1 z 1

Honeywell FTA-T-08 Fail-Safe Digital Output Relay FTA Module

Honeywell FTA-T-08 Fail-Safe Digital Output Relay FTA Module

Only 7 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: FTA-T-08

  • Country of origin:Stany Zjednoczone

  • Product Type: Safety Relay Modules

  • Payment: T/T, Western Union

  • Weight: 1500g

  • Dimensions: 5 x 20 mm (0.2 x 0.78 in) or 5 x 25 mm (0.2 x 0.98 in)

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Description

Engineered for high-integrity safety systems, the Honeywell FTA-T-08 is a 4-channel fail-safe digital output relay Field Termination Assembly (FTA). Designed to interface directly with safety-critical control modules such as the 10201/2/1, this unit provides robust galvanic isolation and contact multiplication for critical process shutdown and safety interlock loops. Each of the four channels features a redundant, diverse relay configuration utilizing devices from different manufacturers to mitigate common-cause failures and comply with rigorous functional safety requirements.

The FTA-T-08 incorporates an integrated 3.15 AT slow-acting fuse on each normally open (NO) field contact, protecting field-side wiring and devices from unexpected overcurrent conditions. Local status diagnostics are indicated through on-board LEDs, facilitating prompt field troubleshooting. Connection to the primary controller rack is accomplished using specialized SIC-C-02 cables, maintaining optimal signal integrity across the termination assembly.

Features

  • Four independent fail-safe digital output relay channels.
  • Redundant contact architecture featuring diverse relays from separate manufacturers to prevent common-mode failures.
  • Individual channel protection via 3.15 AT slow-acting fuses on the output contacts.
  • Integrated diagnostic LEDs for real-time channel status monitoring.
  • Silver alloy contacts designed for reliable and durable switching.
  • Direct integration compatibility with Honeywell 10201/2/1 modules using SIC-C-02 cable assemblies.

Applications

  • Emergency Shutdown Systems (ESD) in petrochemical and refinery environments.
  • Burner Management Systems (BMS) in power utility plants.
  • Fire and Gas (F&G) mitigation control networks.
  • Critical safety interlock loops in chemical processing.

Technical Specifications

Manufacturer Honeywell
Part Number/Model FTA-T-08 (3410713)
Module Compatibility 10201/2/1
Number of Channels 4
Nominal Input Voltage 24 Vdc
Maximum Input Voltage 31 Vdc
Relay Cut-in Voltage 19 Vdc
Typical Input Current 50 mA at 24 Vdc
Maximum Output Current 3.15 A
Minimum Output Current 400 mA at 24 Vdc
Maximum Switched Voltage 250 Vac / 150 Vdc
Maximum Switched Load 1250 VA / 150 W
Maximum Switched Frequency 20 Hz
Contact Material Silver alloy
Fuse Rating 3.15 AT (slow-acting), 5 x 20 mm or 5 x 25 mm
Electrical Lifecycles 80,000 operations
Mechanical Lifecycles 5,000,000 operations
Operating Ambient Temperature -40 degC to +60 degC (-40 degF to +140 degF)
Shipping Weight 1.5 kg

Connections and Interfaces

Connection Interface Specification
Termination Type T10 terminal connection
FTA Connector 1 x 4F connector layout
System Interface Cable SIC-C-02
Signals per Cable 4/4 channels

Installation Guidelines

  • De-energize all power sources before handling, mounting, or wiring the Field Termination Assembly.
  • Mount the module securely on a standard DIN rail or enclosure backplate inside a dust-free, dry industrial cabinet.
  • Isolate and route the high-voltage relay wiring separately from low-voltage logic signal cables.
  • Confirm that the field load does not exceed the maximum rated capacity of the 3.15 AT internal fuses.
  • Maintain sufficient spacing between adjacent modules to ensure continuous convection cooling within the specified ambient temperature limits.

Compliance and Certifications

  • CE Compliant
  • TUV Safety Certified
  • UL Listed

What is the primary function of the Honeywell FTA-T-08?

The FTA-T-08 is a 4-channel fail-safe digital output relay Field Termination Assembly (FTA) designed for isolation and high-integrity switching in safety shutdown and interlock applications.

What makes the relay configuration in this module safety-oriented?

Each channel is built with a diverse pair of redundant relays from different manufacturers to minimize the risk of common-cause failures.

What type of overcurrent protection is installed on the FTA-T-08?

Each output channel features an individual 3.15 AT slow-acting fuse, compatible with standard sizes of 5 x 20 mm or 5 x 25 mm.

What are the operating temperature limits for the FTA-T-08?

The assembly is rated for operations in ambient temperatures ranging from -40 degC to +60 degC (-40 degF to +140 degF).

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Country of origin
Stany Zjednoczone

Ostatnio oglądane produkty

Wiedza techniczna

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...