Description
The Allen-Bradley 1746-OW4 is a reliable digital contact output module designed specifically for the Allen-Bradley SLC 500 modular hardware platform. As part of the 1746 I/O product family, this module provides discrete relay output capabilities to interface your controller with high-capacity actuators, control relays, motor starters, and pilot lights across various industrial automation environments.
Featuring isolated relay contacts, the 1746-OW4 accommodates both AC and DC load types, offering versatile signal switching flexibility for complex control panels. It features 4 normally open relay output points, allowing multi-voltage distribution across separate loads without sharing a common power bus. The robust construction ensures dependable operation within standard industrial temperature ranges and vibration tolerances typical of factory floors.
Features
- 4 discrete normally open relay output channels
- Supports multi-voltage operations ranging from 5 to 265VAC and 5 to 125VDC
- Individual output isolation for flexible power zoning
- Compatible with Allen-Bradley SLC 500 fixed and modular rack controllers
- Low backplane current draw from 5VDC and 24VDC system supplies
- Pluggable terminal block for simplified field wiring and maintenance
Applications
- Industrial machinery and discrete manufacturing lines
- HVAC control systems and building automation
- Pump and valve control panels
- Interface between low-voltage controller logic and high-voltage field devices
- Material handling and conveyor systems
Technical Specifications
| Parameter |
Specification |
| Manufacturer |
Allen-Bradley / Rockwell Automation |
| Product Line |
SLC 500 (1746 I/O) |
| Catalog Number |
1746-OW4 |
| Module Type |
Digital Contact (Relay) Output Module |
| Number of Outputs |
4 Normally Open (Isolated) |
| Operating Voltage Range |
5 to 265VAC, 5 to 125VDC |
| Continuous Current per Module |
8.0 A AC / 8.0 A DC max (per common) |
| Signal Delay (Max Resistive Load) |
ON: 10.0 ms / OFF: 10.0 ms |
| Backplane Current Consumption |
0.045 A @ 5VDC; 0.045 A @ 24VDC |
| Off-State Leakage Current |
0 mA max |
| Minimum Load Current |
10 mA @ 5VDC |
| Country of Origin |
United States |
Connections / Interfaces
The module interfaces directly to the SLC 500 backplane via its integrated card-edge connector. Field wiring connects through a removable front-access terminal block, enabling quick module replacement without disturbing existing machine wiring. Each output point provides dedicated screw terminals for high-voltage or low-voltage load connections.
Installation Guidelines
- Always disconnect all external AC and DC power sources from the module and backplane before installing or removing the unit.
- Insert the 1746-OW4 securely into any available I/O slot of an SLC 500 chassis.
- Ensure the module latching mechanism is fully engaged to maintain reliable backplane communication and power continuity.
- Verify that field device current loads do not exceed the per-contact or per-common continuous current ratings.