1 z 1

Omron NX-AD4603 NX Series 8-Channel Voltage Analog Input Unit

Omron NX-AD4603 NX Series 8-Channel Voltage Analog Input Unit

Only 5 item(s) left in stock
  • Manufacturer: Omron

  • Product No.: NX-AD4603

  • Country of origin:Japonia

  • Product Type: Analog Input Modules

  • Payment: T/T, Western Union

  • Weight: 70g

  • Shipping port: Xiamen

  • Warranty: 12 months

Ilość
Pokaż kompletne dane

Description

Designed for high-density data acquisition within the Sysmac automation platform, the Omron NX-AD4603 provides high-speed, single-ended analog voltage monitoring across eight independent channels. This high-resolution module integrates into the Omron NX-series I/O system, offering seamless communication with Sysmac NJ/NX controllers or industrial couplers. By converting analog physical inputs to precise digital values under a Free-Run refreshing architecture, the Omron NX-AD4603 ensures reliable process tracking for complex industrial manufacturing environments.

Features

  • High-Density 8-Point Layout: Houses eight single-ended input channels within a compact 12 mm width to optimize control cabinet space.
  • Standard Industrial Voltage Range: Accepts -10 V to +10 VDC inputs, supporting standard pressure, temperature, and flow transducers.
  • High Conversion Precision: Features 1/8000 full-scale resolution, mapping analog inputs to a decimal digital scale of -4000 to 4000.
  • Continuous Free-Run Refreshing: Provides constant, asynchronous update cycles for applications where synchronization to the master PLC cycle is not strictly required.
  • Robust Input Protection: Built-in safeguards support an absolute maximum voltage rating of +/-15 V to prevent damage from transient voltage surges.

Applications

  • Multi-Sensor Machine Telemetry: Integrates arrayed displacement, pressure, and level sensors directly into the primary control network.
  • Factory Automation & Assembly: Monitors analog feedback from tooling actuators and automated clamping systems.
  • Continuous Process Monitoring: Captures high-frequency electrical feedback in packaging and material handling machines.

Technical Specifications

Parameter Specification Value
Manufacturer Omron
Model Number NX-AD4603
Number of Inputs 8 points
Input Method Single-ended input
Input Voltage Range -10 to +10 VDC
Absolute Maximum Rating +/-15 VDC
Resolution 1/8000 (Full Scale)
Decimal Conversion Value -4000 to 4000 (0 to 100%)
Overall Accuracy (at 25 degC) 0.2% (Full Scale)
I/O Refreshing Method Free-Run refreshing
Input Conversion Range -5% to 105% (Full Scale)
Unit Weight 0.070 kg (70 grams)
Shipping Weight (Calculated) 0.35 kg

Alternative Models & Compatibility

The Omron NX-AD4603 is fully compatible with any NX-series EtherCAT Coupler Unit (such as the NX-ECC201/ECC202) and EtherNet/IP Coupler Units. It can also be directly mounted to the right of an NX1P2 CPU. Note that Sysmac Studio version 1.10 or higher is required for complete hardware configuration and calibration. If differential voltage inputs are required to isolate electrical signals across distant field sensors, consider the 2-point differential NX-AD2603 or the 4-point NX-AD3603.

Application Pitfalls & Engineering Notes

Because this module utilizes a single-ended input design, all eight channels share a common internal ground connection. If your field transmitters reside at significantly different ground potentials, this shared reference can introduce ground loop noise, affecting reading accuracy or causing drift. In systems where sensor grounds cannot be equalized, install external signal isolators or transition to isolated differential input modules.

Commissioning & Wiring Tips

To prevent electromagnetic interference (EMI) from distorting low-level analog signals, always route input wiring away from high-voltage motor cables and variable frequency drive (VFD) output paths. Use shielded, twisted-pair cabling for all analog inputs, and ground the shielding foil at a single, solid earth point near the PLC chassis. Ensure the sensor voltage does not exceed the absolute limit of +/-15 V, as sustained overvoltage will degrade the internal ADC multiplexer.

Installation Guidelines

CRITICAL WARNING: Prior to physical installation, mounting, or wiring modifications, isolate and de-energize all primary system power supplies. Confirm all residual charge has fully bled down. Failure to de-energize can damage sensitive internal CMOP logic or cause system communication faults on the NX-bus.
1

Align the guide connectors on the side of the NX-AD4603 with the adjacent NX unit on the DIN rail.

2

Slide the module onto the DIN rail until the slide locking mechanism engages with an audible click.

3

Strip field wiring to the specified length (8 to 10 mm) and insert directly into the screwless push-in connection terminals.

4

Power up the system bus and verify status via the LED indicators on the front face of the module.

What is the key difference between single-ended and differential inputs on the NX I/O series?

Single-ended inputs like those on this module share a common internal ground line, reducing wiring complexity and terminal space, whereas differential units isolate each channel's ground to prevent noise in long cable runs.

Can I input a standard 0 to 10 VDC signal into the NX-AD4603?

Yes, the unit accepts an input range of -10 to +10 VDC, which easily covers standard industrial 0 to 10 VDC sensor outputs.

What happens if a field signal surges above the maximum rating?

The module features an absolute maximum voltage rating of +/-15 VDC. Exceeding this limit can cause permanent thermal damage to the internal multi-channel analog-to-digital converter circuitry.

Is an external power supply required to drive the internal logic of the module?

No, the internal logic and communications of the module are fully powered through the NX-bus connection provided by the communication coupler or controller unit.

Globalna ekspresowa wysyłka

  • Standardowa dostawa: 4-6 dni roboczych za pośrednictwem DHL, FedEx i UPS.
  • Ekspresowa wysyłka: Wysyłka tego samego dnia dla zamówień dostępnych w magazynie złożonych przed godziną 14:00 (GMT+8).
  • Globalne pokrycie: Obsługujemy ponad 150 krajów, w tym szybką dostawę do Arabii Saudyjskiej i ZEA.

Zwroty i gwarancja

  • 30-dniowa gwarancja: Zwroty przyjmowane są dla produktów dostępnych w magazynie, w oryginalnym, fabrycznie zapieczętowanym opakowaniu.
  • 12-miesięczna gwarancja: Każdy komponent przemysłowy objęty jest naszą profesjonalną gwarancją techniczną.

Zamówienia są przetwarzane i dostarczane od poniedziałku do piątku (z wyłączeniem dni świątecznych).


Aby poznać pełne warunki kwalifikowalności, opłaty za przyjęcie towaru z powrotem oraz szczegóły dotyczące zwrotów międzynarodowych, prosimy zapoznać się z naszym oficjalnym Polityka zwrotów i zwrotu pieniędzy .

TECHNICAL SPECIFICATIONS

Country of origin
Japonia

Ostatnio oglądane produkty

Wiedza techniczna

Siłowniki elektryczne zaprojektowane do zastąpienia systemów hydraulicznych: praktyczny przewodnik po automatyce przemysłowej

Ten artykuł wyjaśnia, jak zintegrowane siłowniki elektryczne, takie jak seria e-Actuator firmy SMC, rewolucjonizują przemysłową kontrolę ruchu, zastępując tradycyjne systemy pneumatyczne i...

Operacje matematyczne z wykorzystaniem OpenPLC w zastosowaniach automatyki przemysłowej

Ten artykuł wyjaśnia, jak systemy PLC wykonują podstawowe operacje matematyczne, takie jak dodawanie, odejmowanie, mnożenie, dzielenie, modulo oraz potęgowanie w automatyce przemysłowej. Pokazuje,...

Zaawansowana logika boolowska w programowaniu PLC za pomocą FBD: praktyczne zastosowania przemysłowe wykraczające poza podstawową logikę

Artykuł wyjaśnia kilka zaawansowanych funkcji logiki boolowskiej stosowanych w programowaniu PLC, wykraczających poza podstawowe operacje AND, OR i NOT. Omawia, jak narzędzia takie jak tabele prawdy,...

Logika boolowska w programowaniu PLC: Zrozumienie bramek logicznych FBD

Logika boolowska jest podstawą każdego programu PLC. Od prostych sterowań maszyn po złożone systemy automatyki przemysłowej, bramki logiczne decydują o tym, jak sterowniki reagują na zmieniające się...

Szczegółowy przewodnik po przemysłowych zaporach sieciowych i segmentacji sieci OT

Przemysłowe zapory sieciowe odgrywają kluczową rolę w cyberbezpieczeństwie OT, chroniąc sieci PLC, DCS i SCADA poprzez segmentację, kontrolę ruchu przychodzącego/wychodzącego oraz integrację IDS/IPS...

Przewodnik po chwytakach robotycznych: od delikatnego manipulowania po ciężką automatykę

Nowoczesne chwytaki robotyczne ewoluują poza tradycyjne mechaniczne szczęki. Od systemów adhezyjnych inspirowanych gekonem i miękkich chwytaków spożywczych po narzędzia magazynowe zasilane sztuczną...