BECKHOFF KL2692 Bus Terminal

BECKHOFF KL2692 Bus Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: KL2692

  • Country of origin:Jerman

  • Product Type: Bus Terminal

  • Payment: T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

The KL2692 is a multifunctional Bus Terminal from BECKHOFF, combining 2 potential-free relay outputs (normally-open contacts) and 2 digital 24 V DC inputs in a single compact module. This terminal is designed for efficient signal processing and actuator control, allowing for the switching of ohmic or inductive loads up to 5 A (ohmic). With an electrical isolation of 500 V between the K-bus and field potential, the KL2692 ensures reliable separation in complex automation architectures.

Features

  • 2 potential-free relay outputs (normally-open contacts)
  • 2 digital 24 V DC inputs
  • 2-wire connection technology
  • High switching capacity: 5 A ohmic (AC/DC) per channel
  • Minimum load capacity of 10 mA at 5 V DC
  • Mechanical service life of 2 x 10^7 operating cycles
  • Configuration via Bus Coupler or controller
  • Compact IP20-rated housing for DIN rail mounting

Applications

  • Distributed I/O for relay-based logic control
  • Switching of external contactors or solenoids
  • Digital sensor status acquisition combined with output control
  • Automation systems requiring mixed input/output functionality

Technical Specifications

Category Specification
Manufacturer BECKHOFF
Model KL2692
Number of Outputs 2 (relay, NO contacts)
Number of Inputs 2 (digital 24 V DC)
Max. Switching Current (Ohmic) 5 A AC/DC per channel
Max. Switching Current (Inductive) 2 A AC/DC per channel
Nominal Voltage 30 V DC
Current Consumption (K-bus) typ. 165 mA
Electrical Isolation 500 V (K-bus/field potential)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Weight approx. 60 g
Protection Rating IP20

Installation Guidelines

  • Mount the terminal on a 35 mm DIN rail (EN 60715) and secure it using the integrated locking mechanism.
  • Utilize the double slot and key connection for secure side-by-side assembly.
  • Ensure all connections comply with the 2-wire wiring technology requirements.
  • Maintain the ambient operating temperature between 0 and +55 degC to preserve the operational lifespan of the internal relay contacts.
  • Follow EMC standards EN 61000-6-2/EN 61000-6-4 during wiring to prevent signal interference.

Compliance and Certifications

  • CE
  • UL

What is the switching capacity of the relay outputs on the KL2692?

The relay outputs support up to 5 A for ohmic loads and 2 A for inductive loads per channel.

How are the inputs and outputs configured?

Configuration is performed via the Bus Coupler or the host controller.

What is the expected mechanical lifespan of the relays?

The mechanical lifespan is rated for a minimum of 2 x 10^7 operating cycles.

Are the outputs isolated from the K-bus?

Yes, there is 500 V electrical isolation between the K-bus and the field potential.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Putih
Country of origin
Jerman

Recently Viewed Products

Technical knowledge

Panduan Mendalam tentang Firewall Industri dan Segmentasi Rangkaian OT

Firewall industri memainkan peranan penting dalam keselamatan siber OT, melindungi rangkaian PLC, DCS, dan SCADA melalui segmentasi, kawalan masuk/keluar, dan integrasi IDS/IPS yang selaras dengan...

Panduan Pengapit Robotik: Dari Pengendalian Halus ke Automasi Tugas Berat

Pengapit robotik moden sedang berkembang melebihi rahang mekanikal tradisional. Daripada sistem pelekat yang diinspirasikan oleh cicak dan pengapit lembut gred makanan hingga alat gudang yang...

Throwback: Bagaimana Motor Elektrik Awal Mengubah Perlombongan Bawah Tanah

Dari pemampat DC yang digerakkan tali ke troli lombong bertenaga bateri, operasi perlombongan awal menandakan titik perubahan dalam elektrifikasi industri. Artikel ini meneroka bagaimana motor...

Factory I/O: Alat Simulasi PLC Moden untuk Latihan Automasi Industri

Factory I/O sedang mengubah pendidikan PLC dengan menyediakan simulasi industri 3D yang mendalam untuk pelajar, jurutera, dan pasukan penyelenggaraan. Platform ini merapatkan jurang antara teori dan...

Pengaturcaraan Kitaran Gerakan Paksi Tunggal pada Pemacu Servo CMZ

Tutorial ini mengkaji bagaimana fungsi PLC terbina dalam pemacu servo CMZ SBD dapat melaksanakan program gerakan berdiri sendiri, termasuk logik homing, kawalan kedudukan, dan pergerakan paksi...

Persediaan Kawalan Gerakan Paksi Tunggal dengan Pemacu Servo CMZ

Tutorial ini meneroka penyediaan sistem gerakan servo paksi tunggal menggunakan pemacu CMZ SBD, merangkumi penyediaan perkakasan, penskalaan paksi, konfigurasi homing, dan pengesahan gerakan selamat...