Product Overview

The AKV 20-3 (042H2024) is a high-capacity, electronically operated expansion valve designed for precise liquid injection in large-scale refrigeration plants. Operating on the Pulse Width Modulation (PWM) principle, the Danfoss 042H2024 (042H2024) functions as both an expansion device and a solenoid valve, providing a tight shut-off when de-energized. This dual-purpose design is critical for B2B industrial applications such as cold storage warehouses, industrial chillers, and supermarket rack systems, where maintaining an exact superheat (SH) is essential for energy efficiency and compressor safety. The AKV 20-3 is engineered to handle higher mass flow rates than the AKV 20-1/2 models while maintaining rapid response times.

Technical Configuration

The AKV 20-3 utilizes a 13.5 mm actuator system and is typically driven by a Danfoss ADAP-KOOL controller. Instead of modulating the needle position, the valve cycles fully open and fully closed at high frequencies; the duration of the "open" phase determines the refrigerant flow. This mechanical simplicity allows for a robust, hermetic construction capable of withstanding millions of cycles. With a Maximum Working Pressure (PS) of 28 bar (406 psig), it is compatible with most HFC and HCFC refrigerants. The "Type 3" designation indicates a specific orifice capacity within the AKV 20 series, optimized for medium-to-high capacity evaporators.

Technical Specifications

Feature Specification
Model AKV 20-3 (042H2024)
Brand Danfoss
Product Type Electric Expansion Valve (PWM)
Actuator System 13.5 mm
Max Working Pressure (PS) 28 bar (406 psig)
Max Test Pressure 42 bar
Ambient Temp Range -40 to 50 Celsius
Function NC (Normally Closed)
Refrigerant Compatibility R404A, R134a, R407C, R507, etc.
Weight 4.8 kg
Shipping Weight 6.0 kg

Technical FAQs

How does PWM control differ from standard modulating expansion valves?

Standard valves move a needle in and out to restrict flow. PWM valves like the AKV 20-3 cycle between 0% and 100% open. This ensures that the refrigerant velocity is always high when the valve is open, which improves oil return and heat transfer efficiency in the evaporator.

Does this valve require an additional liquid line solenoid?

No. The AKV 20-3 is a Normally Closed (NC) valve that provides a reliable, tight seal when the power is removed. This eliminates the cost and pressure drop associated with an extra solenoid valve in the liquid line.

What is the expected service life of the orifice and needle?

The AKV series is designed for heavy industrial use. The internal components are made from high-grade materials to ensure a service life of over 50 million cycles, provided the system is kept clean and free of moisture.


Engineering & Installation Guide

  • Upstream Filtration Requirements: It is mandatory to install a high-quality filter drier (such as the Danfoss DML or DCL series) immediately before the valve. Because the valve cycles rapidly, any metal shavings or debris in the liquid line can damage the valve seat or cause it to stick, leading to "flooding" or loss of superheat control.

  • Brazing Thermal Protection: During the installation of the solder connections, the valve body must be protected from excessive heat. Wrap the body in a wet cloth and ensure that the temperature of the 13.5 mm actuator housing does not exceed 100 Celsius. Overheating will degrade the internal seals and the solenoid coil interface.

  • Electrical Configuration: Ensure the coil voltage matches the output of your Danfoss AK-CC or AKC controller. The coil must be mounted with the cable entry pointing downwards to prevent moisture from traveling along the wire and into the actuator assembly (drip loop installation).

 

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Gold
Country of origin
United States

Technical knowledge

Derivative Action in PID Control Without Noise Problems

Learn what derivative action contributes to a PID loop, why it can amplify measurement noise and setpoint changes, and how filtering, sampling, and staged tests make D tuning safer.

Designing Industrial Networks That Stay Troubleshootable

A practical guide to segmenting, documenting, and testing industrial Ethernet networks so plant teams can isolate faults quickly, control change, and expand without creating fragile dependencies.

Commissioning IO-Link From Master Ports to IODD Data

Commission IO-Link systematically from master addressing and port modes through IODD selection, PLC byte mapping, parameter backups, device validation, and failure-injection tests.

PowerFlex Dynamic Braking Resistor Design and Testing

A practical PowerFlex braking guide covering regenerative energy, resistor resistance and duty cycle, thermal protection, model-specific parameters, and measured commissioning tests.

Engineering Industrial Joystick Controls for Safe Motion

An industrial joystick is only the first element in a safe motion command chain. This guide covers sensing choices, wiring, signal validation, PLC logic, restart behavior, and commissioning for...

Seeing PID Behavior Before Tuning the Loop

PID tuning becomes safer when engineers can see how proportional, integral, and derivative actions reshape error, output, and response over time. This guide turns live trends into a disciplined...