator сериясы сияқты біріктірілген электрлік актюаторлардың дәстүрлі пневматикалық және гидравликалық жүйелерді ауыстыра отырып, өнеркәсіптік қозғалысты басқаруды...

Өнеркәсіптік автоматтандыру қолданбалары үшін OpenPLC көмегімен математикалық операциялар

Бұл мақалада PLC жүйелерінің өнеркәсіптік автоматтандыруда қосу, алу, көбейту, бөлу, модуль және дәрежелеу сияқты негізгі математикалық операцияларды қалай орындайтыны түсіндіріледі. Онда осы функция...

FBD PLC бағдарламалауындағы жетілдірілген булев логика: Негізгі логикадан тыс практикалық өнеркәсіптік қолданбалар

Мақалада PLC бағдарламалауында негізгі AND, OR және NOT операцияларынан тыс қолданылатын бірнеше күрделі Булев логика функциялары түсіндіріледі. Онда шындық кестелері, мультиплексорлар, импульс...

PLC бағдарламалаудағы логикалық операторлар: FBD логикалық қақпаларын түсіну

Булев логика әрбір ПЛК бағдарламасының негізі болып табылады. Қарапайым машина басқару жүйелерінен күрделі өнеркәсіптік автоматтандыру жүйелеріне дейін, логикалық қақпалар контроллерлердің өзгеретін...