BECKHOFF

BECKHOFF EL3612 EtherCAT Terminal

SKU EL3612

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: EL3612

  • Country of origin:Germany

  • Product Type: EtherCAT Terminals

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The BECKHOFF EL3612 is a 2-channel analog input terminal designed for high-precision current measurement within EtherCAT automation systems. Engineered with differential input technology, this terminal processes 0 to 20 mA signals with a high resolution of 24 bits, making it suitable for demanding industrial measurement and control tasks requiring strict accuracy.

System communication and internal powering are handled directly via the E-bus, integrating smoothly into modular terminal assemblies. The device features configurable conversion times, selectable input filter limit frequencies, and diagnostic capabilities, allowing engineers to adapt signal processing characteristics to specific application requirements.

Features

  • Two differential analog input channels for 0 to 20 mA current signals
  • High-precision measurement with 24-bit resolution including sign
  • Configurable conversion time ranging from 1 to 400 ms
  • Selectable input filter limit frequency up to 3 kHz
  • E-bus powered terminal design with integrated electrical isolation between channels and the E-bus
  • Compact polycarbonate housing featuring signal LEDs for operational status monitoring

Applications

  • Precision industrial process monitoring and control
  • Sensor signal acquisition in test stands and laboratory automation
  • Data logging applications requiring high measurement accuracy
  • Machine-building automation systems utilizing EtherCAT networks

Technical Specifications

General

Parameter Specification
Manufacturer BECKHOFF
Exact Model EL3612
Product Type EtherCAT Terminal
Number of Inputs 2 (differential)
Country of Origin Germany

Electrical

Parameter Specification
Signal Type Differential current
Signal Current 0…20 mA
Power Supply Via the E-bus
Current Consumption E-bus Typ. 190 mA
Internal Resistance Typ. 85 ohm + diode voltage
Common-Mode Voltage UCM Max. 10 V
Electrical Isolation 500 V (E-bus/signal voltage)

Performance

Parameter Specification
Resolution 24 bit (incl. sign)
Conversion Time 1…400 ms configurable
Measuring Error < ±0.01 % at 25 degC (relative to full scale value, 50 Hz filter)
Input Filter Limit Frequency 3 kHz
Crosstalk Attenuation > 60 dB

Mechanical and Environment

Parameter Specification
Design Form Compact terminal housing with signal LEDs
Material Polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Net Weight Approx. 60 g
Mounting On 35 mm DIN rail, conforming to EN 60715 with lock
Protection Rating IP20
Operating Temperature Range -25…+60 degC
Storage Temperature Range -40…+85 degC
Relative Humidity 95 %, no condensation
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4

Connection Technology

Parameter Specification
Connection Cross-Section Solid (s) 0.08…2.5 mm² (AWG 28…14)
Connection Cross-Section Stranded (st) 0.08…2.5 mm² (AWG 28…14)
Connection Cross-Section with Ferrule (f) 0.14…1.5 mm² (AWG 26…16)
Stripping Length 8…9 mm

Installation Guidelines

  1. Ensure the entire control system is safely powered down and isolated from electrical energy before performing any mechanical or electrical work.
  2. Inspect the BECKHOFF EL3612 terminal housing and connection points for any signs of transit damage.
  3. Mount the terminal onto a standard 35 mm DIN rail conforming to EN 60715, ensuring the locking mechanism engages securely.
  4. Connect field sensors to the appropriate terminal points using solid or stranded conductors with proper stripping lengths and ferrule use where required.
  5. Verify that all signal wiring and shield connections adhere to local electrical codes and EMC requirements.
  6. Power on the EtherCAT network and verify proper diagnostic LED operation through the TwinCAT engineering environment before initiating normal system operation.

FAQ

What are the primary electrical specifications and input channels of the BECKHOFF EL3612?

The BECKHOFF EL3612 is a 2-channel analog input terminal designed specifically for processing differential 0 to 20 mA current signals. It features an internal resistance of typically 85 ohms plus diode voltage and supports a maximum common-mode voltage of 10 V. The unit ensures robust operation with a 500 V electrical isolation between the E-bus and the signal voltage.

What kind of measurement precision and resolution does the BECKHOFF EL3612 offer?

The BECKHOFF EL3612 provides an exceptionally high resolution of 24 bits including the sign for precise analog measurements. It delivers a measuring error of less than ±0.01% at 25 degrees Celsius relative to the full scale value using a 50 Hz filter. Furthermore, engineers can configure the conversion time from 1 to 400 ms and utilize an input filter limit frequency of up to 3 kHz.

How is the BECKHOFF EL3612 powered and integrated into an automation network?

The BECKHOFF EL3612 draws its power directly through the E-bus with a typical current consumption of 190 mA. It integrates seamlessly into modular EtherCAT terminal assemblies and mounts easily onto standard 35 mm DIN rails conforming to EN 60715. Signal status monitoring is conveniently handled via integrated LEDs on the compact polycarbonate housing.

What are the environmental and physical limitations of the BECKHOFF EL3612 terminal?

The BECKHOFF EL3612 operates reliably in ambient temperatures ranging from -25 to +60 degrees Celsius and can be stored safely between -40 and +85 degrees Celsius. It is built within a compact IP20-rated polycarbonate enclosure measuring 12 mm by 100 mm by 68 mm with a net weight of approximately 60 grams. The device also complies with strict industrial standards for vibration, shock resistance, and EMC immunity.

View all FAQs →

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Commissioning PLX32-EIP-MBTCP: Subnets, Registers, and RPI

A commissioning checklist for the ProSoft PLX32-EIP-MBTCP covering subnet separation, register contracts, EtherNet/IP timing, failure tests and replacement records.

Diagnosing IC693MDL916 Relay Outputs Before Module Replacement

A field checklist for IC693MDL916 relay commands, terminal blocks, load current, switching rate and contact-side measurements.

Troubleshooting Beckhoff KL1512 Counter Inputs and Mapping

A field checklist for KL1512 signal thresholds, counter direction, process data and the KL1512-to-KS1512 wiring difference.

Troubleshooting Beckhoff EPP2008-0001 Output Faults

A field checklist for EPP2008-0001 current limits, supply voltage, channel LEDs, connector coding and load-related output faults.

Moving TwinCAT 3 Licenses with C9900-L100: Build and Device Checks

Before moving a TwinCAT 3 license with a Beckhoff C9900-L100, verify the TwinCAT build, XML device description, exact order code and cabinet limits.

Replacing a Beckhoff EL4032: Wiring and Output Checks

A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.