Commissioning AS-Interface Networks Without Guesswork
A practical AS-Interface commissioning method covering topology, power and voltage-drop checks, addressing, PLC mapping, fault tests and maintenance records for reliable actuator-sensor networks.
Manufacturer: BECKHOFF
Product No.: CX5130-0122
Country of origin:Germany
Product Type: Embedded PCs
Payment: T/T, Western Union
Weight: 500g
Dimensions: 142 mm x 100 mm x 92 mm
Shipping port: Xiamen
Warranty: 12 months
Executing high-performance automation control tasks directly at the machine level, the Beckhoff CX5130-0122 functions as a robust, DIN-rail mountable Embedded PC equipped with an Intel Atom E3827 dual-core processor. This unit integrates dual independent Gigabit Ethernet interfaces and a built-in 1-second UPS to guarantee data integrity during sudden power disruptions.
| Parameter | Specification |
|---|---|
| Manufacturer | Beckhoff |
| Model Number | CX5130-0122 |
| Processor | Intel Atom E3827 (2 Cores, 1.75 GHz) |
| System Memory | 4 GB DDR3 RAM (Non-expandable) |
| Flash Memory Slots | 1 x CFast slot, 1 x microSD slot (Cards not included) |
| Persistent Memory | Integrated 1-second UPS (1 MB on CFast card) |
| I/O Bus Connection | E-bus (EtherCAT) or K-bus (Bus Terminals), automatic recognition |
| Bus Current Supply | 2 A maximum |
| Supply Voltage | 24 V DC (-15% / +20%) |
| Power Consumption | 14 W typical, 20 W maximum (during UPS charging) |
| TwinCAT Platform Level | Performance (Platform Level 40) |
| Operating Temperature | -25 degC to +60 degC |
| Storage Temperature | -40 degC to +85 degC |
| Protection Rating | IP20 |
| Dimensions (W x H x D) | 142 mm x 100 mm x 92 mm |
| Net Weight | 1095 g |
| Shipping Weight (Calculated) | 3.0 kg |
| Country of Origin | Germany |
| Interface / Port | Function / Assignment |
|---|---|
| 2 x RJ45 Ports | 10/100/1000 Mbit/s independent Ethernet interfaces for network separation. |
| 1 x DVI-I | Connection for external Beckhoff Control Panel or standard digital/analog monitor. |
| 4 x USB 2.0 | Peripheral connections for input devices, flash drives, or external hardware. |
| Power Terminal | 24 V DC power input connection with integrated ground terminal. |
The CX5130-0122 is positioned within the CX5100 series as a dual-core alternative to the single-core CX5120 and the quad-core CX5140. It operates at TwinCAT 3 Platform Level 40 (Performance). Ensure that your TwinCAT runtime licenses are compiled specifically for Platform Level 40 to avoid deployment errors.
The integrated 1-second UPS relies on internal capacitive storage to write up to 1 MB of persistent data to the CFast card. If the CFast card is replaced with a non-industrial grade card lacking high write-endurance, or if the FB_S_UPS function block is not properly called in the TwinCAT PLC project, persistent data will not be saved during a power loss.
When transitioning between E-bus and K-bus terminals, ensure the system is completely powered down. The CX5130 automatically detects the bus type on startup. If the bus terminal line is not terminated with an end terminal (such as KL9010 or EL9011), the CPU will flag a bus error and refuse to enter Run mode.
DANGER: HIGH RISK OF ELECTRICAL SHOCK AND COMPONENT DAMAGE. Always isolate all 24 V DC power sources before mounting, wiring, or inserting/removing CFast cards. Failure to de-energize the system can corrupt the operating system image on the flash media or damage the internal E-bus/K-bus interface circuitry.
Mount the CX5130 vertically on a standard 35 mm DIN rail (EN 60715), ensuring at least 30 mm of free space above and below the unit for natural convection cooling.
Connect the functional ground terminal directly to the low-impedance system ground plane to minimize electromagnetic interference.
Insert a compatible, pre-configured Beckhoff CFast card containing the operating system and TwinCAT runtime into the designated slot.
Wire the 24 V DC power supply to the power input terminals, verifying correct polarity before switching on the main breaker.