1 daripada 6

ABB TU810V1 3BSE013230R1 S800 I/O Compact Module Termination Unit

ABB TU810V1 3BSE013230R1 S800 I/O Compact Module Termination Unit

Hanya 5 item tinggal dalam stok
  • Pengilang: ABB

  • No. Produk: 3BSE013230R1

  • Negara asal:Sweden

  • Jenis Produk: Compact Module Termination Units

  • Kod Bar: 85389091

  • Pembayaran: T/T, Western Union

  • Berat: 200g

  • Dimensi: 165 mm x 45 mm x 72 mm

  • Pelabuhan penghantaran: Xiamen

  • Jaminan: 12 bulan

Kuantiti
Lihat butiran penuh

Description

Serving as a robust connection interface within the S800 I/O distributed automation architecture, the ABB TU810V1 (part number 3BSE013230R1) acts as a compact module termination unit designed to route signals reliably between field wiring and active I/O process modules. This unit accommodates up to 16 independent channels, operating at a maximum rating of 50V, making it a critical component for high-density cabinet layouts where footprint optimization is vital.

Features

  • High-Density Compact Footprint: Allows direct horizontal or vertical DIN-rail mounting to minimize cabinet space requirements.
  • 16-Channel Configuration: Routes up to 16 individual I/O channels alongside dual process voltage connections.
  • Mechanical Coding Keys: Prevents mismatched module insertion, safeguarding the active electronics from field configuration errors.
  • Integrated Modulebus Link: Seamlessly transfers signals and power to adjacent units without external jumper cables.
  • Dual Voltage Distribution: Includes 2 isolated groups with commoned terminal distribution points.

Applications

  • Advant OCS and System 800xA distributed control architectures.
  • Petrochemical, power generation, and water treatment field-instrumentation processing.
  • High-density electrical marshaling cabinets and field junction boxes.

Technical Specifications

Parameter Specification Value
Manufacturer ABB
Model Designation TU810V1
Product ID / SKU 3BSE013230R1
Series S800 I/O
Type Compact Module Termination Unit (MTU)
Number of Channels 16 channels
Rated Voltage 50 V DC / AC maximum
Rated Current 3 A per channel maximum
Connection System Single-wire screw clamp terminals
Conductor Size 0.2 to 2.5 mm² (24 to 14 AWG)
Modulebus Load Negligible (passive routing)
Dimensions (H x W x D) 165 mm x 45 mm x 72 mm
Weight 0.20 kg
Commodity Code 85389091

Connections and Interfaces

Terminal / Connector Point Function / Circuit Assignment
Terminals 1 to 16 I/O Channel connections (Signals 1 to 16)
Terminals 17 & 18 Process Voltage Common 1 (distribution bus)
Terminals 19 & 20 Process Voltage Common 2 (distribution bus)

Empirical Engineering Insights

Alternative Models & Compatibility

The TU810V1 serves as a direct, drop-in evolution of the legacy TU810 compact MTU. The V1 variant features improved thermal tolerance and mechanical housing updates, ensuring absolute backward-compatibility with all existing S800 I/O modules that require a 50V connection interface. If upgrading from non-V1 units, no software modifications or engineering changes are required in the System 800xA or Control Builder environments.

Application Pitfalls & Engineering Notes

While rated for 50V operational limits, designers must verify that the total accumulated current across all 16 connected channels does not exceed the capacity of the power distribution source. In highly compact enclosures, field wiring must be routed systematically to prevent localized heating near the screw terminals, which could accelerate degradation of the adjacent active I/O modules.

Commissioning & Wiring Tips

To ensure noise immunity in electromagnetic interference (EMI) heavy environments, signal cables should be shielded up to the cabinet entrance, and shields must be grounded to a designated bar separate from the MTU. Ensure that the plastic coding keys on the MTU base are properly configured to match the corresponding module type before power-up to prevent physical component damage during hot-swapping procedures.

Installation Guidelines

CRITICAL WARNING: Complete physical isolation and de-energization of the field supply and Modulebus backplane are mandatory before mounting, unmounting, or wiring the MTU. Failure to isolate power may cause electrical arcing, module destruction, or hazardous field conditions.
1

Mount the TU810V1 MTU onto a grounded 35mm horizontal DIN rail by latching the top groove and snapping the lower locking tab onto the rail.

2

Slide the unit laterally along the DIN rail to connect its Modulebus port directly to the adjacent MTU/Modulebus optical port, ensuring the connection latches completely.

3

Strip field signal and distribution wires to 6mm, insert them into the screw terminals (terminals 1-20), and torque them uniformly to 0.5 Nm.

4

Configure the physical mechanical coding keys on the MTU surface to correspond with the targeted I/O module type before docking the electronic module.

Loading product navigation…

What is the primary difference between the TU810 and the TU810V1?

The TU810V1 features updated high-temperature resistant polymers and optimized internal routing traces, offering 100% direct drop-in backward compatibility with older legacy TU810 models.

Does this termination unit support live module hot-swapping?

Yes. S800 I/O modules can be plugged in or unplugged under power from the MTU, provided active loop safety processes permit the live intervention.

What is the maximum torque rating for the field wiring terminals?

The field screw clamp terminals on this MTU should be tightened to a maximum torque specification of 0.5 Nm to prevent mechanical stress on the printed circuit board.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Perniagaan melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Bayaran Balik .

TECHNICAL SPECIFICATIONS

Country of origin
Sweden

Produk yang Baru Dilihat

Pengetahuan teknikal

Logik Boolean Lanjutan dengan Pengaturcaraan PLC FBD: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan Pengapit Robotik: Dari Pengendalian Halus ke Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...

Throwback: Bagaimana Motor Elektrik Awal Mengubah Perlombongan Bawah Tanah

Dari pemampat DC yang digerakkan tali ke troli lombong bertenaga bateri, operasi perlombongan awal menandakan titik perubahan dalam elektrifikasi industri. Artikel ini meneroka bagaimana motor...

Factory I/O: Alat Simulasi PLC Moden untuk Latihan Automasi Industri

Factory I/O sedang mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang mendalam untuk pelajar, jurutera, dan pasukan penyelenggaraan. Platform ini merapatkan jurang antara teori dan...