Dimensions:
2.5 cm x 17.8 cm x 29.8 cm (W x H x D)
Shipping port:
Xiamen
Warranty:
12 months
Description
The ABB IMASM01 Analog Slave Module is a high-level analog input interface designed for use within the INFI 90 Process Management System. Functioning in conjunction with an Analog Master Module such as the IMAMM03, the IMASM01 conditions and routes process field analog input signals to the master module via the slave expander bus.
The module interfaces up to 16 individual high-level analog signals divided into two distinct input groups of eight channels each. Field process signals are directed to the module through system cable connections to associated termination units or modules, such as the NTAI05 or NIAI04. Onboard group address switches and enable/disable jumpers allow flexible system integration and address selection within a Process Control Unit (PCU) rack.
Features
Interfaces up to 16 high-level analog input channels across two independent 8-channel input groups.
Direct compatibility with the IMAMM03 Analog Master Module via the slave expander bus.
Onboard dipswitches for setting independent group addresses (0 to 7) for each 8-channel group.
Dedicated enable/disable jumpers for each input group to prevent address conflicts.
Integrated input filtering circuits providing normal mode and common mode noise rejection.
Supports live insertion and removal without powering down the entire control system.
Applications
Industrial DCS process control and monitoring in power generation, chemical, and refining plants.
High-level analog signal interface for transmitters and field devices (4 to 20 mA and 0 to 10 VDC loops).
Input expansion for INFI 90 Process Control Units (PCUs).
Technical Specifications
Parameter
Specification
Manufacturer
ABB / Elsag Bailey
Model
IMASM01
Module Type
High Level Analog Slave Module
System Compatibility
INFI 90 Process Management System (with IMAMM03 Master)
Number of Inputs
16 high level (15 when used with NIAI04 Termination Module)
Input Channels per Group
8 channels per group (2 groups total)
Input Voltage Ranges
1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC, -10 to +10 VDC
1 slot in standard INFI 90 Module Mounting Unit (MMU)
Operating Temperature
0 to 70 degC (32 to 158 degF)
Relative Humidity
0% to 95% up to 55 degC (131 degF) noncondensing; 0% to 45% at 70 degC (158 degF) noncondensing
Altitude
Sea level to 3 Km (1.86 miles)
Air Quality
Noncorrosive
Termination Support
NTAI05, NIAI04
Connections/Interfaces
Connector Pin / Port
Function
P1 Edge Connector
Connects to logic power (+5 VDC, +15 VDC, -15 VDC) on the MMU backplane
P2 Edge Connector
Connects to the slave expander bus for communication and analog bus routing
P3 Edge Connector
Interfaces to field input wiring via termination unit/module cables (NKTU01/02 or NKTM01)
Installation Guidelines
ESD Protection: Always wear a grounded wrist strap and handle the card by its edges when inserting or removing it from the rack.
Address Configuration: Set group address dipswitches S1 (inputs 9-16) and S2 (inputs 1-8) to unique group addresses (0 to 7) prior to installation.
Group Enable/Disable: Set jumpers JP1 (inputs 1-8) and JP2 (inputs 9-16) to position B to enable a group, or position A to disable an unused group to prevent dual-addressing conflicts.
Slave Expander Bus: Ensure 12-strap dipshunts are installed in the MMU backplane sockets between the master module and associated slave modules.
Module Mounting: Align the module card edges with the guide rails in the Module Mounting Unit (MMU) slot and slide in until flush with the rack frame; tighten the two captive faceplate screws.
Compliance and Certifications
CSA certified for use as process control equipment in an ordinary (nonhazardous) location.
FAQ
How many input channels does the device support?
The module supports up to 16 high-level analog input channels, arranged in two separate groups of eight channels each (or 15 channels when used with an NIAI04 termination module).
What power supplies are required to operate the module?
The device operates on logic power supplied through the backplane at +5 VDC (110 mA max), +15 VDC (80 mA max), and -15 VDC (40 mA max).
How are group addresses set on the device?
Group addresses (0 through 7) are configured prior to installation using onboard dipswitches S1 for inputs 9-16 and S2 for inputs 1-8.
A practical Micro800 commissioning workflow covering hardware checks, USB and Ethernet discovery, safe ladder testing, download risks, fault isolation, and project recovery in FactoryTalk Design...
Learn what derivative action contributes to a PID loop, why it can amplify measurement noise and setpoint changes, and how filtering, sampling, and staged tests make D tuning safer.
A practical guide to segmenting, documenting, and testing industrial Ethernet networks so plant teams can isolate faults quickly, control change, and expand without creating fragile dependencies.
Commission IO-Link systematically from master addressing and port modes through IODD selection, PLC byte mapping, parameter backups, device validation, and failure-injection tests.
An industrial joystick is only the first element in a safe motion command chain. This guide covers sensing choices, wiring, signal validation, PLC logic, restart behavior, and commissioning for...
Choosing a selection results in a full page refresh.