Description
The Allen-Bradley 1794-OA8I is an 8-point isolated AC digital output module for the FLEX I/O system. It provides eight individually isolated output channels for switching 85 to 132 VAC field loads.
Each output is rated for up to 0.5 A at 55 degC. The module supports a maximum combined output current of 4 A when all eight channels operate at 0.5 A.
Channel-to-channel isolation separates the individual AC output circuits. The field circuits are also isolated from the FLEX I/O backplane.
The 1794-OA8I is designed for distributed digital output applications requiring independently isolated 120 VAC load control within a FLEX I/O station.
Features
-
Eight isolated AC digital output channels
-
85 to 132 VAC output voltage range
-
120 VAC nominal output type
-
0.5 A maximum per output at 55 degC
-
4 A maximum output current per module
-
Individual channel-to-channel isolation
-
Field-to-backplane isolation
-
FLEX I/O distributed I/O architecture
-
Removal and Insertion Under Power capability
-
Operating temperature range from 0 to 55 degC
-
Individual field wiring through the FLEX I/O terminal base system
Applications
-
AC solenoid valve control
-
Contactor and relay coil switching
-
Machine actuator control
-
Distributed 120 VAC digital output stations
-
Isolated field-load switching
-
FLEX I/O expansion in industrial control systems
Technical Specifications
General
| Parameter |
Specification |
| Manufacturer |
Allen-Bradley |
| Catalog Number |
1794-OA8I |
| Product Family |
FLEX I/O |
| Product Type |
Isolated AC Digital Output Module |
| Number of Outputs |
8 |
| Output Type |
120 VAC |
| Isolation |
Individual isolated outputs |
| Country of Origin |
Singapore |
| UPC |
612598179954 |
| Lifecycle Status |
Active Mature |
Electrical
| Parameter |
Specification |
| Output Voltage Range |
85 to 132 VAC |
| Nominal Output Voltage |
120 VAC |
| Minimum On-state Current |
5 mA per output |
| Maximum On-state Current |
0.5 A per output at 55 degC |
| Maximum Module Output Current |
4 A |
| Maximum On-state Voltage Drop |
1.0 V at 0.5 A |
| Maximum Off-state Leakage Current |
2.25 mA |
| Maximum Surge Current |
7 A for 45 ms, repeatable every 8 seconds |
| Field-to-Backplane Isolation |
120 V continuous |
| Channel-to-Channel Isolation |
120 V continuous |
| Isolation Test Voltage |
1250 VAC for 60 seconds |
Environmental
| Parameter |
Specification |
| Operating Temperature |
0 to 55 degC (32 to 131 degF) |
Connections / Interfaces
The 1794-OA8I connects to field devices through a compatible FLEX I/O terminal base arrangement.
Each output channel is electrically isolated. Separate AC sources are required for individual channels where channel-to-channel isolation must be maintained.
Field wiring should follow the applicable Rockwell Automation 1794-OA8I wiring diagram and terminal-base documentation.
Installation & Commissioning
-
Verify the catalog number and 85 to 132 VAC field-load requirement before installation.
-
Confirm the selected FLEX I/O terminal base and wiring arrangement.
-
Verify load current remains within the output and module current limits.
-
Preserve channel isolation where the application requires isolated AC circuits.
-
Check field wiring before applying AC power to the outputs.
-
Verify each output independently during commissioning.
-
Confirm PLC output commands correspond with the intended field loads.