Providing dedicated human-machine visualization, the Omron NS10-TV00B-V1 serves as a high-resolution graphical operator interface designed for real-time monitoring and control inside automated industrial systems. This model features a robust 10.4-inch TFT active matrix display integrated with a highly responsive touchscreen interface, enabling intuitive system diagnostics and process management. Encased in a black bezel housing, the device is engineered with built-in serial and USB ports to ensure seamless connectivity within multi-node PLC architectures.

Features

  • High-durability TFT color LCD screen displaying up to 256 colors for clear, high-contrast diagnostics.
  • Dual integrated RS-232C serial communication ports enabling direct, simultaneous PLC and peripheral interfacing.
  • Dedicated CompactFlash slot for automated screen project backup, event logging, and recipe data storage.
  • USB host and slave interfaces supporting seamless PC programming via CX-Designer and auxiliary data transfer.
  • Modular expansion capability via dedicated rear-panel option slot for Ethernet or Controller Link modules.

Applications

  • Automotive body shop assembly lines and conveyor system visualization.
  • Packaging machinery, palletizers, and material handling systems.
  • Water treatment processing and pump control monitoring stations.
  • Food and beverage batching, mixing, and heating processes.

Technical Specifications

Manufacturer Omron
Model Reference NS10-TV00B-V1
Display Type TFT Color Active Matrix LCD
Screen Size (Diagonal) 10.4 inches
Resolution 640 x 480 pixels (VGA)
Display Colors 256 colors
Rated Input Voltage 24 VDC
Allowable Voltage Range 20.4 to 27.6 VDC
Power Consumption 25 W maximum
Serial Communications 2 x RS-232C ports (9-pin D-sub)
USB Ports 1 x USB Type B (Slave, USB 1.1)
Expansion Slot 1 x Slot (for network interfaces or video input board)
Storage Medium CompactFlash Slot (Type I/II)
Operating Temperature 0 to 50 degC
Ambient Humidity 35% to 85% RH (non-condensing)
Bezel Color Black
Shipping Weight (Calculated) 3.5 kg

Connections and Interfaces

Interface Connection Physical Connector Signal / Function Assignment
Serial Port A 9-pin D-sub (Female) Host Link / NT Link (1:1 or 1:N) protocol interface
Serial Port B 9-pin D-sub (Female) Host Link, NT Link, or temperature controller serial link
USB Slave USB Type B Direct PC programming and screen data transfer
Power Terminals 3-position terminal block 24 VDC (+), 0 VDC (-), Functional Ground (GR)

Empirical Engineering Insights

Alternative Models & Compatibility

The legacy non-V1 version and the updated V1 module are mount-compatible, utilizing identical cabinet cutouts. Note that screen projects compiled for V1 hardware require updating the target HMI system program in CX-Designer before performing a serial or USB download to prevent runtime initialization faults.

Application Pitfalls & Engineering Notes

Thermal behavior inside small, unventilated enclosures can accelerate backlight aging. Always maintain a minimum clearance of 100 mm around all rear chassis surfaces. Do not use standard consumer-grade MLC CompactFlash cards; write endurance limits will trigger localized sectors to corrupt under heavy data-logging cycles. Standardize on SLC industrial-grade media.

Commissioning & Wiring Tips

When wiring high-speed NT Link serial configurations over long distances, route serial runs strictly away from high-current AC motor leads to reduce electromagnetic interference. Ground loops are common if functional ground terminals are bridged back to industrial drive bus commons. Ensure functional ground (GR) is terminated directly to the main cabinet star ground plate.

Installation Guidelines

CRITICAL WARNING: ELECTRICAL RISK

Isolate and lock out all AC/DC power sources feeding the enclosure panel prior to preparing cutouts, executing physical installation, or terminating control wiring. Failure to do so may result in device damage, internal circuit failure, or high-voltage shock.

1
Prepare Panel Cutout: Trace and cut a clear rectanglar opening of 302.0 mm x 228.0 mm (tolerance +1.0 / -0.0 mm) in the enclosure door. Ensure panel thickness is between 1.6 mm and 4.8 mm.
2
Verify Bezel Gasket: Confirm that the waterproof rubber sealing gasket is seated flat inside the outer perimeter groove of the HMI bezel. This is critical to maintain IP65-equivalent protection.
3
Secure Mounting Brackets: Insert the device from the front of the panel cutout, then slide the mounting brackets into the side tracks from behind. Progressively tighten the screws with a torque of 0.5 to 0.6 N-m to ensure an even seal without cracking the bezel.
4
Terminate Power & Ground: Connect 24 VDC power lines using 2 mm2 cross-section wires. Wire the Functional Ground terminal using a green/yellow earth lead directly to the main system electrical ground point.

What configuration tool is required for programming the NS10-TV00B-V1?

The HMI must be configured using Omron CX-Designer software, which is distributed as a component of the standard CX-One automation suite.

Are the older NS10 units cross-compatible with the V1 model?

Yes. The physical footprint, cutout dimensions, and electrical inputs match older units, but you must select the V1 hardware profile in CX-Designer before downloading existing screen programs.

Can the LCD backlight assembly on this screen be replaced?

Yes, the backlight on the NS10-TV00B-V1 HMI is designed to be field-replaceable. Utilize only genuine Omron replacement backlight kits to ensure durability.

What type of storage cards should be used in the integrated card slot?

The device features a CompactFlash (CF) Type I/II slot. For high reliability in data logging and firmware storage, always specify industrial-grade SLC CompactFlash cards.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Сұйықтық қуат жүйелерін ауыстыруға арналған электрлік актуаторлар: Практикалық өнеркәсіптік автоматтандыру нұсқаулығы

Бұл мақала SMC компаниясының e-Actuator сериясы сияқты біріктірілген электрлік актюаторлардың дәстүрлі пневматикалық және гидравликалық жүйелерді ауыстыра отырып, өнеркәсіптік қозғалысты басқаруды...

Өнеркәсіптік автоматтандыру қолданбалары үшін OpenPLC көмегімен математикалық операциялар

Бұл мақалада PLC жүйелерінің өнеркәсіптік автоматтандыруда қосу, алу, көбейту, бөлу, модуль және дәрежелеу сияқты негізгі математикалық операцияларды қалай орындайтыны түсіндіріледі. Онда осы функция...

FBD PLC бағдарламалауындағы жетілдірілген булев логика: Негізгі логикадан тыс практикалық өнеркәсіптік қолданбалар

Мақалада PLC бағдарламалауында негізгі AND, OR және NOT операцияларынан тыс қолданылатын бірнеше күрделі Булев логика функциялары түсіндіріледі. Онда шындық кестелері, мультиплексорлар, импульс...

PLC бағдарламалаудағы логикалық операторлар: FBD логикалық қақпаларын түсіну

Булев логика әрбір ПЛК бағдарламасының негізі болып табылады. Қарапайым машина басқару жүйелерінен күрделі өнеркәсіптік автоматтандыру жүйелеріне дейін, логикалық қақпалар контроллерлердің өзгеретін...