1 z 4

Omron CJ1G-CPU45P CJ1G Series Loop Control CPU Unit

Omron CJ1G-CPU45P CJ1G Series Loop Control CPU Unit

Only 7 item(s) left in stock
  • Manufacturer: Omron

  • Product No.: CJ1G-CPU45P

  • Country of origin:Japonia

  • Product Type: Loop Control CPU Unit

  • Payment: T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Description

The Omron CJ1G-CPU45P is a high-performance central processing unit featuring integrated loop control functions, designed specifically for the SYSMAC CJ1 series programmable controller platform. It integrates traditional sequence control with advanced analog loop control, allowing the block processing of PID algorithms directly within the CPU unit. This module eliminates the need for separate analog regulatory controllers by executing seamless sequence and process loop execution simultaneously. Outfitted with an onboard peripheral port, standard RS-232C connectivity, and internal flash memory storage, it provides a stable and optimized architecture for complex industrial process environments.

Features

  • Integrated engine for sequential logic and regulatory loop control functions.
  • Supports function blocks for standard PID control, cascade control, and feed-forward loops.
  • Dedicated internal memory area for scaling and allocating process variables.
  • Built-in RS-232C interface and standard peripheral hardware connection port.
  • Slotless, compact layout minimizing din-rail backplane surface configuration.
  • Flash memory execution architecture protects user logic records from voltage drops without requiring immediate battery assist.
  • Seamless interfacing options with standard CJ-series discrete and high-density analog I/O modules.

Applications

  • Temperature control and thermal regulation systems in chemical reactors.
  • Flow rate monitoring and automated water treatment plants.
  • Pressure control loops for gas and liquid distribution systems.
  • Extrusion and batch processing lines in plastic manufacturing.
  • Food and beverage Pasteurization and brewing processes.

Technical Specifications

Performance and System Capacity

ParameterSpecification
Program Capacity 60K steps
Data Memory Capacity 128K words
Number of Loop Control Blocks Up to 300 blocks
LD Instruction Execution Speed 0.04 μs
Maximum I/O Capacity 1,280 points
Maximum Number of Expansion Racks 3 Racks

 

Communication and Interfaces

ParameterSpecification
Built-in Peripheral Port Proprietary tool bus connection
Built-in Serial Port RS-232C (D-Sub 9-pin female connector)
Protocol Support Host Link, NT Link, No-protocol serial communication
Storage Interface CompactFlash card slot for system backups and data logging

 

Electrical and Environmental

ParameterSpecification
Current Consumption 0.91 A at 5 VDC
Operating Ambient Temperature 0 to 55 Celsius
Storage Ambient Temperature -20 to 75 Celsius
Ambient Operating Humidity 10% to 90% RH (non-condensing)
Operating Atmosphere Free from corrosive gases

 

Connections / Interfaces

Port / InterfaceConnector TypeFunction
Peripheral Port Custom Omron Connector Connection for programming software (CX-Programmer / CX-Process)
RS-232C Port D-Sub 9-pin (Female) Interfacing with local HMI displays, smart transmitters, or SCADA
Memory Card Slot CompactFlash (CF) Slot Storing loop configuration files, program backups, and historical data logs

 

Installation Guidelines

  • Module Assembly: Hook the upper guide of the CPU onto the DIN rail track beside the system power supply module. Slide the unit lock connectors downward until they fully snap into position.
  • Functional Grounding: Connect a dedicated ground conductor (2 mm2 or thicker) directly to the ground terminal located on the primary rack power supply unit.
  • Thermal Management: Keep an open boundary space of at least 20 mm around the top and bottom vents of the module assembly to ensure uniform heat dissipation.
  • Signal Shielding: Ensure analog loop sensor cables and low-voltage signal lines are shielded and separated from heavy motor cables or power mains switching lines.
  • Hot-Swapping Restriction: Isolate the entire system rack from incoming power distribution sources before attempting to clear or mount the CPU unit.

FAQ

  • What is the primary difference between this model and a standard CJ1G CPU? The "P" suffix denotes integrated loop control capability, embedding process loop block functionality alongside standard ladder logic.
  • Which programming software is required to configure the loop blocks? CX-Process software is used to design and configure the process loop blocks, while CX-Programmer manages standard sequence control.
  • Is an external battery needed to preserve the step programs? No, user programs and loop configuration blocks are written to internal non-volatile flash memory storage automatically.
  • Does this module support online adjustment of loop parameters? Yes, tuning parameters such as PID gains can be modified during operation using compatible software or connected HMIs.
  • Can this unit operate without an attached power supply module? No, it requires a compatible CJ-series system power supply module installed on the left side of the backplane.
  • What type of memory card does the integrated slot accept? It accommodates standard Omron-certified CompactFlash cards for localized data logging and maintenance tasks.
  • How many hardware I/O points can this unit handle locally? It supports a maximum capacity of 1,280 discrete and analog hardware I/O points across the local rack and expansion racks.
  • What communication modes are supported by the D-Sub port? It can run under Host Link, NT Link (1:N), or No-protocol configurations for custom serial line data exchange.
  • How do I monitor loop execution errors? System status blocks and indicators like the ERR/ALM LED indicate status changes, which can be diagnosed via software toolsets.
  • What should I do if the unit experiences electrical noise issues? Ensure the power supply functional ground terminal is connected to an independent, clean industrial earth ground line.

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Color pattern
Czarny Biały
Country of origin
Japonia
Power source
Zasilanie prądem stałym

Ostatnio oglądane produkty

Wiedza techniczna

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...