Description

Designed for precise decentralized temperature acquisition, the BECKHOFF IE3202 Fieldbus Box extension module interfaces directly with resistive sensors in rugged, industrial environments. This IP67-rated analog input device facilitates the direct connection of up to four resistance thermometers without requiring protective control cabinets. By digitizing signals close to the physical process, it reduces noise susceptibility and cabling complexity.

The IE3202 supports a broad spectrum of RTD configurations, including standard Pt100, Pt200, Pt500, and Pt1000 sensors, alongside Ni100, Ni120, and Ni1000 variants. It also accommodates direct resistance measurements, such as those from potentiometers. Each of the four channels utilizes screw-type M12 connectors that can be wired in 2-wire, 3-wire, or 4-wire configurations (preset to 4-wire) to compensate for cable resistance errors and optimize measurement precision.

Operating as an IP-Link extension module, this device integrates seamlessly with Beckhoff Coupler Box modules, transferring digitized process data over high-speed IP-Link communication channels. The robust housing, high-resolution digitization, and configurable filtering capabilities make it an ideal choice for challenging distributed control architectures.

Features

  • Four independent analog inputs dedicated to RTD and resistance measurements.
  • Flexible M12 screw-type connections supporting 2-, 3-, and 4-wire configurations.
  • Compatible with a comprehensive range of platinum (Pt) and nickel (Ni) sensors.
  • High-resolution data acquisition at 0.1 degC per digit for sensitive thermal monitoring.
  • Configurable conversion times ranging from a standard 250 ms down to 65 ms.
  • Five configurable digital input filter variations for advanced noise rejection.
  • IP-Link interface for fast, reliable data exchange with fieldbus couplers.
  • Heavy-duty IP65/66/67 protection rating for direct mounting in harsh industrial zones.

Applications

  • Decentralized process temperature tracking in plant engineering and machine construction.
  • Thermal monitoring of motors, bearings, and critical mechanical assemblies.
  • Food processing and washdown-heavy environments requiring direct-to-machine installation.
  • HVAC, chemical processing, and environmental monitoring systems.

Technical Specifications

ManufacturerPart Number / ModelNumber of InputsConnection MethodSensor TypesMeasuring RangeResolutionMeasurement Error / UncertaintyConversion TimeNominal VoltageMeasuring CurrentInput FilterSensor SupplyCurrent Consumption from USPower Supply ConnectionBit Width in Process ImageElectrical IsolationOperating TemperatureStorage TemperatureVibration / Shock ResistanceEMC Immunity / EmissionProtection RatingInstallation PositionWeight
BECKHOFF
IE3202
4
Screw-type M12 for 2-, 3-, and 4-wire connections (preset: 4-wire)
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g., potentiometer)
-250 to +850 degC (Pt sensors); -60 to +250 degC (Ni sensors)
0.1 degC per digit
less than ±1 degC
Approx. 250 ms, configurable down to 65 ms
24 V DC (-15 % / +20 %)
typ. 0.5 mA
5 variations, configurable
Derived from control voltage US
40 mA (excluding sensor current)
Feed: 1 x M8 male socket (4-pin); Downstream: 1 x M8 female socket (4-pin)
Input: 4 x 16-bit data (4 x 8-bit control/status optional)
Channels/control voltage: 500 V; Between channels: None; Control voltage/fieldbus: Yes, via IP-Link
0 to +55 degC
-25 to +85 degC
Conforms to EN 60068-2-6 / EN 60068-2-27
Conforms to EN 61000-6-2 / EN 61000-6-4
IP65/66/67 (conforms to EN 60529)
Variable
2.0 kg

Connections and Interfaces

Power FeedPower DownstreamAnalog Inputs 1 - 4
Connection Point Connector Type Functional Assignment
M8 Male, 4-pin Control voltage US input
M8 Female, 4-pin Loop-through control voltage US to subsequent modules
M12 Female, 5-pin RTD sensor connection (supporting 2-, 3-, or 4-wire layouts)

Installation Guidelines

  • Mounting: Mount the unit directly onto a flat, vibration-resistant surface using appropriate fastening screws. Ensure sufficient clearance for connecting and disconnecting cables.
  • Shielding & Grounding: To minimize electromagnetic interference, use shielded sensor cables. Connect the cable shields to the metal M12 connector housings wherever possible.
  • Environmental Protection: To maintain the IP65/66/67 seal, tighten all M12 and M8 connectors to their specified torque limits. Seal any unused connection ports with industrial-grade protective caps.
  • Cabling: Maintain separation between sensor input lines and high-power AC power cables or variable frequency drive outputs to prevent noise coupling.

Compliance and Certifications

  • CE: European Conformity
  • UL: Underwriters Laboratories Listed
Loading product navigation…

Which temperature sensor types are compatible with the Beckhoff IE3202?

The IE3202 is compatible with several RTD types, including Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, and Ni1000. It also supports general resistance and potentiometer measurements.

Does the IE3202 support 3-wire RTD configurations?

Yes, the M12 screw-type terminals can be wired for 2-wire, 3-wire, or 4-wire sensors. The device is preset for 4-wire operation out of the box.

What is the ingress protection rating of the IE3202 Fieldbus Box?

It is rated at IP65, IP66, and IP67, making it dust-tight and highly resistant to water jets and temporary submersion. This allows direct installation on machines without control cabinets.

How does the IE3202 transfer its measurement data to the main PLC system?

The IE3202 acts as an extension module that connects to a master Fieldbus Box (Coupler Box) via the high-speed fiber-optic IP-Link interface, which then bridges the data to the main fieldbus protocol.

Penghantaran Ekspres Global

  • Penghantaran Standard: 4-6 Hari Bekerja melalui DHL, FedEx, dan UPS.
  • Penghantaran Ekspres: Penghantaran pada hari yang sama untuk pesanan dalam stok yang dibuat sebelum 2:00 PM (GMT+8).
  • Liputan Seluruh Dunia: Berkhidmat di lebih 150 negara, termasuk penghantaran pantas ke Arab Saudi dan UAE.

Pemulangan & Jaminan

  • Jaminan 30 Hari: Pemulangan diterima untuk produk dalam stok dalam pembungkusan asal yang disegel kilang.
  • Jaminan 12 Bulan: Setiap komponen industri disokong oleh jaminan teknikal profesional kami.

Pesanan diproses dan dihantar Isnin-Jumaat (tidak termasuk cuti umum).


Untuk kelayakan penuh, yuran penyimpanan semula, dan butiran pemulangan antarabangsa, sila lihat rasmi kami Polisi Pemulangan & Pengembalian Wang .

TECHNICAL SPECIFICATIONS

Country of origin
Jerman

Produk yang Baru Dilihat

Pengetahuan teknikal

Penggerak Elektrik Direka untuk Menggantikan Sistem Kuasa Cecair: Panduan Automasi Industri Praktikal

Artikel ini menerangkan bagaimana aktuator elektrik bersepadu, seperti siri e-Actuator SMC, mengubah kawalan gerakan industri dengan menggantikan sistem pneumatik dan hidraulik tradisional. Ia...

Operasi Matematik Menggunakan OpenPLC untuk Aplikasi Automasi Industri

Artikel ini menerangkan bagaimana sistem PLC melaksanakan operasi matematik teras seperti penambahan, penolakan, pendaraban, pembahagian, modulo, dan perpangkatan dalam automasi industri. Ia...

Logik Boolean Lanjutan dengan Pengaturcaraan FBD PLC: Aplikasi Industri Praktikal Melebihi Logik Asas

Artikel ini menerangkan beberapa fungsi logik Boolean lanjutan yang digunakan dalam pengaturcaraan PLC selain operasi asas AND, OR, dan NOT. Ia merangkumi bagaimana alat seperti jadual kebenaran,...

Logik Boolean dalam Pengaturcaraan PLC: Memahami Pintu Logik FBD

Logik Boolean adalah asas bagi setiap program PLC. Dari kawalan mesin yang mudah hingga sistem automasi industri yang kompleks, pintu logik menentukan bagaimana pengawal bertindak balas terhadap...

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan untuk Pengapit Robotik: Dari Pengendalian Halus hingga Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...