1 z 3

Bently Nevada 3500/04-01 136719-01 Earthing I/O Module

Bently Nevada 3500/04-01 136719-01 Earthing I/O Module

Only 4 item(s) left in stock
  • Manufacturer: Bently Nevada

  • Product No.: 136719-01

  • Country of origin:Stany Zjednoczone

  • Product Type: Earthing I/O Module

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 400g

  • Dimensions: 241 mm x 24.4 mm x 103.1 mm (H x W x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Description

The Bently Nevada 136719-01 (part of the 3500/04-01 assembly) is an Earthing I/O Module designed for intrinsically safe (IS) ground reference management within the 3500 Machinery Protection System. Installed directly into the rear of the 3500 system rack, the 136719-01 provides the essential intrinsically safe earth connection through the 3500 system backplane to interface with internal barrier monitor I/O modules. This configuration enables safe, direct interconnection with approved field transducers—such as 3300 XL Proximitor sensors, Velomitor sensors, thermocouples, and RTDs—operating in hazardous environments without requiring external barriers or compromising system performance.

Features

  • Provides the intrinsically safe ground connection for internal barrier I/O modules via the 3500 system backplane.
  • Installs in a dedicated monitor position within the standard 3500 Machinery Protection System rack.
  • Fully integrated backplane routing eliminates the need for external zener or galvanic isolation barrier units.
  • Supports combined rack layouts hosting both internal barrier modules and standard I/O modules.

Applications

  • Intrinsically safe field wiring grounding for 3500 Machinery Protection Systems in hazardous industrial areas.
  • Turbomachinery vibration, speed, position, and temperature monitoring systems requiring IS loop protection.

Ordering Information

Part Number / Option Code Description
3500/04-AA-BB 3500/04 Internal Barrier System
A: I/O Module Type 01 Earthing I/O Module
B: Agency Approval

00 None

01 North American Hazloc

02 Multi (CSA, ATEX, IECEx)

136719-01 Earthing I/O Module (Spare Part)
138257-01 Earthing Module Front Panel (Spare Part)

Technical Specifications

Specification Category Parameter / Value
Manufacturer Bently Nevada
Module Type Earthing I/O Module (3500/04 IS Earthing Module)
Dimensions (H x W x D) 241 mm x 24.4 mm x 103.1 mm (9.50 in. x 0.96 in. x 4.06 in.)
Weight 0.201 kg (0.443 lb.)

Installation Guidelines

  • Rack Slot Allocation: The 136719-01 IS Earthing Module requires a dedicated monitor position in the rack, which limits a standard 19-inch rack to 13 monitor positions.
  • Positioning: Locate the IS Earthing Module in a rack position that allows easy access for routine online maintenance. When positioned between internal barrier I/O modules, allow a minimum of two rack positions to facilitate online access.
  • Requirement: Any 3500 rack containing internal barrier I/O modules must be equipped with a 3500/04-01 IS Earthing Module to provide the backplane IS earth path.
  • Wiring Separation: Route hazardous area field wiring above the 3500 rack and safe area wiring below to maintain a minimum physical separation of 50 mm (2 in).

Compliance and Certifications

Standard / Approval Type Certificate / Standard Level
FCC Complies with Part 15 of FCC Rules
EMC Directive European Community Directive 2014/30/EU; EN 61000-6-2, EN 61000-6-4
Electrical Safety European Community Directive 2014/35/EU; EN 61010-1
Marine Classification DNV GL rules for classification; ABS Rules Part 1
cNRTLus Class I, Zone 2: AEx/Ex nA nC ic IIC T4 Gc; Class I, Zone 2: AEx/Ex ec nC ic IIC T4 Gc; Class I, Division 2, Groups A, B, C, D; T4 @ Ta = -20 degC to +65 degC
ATEX / IECEx II 3 G; Ex nA nC ic IIC T4 Gc; Ex ec nC ic IIC T4 Gc; T4 @ Ta = -20 degC to +65 degC
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 3500/04-01 136719-01 Earthing I/O Module

Which chassis slot does the earthing module occupy in the rack?

The module installs into a dedicated monitor position on the 3500 rack backplane, reducing available monitor slots to 13.

Does the earthing module require software configuration?

The module acts as a passive backplane ground reference interface and does not require independent software programming.

Can standard and internal barrier modules coexist in the same chassis?

Standard and internal barrier modules can reside in the same chassis provided the earthing module establishes backplane IS ground.

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Color pattern
Srebro
Country of origin
Stany Zjednoczone

Ostatnio oglądane produkty

Wiedza techniczna

What Is a PLC? The Controllers That Still Run the Plant Floor

PLCs still run the plant floor: scan cycles, I/O, and IEC 61131-3 languages decide whether machines stay deterministic. Here is how controllers work, where they win, and where they strain.

What It Really Takes to Learn Industrial Automation in 2026

Learning industrial automation now means mastering PLCs, networks, and protection systems—not just robots. This guide maps skills, pitfalls, and career paths for engineers entering control-heavy...

Modernizacja interfejsów HMI Bailey INFI 90 Symphony działających na OpenVMS Alpha

Praktyczny przewodnik po zastępowaniu starzejących się stacji operatorskich Bailey Symphony działających w systemie OpenVMS Alpha. Porównuje emulację platformy Alpha, migrację do OpenVMS x86, zmianę...

Dlaczego dane dotyczące konserwacji są niezbędne dla niezawodności przemysłowej

Dane dotyczące utrzymania ruchu łączą zlecenia prac, sygnały z czujników, historię zasobów, koszty i wiedzę techników. Właściwie wykorzystywane usprawniają planowanie, niezawodność, konserwację...

Siłowniki elektryczne zaprojektowane jako zamiennik układów napędzanych cieczą: praktyczny przewodnik po automatyzacji przemysłowej

Ten artykuł wyjaśnia, jak zintegrowane siłowniki elektryczne, takie jak seria e-Actuator firmy SMC, zmieniają przemysłowe sterowanie ruchem, zastępując tradycyjne systemy pneumatyczne i hydrauliczne....

Operacje matematyczne z użyciem OpenPLC w zastosowaniach automatyki przemysłowej

Ten artykuł wyjaśnia, jak systemy PLC wykonują podstawowe operacje matematyczne, takie jak dodawanie, odejmowanie, mnożenie, dzielenie, modulo i potęgowanie, w ramach automatyki przemysłowej....