Beckhoff BC7300 Modbus Bus Terminal Controller

Beckhoff BC7300 Modbus Bus Terminal Controller

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: BC7300

  • Country of origin:Germany

  • Product Type: Modbus Bus Terminal Controllers

  • Payment: T/T, Western Union

  • Weight: 3000g

  • Dimensions: 51 mm x 100 mm x 69 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Executing local control logic while maintaining high-speed fieldbus communications, the BECKHOFF BC7300 serves as a decentralized programmable controller that seamlessly bridges serial Modbus networks and modular I/O terminals. This compact controller integrates a complete PLC runtime system conforming to IEC 61131-3, allowing local preprocessing of signals independent of the master control system. Capable of hosting up to 64 Bus Terminals, the device optimizes distributed topologies by managing up to 256 digital or 128 analog inputs and outputs directly on the K-bus assembly.

The integrated RS485 D-sub interface supports both Modbus RTU and ASCII protocols, facilitating straightforward integration into legacy SCADA, DCS, or third-party PLC architectures. Configured using TwinCAT programming environments, the device features robust electrical isolation and a dedicated internal power supply to drive connected terminal modules reliably under harsh industrial conditions.

Features

  • Local Intelligence: Built-in PLC runtime system executes 1 PLC task with a cycle time of approximately 3 ms per 1,000 instructions.
  • Flexible Address Configuration: Address settings and operating modes can be adjusted directly via integrated rotary switches or KS2000 software.
  • High I/O Capacity: Supports direct connection of up to 64 Beckhoff Bus Terminals (K-bus expansion).
  • Dual Protocol Support: Configurable for either Modbus RTU or Modbus ASCII serial communication protocols.
  • Substantial Local Memory: Equipped with 32/96 KB of program memory and 32/64 KB of data memory, alongside 512 bytes of remanent data storage.
  • Industrial Protection: Features 500 V electrical isolation between the power contacts, supply voltage, and the fieldbus interface.

Applications

  • Decentralized manufacturing automation lines requiring local preprocessing.
  • Remote Terminal Unit (RTU) deployments in infrastructure, water, and wastewater systems.
  • HVAC and building automation networks utilizing serial Modbus RTU protocols.
  • Substation monitor systems requiring localized signal conditioning and processing.

Technical Specifications

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Number BC7300
Fieldbus Interface D-sub 9-pin, RS485
Supported Protocols Modbus RTU, Modbus ASCII (Default: RTU)
Data Transfer Rates 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 baud
Programming Software TwinCAT (via programming interface or fieldbus)
Program Memory 32 / 96 kbytes
Data Memory 32 / 64 kbytes
Remanent Data 512 bytes
K-Bus Current Supply 1750 mA
Power Contacts Max. 24 V DC / Max. 10 A
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
ATEX Ex Marking II 3 G Ex nA IIC T4 Gc
Physical Dimensions 51 mm x 100 mm x 69 mm
Product Weight 170 g
Shipping Weight (Calculated) 3.0 kg (with heavy-duty industrial protective packaging)

Connections and Interfaces

D-sub 9-Pin Pinout Signal Designation Description
Pin 3 RxD/TxD-B (+) Transmit / Receive Data (Positive)
Pin 8 RxD/TxD-A (-) Transmit / Receive Data (Negative)
Pin 5 GND Signal Ground Reference
Pin 1 Shield Functional Earth / Shield Connection

Empirical Engineering Insights

Alternative Models & Compatibility

While the BC7300 targets serial Modbus RTU/ASCII applications, systems transitioning to Ethernet infrastructures should consider the BC9000 (Modbus/TCP). When upgrading legacy setups, ensure that the TwinCAT target system configuration matches the target BC architecture, as compiling for BK-type couplers is incompatible with BC programmable controllers.

Application Pitfalls & Engineering Notes

The BC7300 features a maximum K-Bus current supply capacity of 1750 mA. When configuring a dense physical node with multiple analog or special function terminals, calculate the cumulative current consumption of all modules. If the requirements exceed 1750 mA, you must integrate intermediate power feed terminals (such as the KL9110 or KL9210) to prevent dropouts on the internal bus.

Commissioning & Wiring Tips

Always verify that the termination resistor on the Modbus RS485 physical line is correctly switched or wired. Because the BC7300 reads rotary switch station addresses only during its initial boot phase, any physical modifications made to the node address while powered will not take effect until the device undergoes a complete power cycle.

Installation Guidelines

CRITICAL SAFETY WARNING

Isolate all electrical power sources before initiating hardware installation, wire termination, or terminal block removal. Failure to de-energize primary supply circuits and physical contacts can result in permanent equipment damage, short circuits, or electrical shock hazards to commissioning engineers.

1 Mount the BC7300 controller firmly onto a standard 35 mm DIN rail (conforming to EN 60715) until the rear locking mechanism fully engages.
2 Slide adjacent Beckhoff Bus Terminals onto the rail from right to left, utilizing the integrated double slot and key connection for reliable structural alignment.
3 Terminate field wiring into the cage clamp terminals using a flat-head screwdriver to actuate the spring tension mechanism. Strip conductors strictly to 8–9 mm.
4 Connect the RS485 Modbus serial line via the D-sub 9-pin interface. Ensure that proper shielding is maintained and grounded at a single, centralized earth point.

What software is required to program the BC7300?

The BC7300 is programmed using TwinCAT 2 in compliance with the IEC 61131-3 standard. Programming can be done through the serial configuration interface or over the fieldbus network.

What is the maximum K-bus current supplied by the controller?

The BC7300 supplies up to 1750 mA to the connected Bus Terminals. If your specific I/O configuration requires more current, you must insert a power feed terminal such as the KL9110 or KL9210.

How do you set the station address on the BC7300?

The Modbus station address is configured via the integrated rotary address switches on the controller housing, or it can be configured via the KS2000 configuration software. Address modifications require a power cycle to take effect.

Does the BC7300 support Modbus RTU and ASCII protocols?

Yes. The controller supports both Modbus RTU and Modbus ASCII. Modbus RTU is the factory default protocol.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Сұйықтық қуат жүйелерін ауыстыруға арналған электрлік актуаторлар: Практикалық өнеркәсіптік автоматтандыру нұсқаулығы

Бұл мақала SMC компаниясының e-Actuator сериясы сияқты біріктірілген электрлік актюаторлардың дәстүрлі пневматикалық және гидравликалық жүйелерді ауыстыра отырып, өнеркәсіптік қозғалысты басқаруды...

Өнеркәсіптік автоматтандыру қолданбалары үшін OpenPLC көмегімен математикалық операциялар

Бұл мақалада PLC жүйелерінің өнеркәсіптік автоматтандыруда қосу, алу, көбейту, бөлу, модуль және дәрежелеу сияқты негізгі математикалық операцияларды қалай орындайтыны түсіндіріледі. Онда осы функция...

FBD PLC бағдарламалауындағы жетілдірілген булев логика: Негізгі логикадан тыс практикалық өнеркәсіптік қолданбалар

Мақалада PLC бағдарламалауында негізгі AND, OR және NOT операцияларынан тыс қолданылатын бірнеше күрделі Булев логика функциялары түсіндіріледі. Онда шындық кестелері, мультиплексорлар, импульс...

PLC бағдарламалаудағы логикалық операторлар: FBD логикалық қақпаларын түсіну

Булев логика әрбір ПЛК бағдарламасының негізі болып табылады. Қарапайым машина басқару жүйелерінен күрделі өнеркәсіптік автоматтандыру жүйелеріне дейін, логикалық қақпалар контроллерлердің өзгеретін...