  • Manufacturer: BECKHOFF

  • Product No.: EK1122-0008

  • Country of origin:Niemcy

  • Product Type: 2-port EtherCAT junction with M8 connection

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 24 mm x 100 mm x 52 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Product Overview

The EK1122-0008 (EK 1122-0008) is a specialized 2-port EtherCAT junction terminal engineered for rugged industrial environments where mechanical stability and vibration resistance are paramount. Designed to facilitate the branching of EtherCAT topologies, this module replaces standard RJ45 ports with two M8 shielded, screw-type interfaces. In high-dynamic applications such as robotic arms, mobile assembly platforms, and wind turbine pitch control, the EK1122-0008 ensures a gas-tight, secure physical connection. By enabling the creation of star or tree topologies within an EtherCAT segment, it allows for decentralized station coupling with a minimal internal delay of approximately 1 microsecond, maintaining the deterministic performance of the 100 Mbit/s network.

Technical Configuration

The EK1122-0008 serves as a transparent junction within the EtherCAT system, requiring no manual software configuration or addressing. It utilizes the E-bus for its internal power supply, consuming typically 220 mA. The module is capable of driving 100BASE-TX signals over distances of up to 100 meters using shielded Cat.5 (or higher) cabling. Its architecture is specifically hardened for extreme conditions, featuring vibration and shock resistance according to EN 60068 standards. Furthermore, it carries extensive hazardous area certifications, including ATEX (Ex nA) and cFMus (Class I, Division 2), permitting deployment in explosive atmospheres where Zone 2 or Division 2 safety protocols are required.

Technical Specifications

Attribute Specification Details
Model EK1122-0008
Brand BECKHOFF
Origin Germany
Bus Interface 2 x M8 (Shielded, Screw Type)
Protocol EtherCAT
Data Transfer Rate 100 Mbit/s
Delay approx. 1 microsecond
Distance between Stations Max. 100 m (100BASE-TX)
Current Consumption Typ. 220 mA (from E-bus)
Operating Temperature -25 to +60 deg C
Dimensions (W x H x D) 24 mm x 100 mm x 52 mm
Protection Rating IP20
Weight 65 g
Shipping Weight 2.0 kg
Approvals CE, UL, ATEX, IECEx, cFMus

Technical FAQs

Why would I choose M8 connections over standard RJ45 for a junction?

The M8 screw-type connection on the EK1122-0008 provides significantly higher mechanical security. Unlike RJ45 clips which can snap or vibrate loose, the M8 threaded coupling ensures the shield and data pins remain in constant contact even under high-frequency vibration or repetitive movement.

Does the EK1122-0008 require its own IP address?

No. As an EtherCAT junction, the EK1122-0008 is transparent to the network. The EtherCAT master automatically manages the data flow through the junction to any downstream devices without the need for manual configuration or IP assignment.

Can this junction be used to power downstream terminals?

The EK1122-0008 draws its own power from the E-bus to drive the 2-port switch logic, but it is primarily a data coupling device. Ensure that your EtherCAT coupler (e.g., EK1100) has sufficient E-bus power capacity to support the 220 mA consumption of this junction plus all other attached ELxxxx terminals.


Engineering & Installation Guide

M8 Connector Assembly and Shielding:

To maintain the required EMC immunity (conforming to EN 61000-6-2/4), use only shielded M8 4-pin D-coded cables. Tighten the M8 screw-type connectors to the manufacturer’s recommended torque to ensure the shield makes a 360-degree connection with the terminal housing. This is critical in preventing data packet loss in high-interference environments typical of motor control centers.

Hazardous Area (Ex) Installation:

For ATEX and cFMus Class I, Div 2 installations, the EK1122-0008 must be installed in a tool-secured enclosure that provides at least IP54 protection. Ensure that the M8 cables are also rated for the environment and that the 35 mm DIN rail is connected to a clean functional earth. Under no circumstances should the M8 connectors be disconnected while the circuit is live in a hazardous atmosphere.

Topology Planning and Delay:

With a minimal internal delay of 1 microsecond, the EK1122-0008 allows for deep nesting of EtherCAT branches without significantly impacting the cycle time. When planning the network, keep in mind that the 100-meter distance limit applies to each segment (from the junction to the next station). Use the double slot and key connection to firmly mount the junction alongside other EtherCAT terminals to ensure E-bus continuity.

 

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Color pattern
Srebro
Country of origin
Niemcy
Power source
Zasilanie prądem stałym

Ostatnio oglądane produkty

Wiedza techniczna

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...