What Is SCADA? Supervisory Control Without Replacing the PLC
SCADA sits above PLCs and RTUs: it acquires field data, alarms operators, and issues supervisory commands across plants and remote assets—without replacing local deterministic control.

Designed for space-saving DIN rail mounting, the Beckhoff CX5120-0100 serves as a robust fanless controller within the CX5100 Embedded PC series. This industrial PC features an energy-efficient Intel Atom E3815 single-core processor operating at 1.46 GHz, making it well-suited for medium-scale automation tasks requiring direct EtherCAT or Bus Terminal integration. The module includes dual independent Gigabit Ethernet ports, USB 2.0 connectivity, and a DVI-D display interface, allowing for direct visual monitoring and fast network integration.
The controller is equipped with 2 GB of non-expandable DDR3 RAM and features separate slots for CFast and microSD cards to manage operating systems and application data. An integrated 1-second UPS protects volatile memory by saving up to 1 MB of persistent data to the CFast card during power loss events. For flexible I/O configurations, the CX5120-0100 automatically detects and supports either E-bus (EtherCAT) or K-bus (Bus Terminals) connections. Note that this specific model variant is delivered without a pre-installed operating system or TwinCAT runtime license, allowing custom software provisioning.
| Order Code | Description |
|---|---|
| CX5120-0100 | Embedded PC, Intel Atom E3815 1.46 GHz, 2 GB RAM, no OS, no TwinCAT |
| CX2900-0107 | Factory option for ATEX, IECEx, and cFMus hazardous area certifications |
| Technical Parameter | Specification Value |
|---|---|
| Manufacturer | BECKHOFF |
| Model / Part Number | CX5120-0100 |
| Processor Type | Intel Atom E3815, 1.46 GHz, 1 Core |
| System Memory | 2 GB DDR3 RAM (non-expandable) |
| Flash Storage Interfaces | 1 x CFast card slot, 1 x microSD card slot |
| Persistent Memory | Integrated 1-second UPS, 1 MB on CFast card |
| Operating System | None (Without Operating System) |
| TwinCAT Platform Level | Performance (40), TwinCAT license not included |
| I/O Interface Support | E-bus (EtherCAT) or K-bus (Bus Terminal), automatic detection |
| Network Interfaces | 2 x RJ45 10/100/1000 Mbit/s (independent) |
| Display Interface | 1 x DVI-D |
| Peripheral Interfaces | 4 x USB 2.0, 1 x Optional interface slot |
| Input Supply Voltage | 24 V DC (-15% / +20%) |
| Current Supply (E-bus/K-bus) | 2 A |
| Power Consumption | 11 W maximum (18 W maximum when loading UPS) |
| Diagnostics Indicator | 1 x Power, 1 x TC Status, 1 x Flash Access, 2 x Bus Status |
| System Clock | Internal battery-backed real-time clock (exchangeable battery) |
| Dimensions (W x H x D) | 122 mm x 100 mm x 92 mm |
| Unit Weight | 975 g |
| Operating Temperature | -25 to +60 degC |
| Storage Temperature | -40 to +85 degC |
| Relative Humidity | 95%, non-condensing |
| Protection Rating | IP20 |
| Vibration Resistance | Conforms to EN 60068-2-6 |
| Shock Resistance | Conforms to EN 60068-2-27 |
| EMC Immunity / Emission | Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Connector / Interface | Function Description |
|---|---|
| RJ45 Port 1 & 2 | Gigabit Ethernet (10/100/1000 Base-T) interfaces for network connection |
| DVI-D Port | Digital display interface output for local HMI visual panels |
| USB Ports (4x) | USB 2.0 interface ports for connecting mouse, keyboard, or storage |
| Option Slot | Configurable interface port for optional Fieldbus master/slave connections |
| Bus Extension Interface | Automatic termination interface for Beckhoff E-bus or K-bus terminals |
Global Express Shipping
Returns & Warranty
Orders are processed and delivered Monday-Friday (excluding public holidays).
For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .
| Country of origin |
Germany
|