Danfoss

034G1707 Danfoss ETS 50 Electric Expansion Valve

SKU 034G1707

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Danfoss

  • Product No.: 034G1707

  • Country of origin:United States

  • Product Type: Electric Expansion Valve ETS 50

  • Payment: T/T, Western Union

  • Weight: 3000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Overview

The 034G1707 (034G1707) is a high-precision ETS 50 series electric expansion valve designed for precise liquid injection in air conditioning and refrigeration systems. Engineered to work with electronically controlled controllers, the 034G1707 utilizes a bipolar motor actuator to provide accurate flow regulation across a wide range of evaporation temperatures. Featuring a balanced design and bi-metal (steel/copper) solder connections, this straightway valve ensures optimum system efficiency and compressor protection by maintaining stable superheat. The IP67-rated M12 electrical connection guarantees reliable performance in environments prone to moisture and condensation, making it a staple for high-capacity chillers and commercial heat pump systems.

Technical Configuration

The 034G1707 features a sophisticated mechanical and electrical interface for seamless system integration:

  • ETS 50 Series Actuation: Utilizes a precise bipolar stepper motor that translates electrical pulses into linear needle movement, allowing for minute adjustments in refrigerant flow.

  • Bi-Metal Solder Connections: The steel/copper ODF solder connections simplify installation by allowing for standard copper-to-copper brazing without the need for specialized flux or welding techniques.

  • Straightway Flow Design: The linear internal geometry minimizes pressure drop across the valve while maintaining a balanced orifice for consistent performance regardless of inlet pressure.

  • M12 4-Pin Connector: A standardized electrical interface that provides secure, vibration-resistant connectivity, compatible with most universal EEV controllers and Danfoss EKD series drivers.

Technical Specifications

Feature Specification
Model 034G1707 (ETS 50)
Brand Danfoss
Connection Type Solder ODF
Connection Material Bi-metal (Steel/Copper)
Flow Configuration Straightway
Electrical Interface M12, 4-Pin Male
Enclosure Rating IP67
Max Working Pressure 45.5 bar (660 psig)
Compatible Refrigerants R410A, R407C, R404A, R134a, R22, etc.
Step Precision 2625 Steps (Full Stroke)
Shipping Weight 3.0 kg

Technical FAQs

Does the ETS 50 valve require a specific orientation for installation?

The 034G1707 is a straightway valve, but for optimum oil return and to prevent liquid slugging at the actuator, the valve should be installed with the motor housing (actuator) pointing upwards. Horizontal installation is permissible but never with the motor pointing downwards.

What is the benefit of the bi-metal connection?

The bi-metal design allows the valve body to be constructed of durable stainless steel while providing copper ends for brazing. This eliminates the risk of overheating the sensitive internal valve components during the soldering process, as copper conducts heat more efficiently for the joint.

Can this valve be used as a solenoid shut-off valve?

While the ETS 50 provides tight shut-off, it is a modulating valve. In systems where safety regulations require a positive mechanical shut-off during power failure, a dedicated solenoid valve should be installed in the liquid line upstream of the 034G1707.


Engineering & Installation Guide

  • Brazing Protection: Even with bi-metal connections, it is critical to protect the valve body and the M12 electrical connector from excessive heat. Wrap the valve body in a wet cloth during brazing to ensure the internal motor windings and seals do not exceed 120 Celsius.

  • Cable Routing: When connecting the M12 4-pin cable, ensure the cable is routed with a "drip loop" to prevent moisture from entering the connector. Although rated IP67, constant exposure to standing water can lead to pin corrosion over time.

  • Controller Calibration: Upon first power-up, ensure the controller performs a "battery backup" or "manual close" sequence to calibrate the zero-point of the stepper motor. The ETS 50 requires 2625 total steps to move from fully closed to fully open; incorrect step calibration will lead to erratic superheat control.

 

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States
Power source
AC-powered

Technical knowledge

Troubleshooting Beckhoff EPP2008-0001 Output Faults

A field checklist for EPP2008-0001 current limits, supply voltage, channel LEDs, connector coding and load-related output faults.

Moving TwinCAT 3 Licenses with C9900-L100: Build and Device Checks

Before moving a TwinCAT 3 license with a Beckhoff C9900-L100, verify the TwinCAT build, XML device description, exact order code and cabinet limits.

Replacing a Beckhoff EL4032: Wiring and Output Checks

A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.

Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap

Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.