Description

The BECKHOFF EL3702 is a high-performance 2-channel analog input terminal designed for high-speed, high-precision voltage measurements. Operating within the modular EtherCAT I/O system, this terminal supports differential signal acquisition in the range of -10 to +10 V with 16-bit resolution. It is engineered specifically for dynamic measurement tasks requiring synchronous, high-frequency data collection across distributed control systems.

A key capability of the BECKHOFF EL3702 is its support for oversampling technology. This allows the terminal to sample analog input values at rates far higher than the master control cycle time. By utilizing EtherCAT Distributed Clocks (DC), the acquired measurements are precisely timestamped and synchronized across the network with sub-microsecond precision, making it an excellent choice for detailed signal analysis and transient state monitoring.

Features

  • Two differential analog input channels designed for ±10 V voltage signals.
  • Oversampling technology with a selectable factor (n = 1 to 100) for custom data acquisition profiles.
  • Maximum sampling rate of 10 microseconds (100 ksamples/s) per channel, executed simultaneously.
  • 16-bit analog-to-digital conversion resolution (including sign) for high-fidelity signal reconstruction.
  • Integrated Distributed Clocks (DC) support, delivering synchronization precision of less than 1 microsecond.
  • 500 V electrical isolation between the E-bus logic and the incoming signal voltage.
  • Compact 12 mm housing with status LEDs indicating operational and diagnostic states.

Applications

  • High-speed transient signal and wave recording.
  • Vibration analysis, acoustic measurement, and structural health monitoring.
  • Dynamic force, pressure, or torque monitoring in test benches.
  • Fast closed-loop control systems where low-latency feedback is critical.
  • Quality control systems requiring high-frequency sensor signal analysis.

Technical Specifications

General

Parameter Specification
Manufacturer BECKHOFF
Model EL3702
Product Type EtherCAT Terminal
Design Form Compact terminal housing with signal LEDs
Material Polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Installation 35 mm DIN rail (EN 60715) with locking mechanism
Weight Approx. 60 g

Signal and I/O

Parameter Specification
Number of Inputs 2 (differential)
Signal Type Differential voltage
Signal Voltage Range -10 V to +10 V
Internal Resistance > 200 kOhm
Input Filter Limit Frequency 80 kHz
Recommended Input Bandwidth 0 to 30 kHz
Common-Mode Voltage (UCM) Max. 35 V

Electrical

Parameter Specification
Power Supply Via the E-bus
Current Consumption (E-bus) Typ. 200 mA
Current Load Power Contacts Max. 10 A
Electrical Isolation 500 V (E-bus / signal voltage)

Performance and Synchronization

Parameter Specification
Conversion Time ~ 10 microseconds per sample
Resolution 16 bit (including sign)
Maximum Sampling Rate 10 microseconds / 100 ksps per channel, simultaneous
Oversampling Factor (n) 1 to 100 (selectable)
Measuring Error (up to 10 Hz) < ±0.3% (relative to full scale value)
Distributed Clocks (DC) Yes
Distributed Clock Precision << 1 microsecond
Process Image Width Input: n x 2 x 16 bit data; optional 2 x 16 bit cycle counter, 4 byte StartNextLatch time

Connection

Parameter Specification
Wiring Technology Spring actuation by screwdriver
Conductor Cross-Section (Solid/Stranded) 0.08 to 2.5 mm² (AWG 28 to 14)
Conductor Cross-Section (With Ferrule) 0.14 to 1.5 mm² (AWG 26 to 16)
Stripping Length 8 to 9 mm

Environmental and Safety

Parameter Specification
Operating Temperature -25 to +60 Celsius
Storage Temperature -40 to +85 Celsius
Relative Humidity 95%, non-condensing
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20
Installation Position Variable
Approvals and Markings CE, UL, ATEX, IECEx, cFMus

Installation Guidelines

  1. De-energize the System: Always disconnect the power supply to the entire bus terminal block before inserting, removing, or wiring any module.
  2. DIN Rail Mounting: Slide the EL3702 terminal onto a standard 35 mm DIN rail (EN 60715) until the lock clicks securely into place.
  3. Terminal Connection: Ensure the terminal is pushed flush against adjacent modules to guarantee reliable contact for the E-bus and potential connections.
  4. Wiring: Insert a suitable screwdriver into the release slot to open the spring clamp, feed the stripped conductor (8 to 9 mm) into the contact point, and release. Use shielded cables for analog signals to minimize electromagnetic interference.
  5. Configuration: Scan the terminal in the TwinCAT System Manager, select the required oversampling factor, and link the resulting process image variables to your control application.

FAQ

What is the main function of the BECKHOFF EL3702?

The BECKHOFF EL3702 is a 2-channel analog input EtherCAT Terminal designed for high-speed acquisition of voltage signals in the range of ±10 V using differential input technology and oversampling capabilities.

What is the maximum sampling rate of the BECKHOFF EL3702?

The BECKHOFF EL3702 supports a maximum sampling rate of 10 microseconds (100 ksamples/s) per channel simultaneously, depending on the chosen oversampling factor.

How does oversampling work on the BECKHOFF EL3702?

The BECKHOFF EL3702 registers multiple analog measurements within a single PLC cycle (using an oversampling factor of 1 to 100) and transmits them in a structured packet back to the controller via EtherCAT.

Does the BECKHOFF EL3702 support Distributed Clocks (DC)?

Yes, the BECKHOFF EL3702 supports EtherCAT Distributed Clocks (DC), enabling synchronization precision of significantly less than 1 microsecond across all networked nodes.

What are the power requirements for the BECKHOFF EL3702?

The BECKHOFF EL3702 is powered directly from the E-bus backplane with a typical current consumption of 200 mA; it does not draw current from the external field-side power contacts.

View all FAQs →

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Commissioning PLX32-EIP-MBTCP: Subnets, Registers, and RPI

A commissioning checklist for the ProSoft PLX32-EIP-MBTCP covering subnet separation, register contracts, EtherNet/IP timing, failure tests and replacement records.

Diagnosing IC693MDL916 Relay Outputs Before Module Replacement

A field checklist for IC693MDL916 relay commands, terminal blocks, load current, switching rate and contact-side measurements.

Troubleshooting Beckhoff KL1512 Counter Inputs and Mapping

A field checklist for KL1512 signal thresholds, counter direction, process data and the KL1512-to-KS1512 wiring difference.

Troubleshooting Beckhoff EPP2008-0001 Output Faults

A field checklist for EPP2008-0001 current limits, supply voltage, channel LEDs, connector coding and load-related output faults.

Moving TwinCAT 3 Licenses with C9900-L100: Build and Device Checks

Before moving a TwinCAT 3 license with a Beckhoff C9900-L100, verify the TwinCAT build, XML device description, exact order code and cabinet limits.

Replacing a Beckhoff EL4032: Wiring and Output Checks

A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.