Description
Designed for highly precise industrial signal processing, the BECKHOFF EL4114 analog output terminal generates analog control currents in the 0 to 20 mA range. This 4-channel output module features a high 16-bit resolution, delivering accurate control variables directly to field devices such as proportional valves, variable speed drives, and process indicators. Integrating natively into the EtherCAT high-speed communication network, the terminal supports Distributed Clocks (DC) to achieve synchronization precision of less than 1 microsecond, making it ideal for highly synchronized multi-axis control loops and demanding automation processes.
The compact 12 mm housing includes diagnostic LEDs indicating active status and communication states. The EL4114 utilizes 2-wire, single-ended connection technology, allowing for clean, space-saving cabinet layouts. Integrated parameterizable watchdog timers ensure safe fall-back states in the event of a control bus interruption.
Features
- Four analog output channels processing standard 0 to 20 mA signals.
- High-resolution 16-bit digital-to-analog conversion for fine control increments.
- EtherCAT Distributed Clocks (DC) support with precision under 1 µs.
- 2-wire, single-ended wiring configuration.
- Short-circuit proof outputs with a maximum load capacity of 350 ohms.
- Configurable watchdog parameters for safety during communication faults.
- Robust electrical isolation of 500 V between the internal E-bus and signal channels.
Applications
- Proportional valve control and actuator positioning.
- Speed referencing for variable frequency drives (VFDs) and motor controllers.
- Analog signal transmission to remote recorders or data acquisition units.
- Process loop control in oil & gas, water treatment, and power generation.
Technical Specifications
| Manufacturer |
BECKHOFF |
| Part Number / Model |
EL4114 |
| Number of Outputs |
4 |
| Signal Current |
0 to 20 mA |
| Resolution |
16 bit (including sign) |
| Connection Technology |
2-wire, single-ended |
| Power Supply |
24 V DC via power contacts |
| Distributed Clocks |
Yes (precision < 1 µs) |
| Load Resistance |
< 350 Ohm (short-circuit proof) |
| Output Error |
< 0.1% (relative to end value) |
| Output Rate |
Max. 4 ksps |
| Electrical Isolation |
500 V (E-bus / signal voltage) |
| Current Consumption Power Contacts |
Typ. 15 mA + load |
| Current Consumption E-bus |
Typ. 160 mA |
| Process Image Bit Width |
4 x 16 bit AO output |
| Operating Temperature |
0 to +55 degC |
| Storage Temperature |
-25 to +85 degC |
| Relative Humidity |
95%, non-condensing |
| Vibration/Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity/Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Protection Rating |
IP20 |
| Dimensions (W x H x D) |
12 mm x 100 mm x 68 mm |
| Weight |
Approx. 65 g |
Connections and Interfaces
| Conductor Type |
Cross-section Range |
AWG Range |
| Solid Conductor (e) |
0.08 to 2.5 mm² |
AWG 28 to 14 |
| Stranded Conductor (st) |
0.08 to 2.5 mm² |
AWG 28 to 14 |
| Flexible Conductor with Ferrule (f) |
0.14 to 1.5 mm² |
AWG 26 to 16 |
Note: Stripping length for terminals is 8 to 9 mm. Wire release via spring-actuated mechanism using a standard screwdriver.
Installation Guidelines
- Mount vertically on standard 35 mm DIN rails conforming to EN 60715 using the integrated locking mechanism.
- Ensure secure side-by-side connection using the built-in double slot and key system on the terminal housing.
- An IP20 rated enclosure must be utilized to safeguard against environmental contaminants and conductive dust.
- Avoid routing sensitive analog signal lines parallel to high-voltage power cables to minimize EMI coupling.
Compliance and Certifications
- CE
- UL
- ATEX: II 3 G Ex nA IIC T4 Gc