BECKHOFF

BECKHOFF EL4114-0020 EtherCAT Terminal

SKU EL4114-0020

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: EL4114-0020

  • Country of origin:Germany

  • Product Type: EtherCAT Terminals

  • Payment: T/T, Western Union

  • Weight: 65g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The BECKHOFF EL4114-0020 is a high-precision, 4-channel analog output EtherCAT Terminal designed for generating accurate current signals within industrial control systems. Operating in the range of 0 to 20 mA, this specialized terminal features 16-bit resolution and comes factory calibrated to ensure exceptional signal fidelity and minimal output error.

Compared to standard analog output models, the BECKHOFF EL4114-0020 variant is optimized for demanding automation and testing environments where high-precision control loop feedback is mandatory. Its integration into the EtherCAT system allows for fast, deterministic signal transmission, making it a reliable component in multi-axis machinery and distributed process systems.

With built-in support for Distributed Clocks (DC), the terminal enables synchronized output actions across the entire network with sub-microsecond precision. The 2-wire connection layout allows for a clean, space-saving arrangement within standard terminal boxes and electrical enclosures.

Features

  • 4 analog output channels delivering current signals from 0 to 20 mA
  • Enhanced 16-bit signal resolution for high-accuracy setpoint adjustment
  • Factory calibrated with an individual calibration certificate included
  • Distributed Clocks (DC) compatibility for highly synchronized output updates
  • Short-circuit proof current outputs supporting loads up to 350 Ohms
  • Parameterizable watchdog function to handle communication interruptions safely
  • Compact 12 mm terminal housing with integrated status LEDs

Applications

  • High-precision control valve and actuator positioning
  • Current-loop feedback signal generation for variable frequency drives
  • Test benches and simulation environments requiring precise physical signal emulation
  • Process engineering systems requiring continuous and synchronized setpoint signals

Technical Specifications

General Specifications

Parameter Specification
Manufacturer BECKHOFF
Exact Model EL4114-0020
Product Type EtherCAT Terminal
Number of Channels 4
Signal Current 0 to 20 mA
Connection Technology 2-wire, single-ended

Electrical Specifications

Parameter Specification
Power Supply 24 V DC via power contacts
Current Consumption (E-Bus) typ. 160 mA
Current Consumption (Power Contacts) typ. 15 mA + load
Electrical Isolation 500 V (E-bus / signal voltage)
Current Load Power Contacts max. 10 A

Performance Specifications

Parameter Specification
Resolution 16-bit (including sign)
Load Resistance < 350 Ohm (short-circuit proof)
Output Error < 0.1% (relative to end value)
Output Rate max. 4 ksps
Distributed Clocks (DC) Yes (precision << 1 µs)
Calibration Factory calibrated with calibration certificate

Physical and Environmental Data

Parameter Specification
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Weight approx. 65 g
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95%, non-condensing
Protection Class IP20
Mounting 35 mm DIN rail (EN 60715) with lock

Installation Guidelines

  1. Ensure the system is completely de-energized before mounting or removing the EtherCAT terminal.
  2. Mount the terminal on a standard 35 mm DIN rail conforming to EN 60715. Use the integrated locking mechanism and slot-and-key connection for side-by-side terminal mounting.
  3. Ensure secure electrical connection via the gold-plated E-bus power contacts. Do not clean contacts with abrasive tools.
  4. Strip conductors to a length of 8 to 9 mm. Terminate using solid wire, stranded wire, or wire-end ferrules through the spring actuation mechanism.
  5. Perform electrical and functional testing on the signal lines before energizing the control system.

Replacement Recommendations

When replacing an existing terminal with the BECKHOFF EL4114-0020, verify that the 16-bit configuration and mapping match your TwinCAT process image settings, particularly if replacing a standard 12-bit output terminal. Ensure that the individual calibration requirements of your application are verified and documented with the newly supplied factory certificate details.

Compliance and Certifications

Parameter Specification
Approvals CE, UL, ATEX
Ex Marking II 3 G Ex nA IIC T4 Gc
EMC Standards Conforms to EN 61000-6-2 and EN 61000-6-4

FAQ

What is the key difference between the BECKHOFF EL4114-0020 and the standard EL4114?

The BECKHOFF EL4114-0020 features a higher 16-bit resolution (including sign) and is factory calibrated with an individual calibration certificate, whereas the standard EL4114 has a 12-bit resolution and standard factory tuning.

Does the BECKHOFF EL4114-0020 support Distributed Clocks (DC)?

Yes, the BECKHOFF EL4114-0020 fully supports Distributed Clocks (DC) with synchronization precision of less than 1 microsecond for precise, deterministic control loops.

What is the maximum load resistance supported by this terminal?

The BECKHOFF EL4114-0020 supports a maximum load resistance of up to 350 Ohms per channel, and the analog current outputs are short-circuit proof.

Which wire sizes are compatible with the connection points on this terminal?

The BECKHOFF EL4114-0020 supports solid or stranded conductors with cross-sections from 0.08 to 2.5 mm² (AWG 28 to 14), and flexible conductors with ferrules from 0.14 to 1.5 mm² (AWG 26 to 16).

Does the EL4114-0020 terminal require a separate power supply for the outputs?

Yes, power is supplied to the field-side electronics of the BECKHOFF EL4114-0020 via the 24 V DC power contacts of the adjacent potential feed terminal.

View all FAQs →

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

Moving TwinCAT 3 Licenses with C9900-L100: Build and Device Checks

Before moving a TwinCAT 3 license with a Beckhoff C9900-L100, verify the TwinCAT build, XML device description, exact order code and cabinet limits.

Replacing a Beckhoff EL4032: Wiring and Output Checks

A field checklist for replacing a Beckhoff EL4032, covering the ±10 V load, terminal map, power contacts, EtherCAT state, and watchdog behavior.

Replacing Yokogawa AAI835: Wiring and Barrier Checks Before Swap

Before replacing a Yokogawa AAI835, verify the 4-in/4-out channel map, power-loss loop behavior, barrier type, output load, cable, and redundancy.

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.