1 of 1

Beckhoff EL9222-5500 Overcurrent Protection Terminal

Beckhoff EL9222-5500 Overcurrent Protection Terminal

Only 10 item(s) left in stock
  • Manufacturer: BECKHOFF

  • Product No.: EL9222-5500

  • Country of origin:Germany

  • Product Type: Overcurrent protection terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

The EL9222-5500 is a 2-channel overcurrent protection terminal for 24 V DC applications, designed to provide precise electronic circuit protection within the Beckhoff EtherCAT terminal system. This terminal features an adjustable rated current from 1 A to 10 A in 1 A steps, with a maximum total sum current of 10 A. The module integrates advanced monitoring functions, including a 90% advance warning output load and an integrated 15 A fail-safe element per channel, ensuring operational reliability and equipment safety in industrial automation environments.

Features

  • 2-channel overcurrent protection
  • Adjustable rated current: 1…10 A (in 1 A steps)
  • Total sum current (∑) up to 10 A
  • 90% load advance warning output
  • Integrated 15 A (F) fail-safe element
  • Output 1 contact available via power contact
  • LED button for status monitoring and control
  • Electrical isolation: 500 V (E-bus/signal voltage)

Technical Specifications

Feature Specification
Manufacturer Beckhoff
Technology Overcurrent protection terminal 24 V DC
Number of Channels 2
Nominal Voltage 24 V DC
Rated Current Adjustable 1…10 A (in 1 A steps)
Total Current (∑) Max. 10 A
E-bus Consumption Typ. 80 mA
Electrical Isolation 500 V (E-bus/signal voltage)
Dimensions 12 mm x 100 mm x 68 mm
Weight Approx. 55 g
Operating Temperature 0…+55 degC
Storage Temperature -25…+85 degC
Protection Rating IP20
Approvals CE, cULus, cURus

Installation Guidelines

  • Mounting: Designed for installation on 35 mm DIN rails conforming to EN 60715 with a secure locking mechanism.
  • Side-by-Side Mounting: Utilizes a double slot and key connection system for rigid terminal block assembly.
  • Wiring: Supports solid (s), stranded (st), and ferrule (f) conductors. Spring actuation is performed using a screwdriver.
  • Connection Cross-sections:
    • Solid/Stranded: 0.08…2.5 mm² (AWG 28…14)
    • With Ferrule: 0.14…1.5 mm² (AWG 26…16)
  • Stripping Length: 8…9 mm.
  • Safety: Ensure proper grounding and verify that total load does not exceed the specified ∑ 10 A limit.

What is the adjustable current range for the EL9222-5500?

The rated current is adjustable from 1 A to 10 A in 1 A increments.

Does this terminal include fail-safe protection?

Yes, it features an integrated 15 A (F) fail-safe element for each of the two channels.

What are the physical dimensions of the terminal?

The dimensions are 12 mm x 100 mm x 68 mm.

What is the operating temperature range?

The terminal is designed to operate between 0 degC and +55 degC.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Greyish White
Country of origin
Germany

Recently Viewed Products

Technical knowledge

Modernizing Bailey INFI 90 Symphony HMIs Running on OpenVMS Alpha

A practical guide to replacing aging Bailey Symphony operator stations running on OpenVMS Alpha. It compares Alpha emulation, OpenVMS x86 migration, OPC re-platforming, and phased ABB modernization.

Why Maintenance Data Is Essential for Industrial Reliability

Maintenance data connects work orders, sensor signals, asset history, costs, and technician knowledge. Used well, it improves planning, reliability, predictive maintenance, spare-parts control, and...

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...