Description
The BECKHOFF ELX3204 is a high-precision, 4-channel analog input terminal designed for direct temperature measurement using resistance temperature detectors (RTDs) in hazardous locations. This intrinsically safe (Ex i) EtherCAT Terminal enables sensors located in explosive atmospheres—such as Zone 0/20 or Zone 1/21—to be wired directly to the I/O system, eliminating the need for external barriers or isolation amplifiers.
Equipped with 16-bit resolution, the BECKHOFF ELX3204 delivers highly accurate temperature signals back to the controller. It supports a broad range of standard resistance-based sensors, including platinum and nickel RTDs, as well as direct resistance measurements. Power for the E-bus and the internal electronics is managed safely through the EtherCAT Terminal system in conjunction with an ELX9560 power supply terminal, ensuring electrical safety and signal isolation.
Features
- Four differential analog input channels for RTD sensors and resistance measurements.
- Intrinsically safe (Ex i) design for direct connection to sensors in hazardous zones.
- High-resolution 16-bit analog-to-digital conversion for precise process value monitoring.
- Configurable 2-wire connection technology per channel.
- Integrated limit value monitoring, digital filters, and sensor-specific characteristic curve linearization.
- Diagnostic capabilities supported by integrated signal LEDs indicating channel status and errors.
Applications
- Intrinsically safe temperature monitoring in chemical and petrochemical processing plants.
- Direct RTD sensor interfacing inside explosive gas and dust environments (Zone 0/20, Zone 1/21).
- Oil and gas refinery process automation where explosion protection is required.
- Pharmaceutical processing systems handling volatile solvents.
Technical Specifications
General
| Parameter |
Specification |
| Manufacturer |
BECKHOFF |
| Model |
ELX3204 |
| Product Type |
EtherCAT Terminal, Analog Input, Ex i |
| Number of Inputs |
4 differential inputs |
| Design Form |
Compact terminal housing with signal LEDs |
| Material |
Polycarbonate |
Electrical and Power
| Parameter |
Specification |
| Power Supply |
Via the E-bus |
| Supply Voltage Electronics |
24 V DC (via power contacts), ELX9560 power supply required |
| Current Consumption E-bus |
typ. 70 mA |
| Current Consumption Power Contacts |
typ. 10 mA |
| Power Contacts |
2 blade/spring contacts |
Signal and Measurement
| Parameter |
Specification |
| Sensor Types |
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, KT(Y) sensors, resistance (10 Ohm to 4 kOhm) |
| Connection Method |
2-wire |
| Temperature Range (Pt sensors) |
-200 to +850 degC |
| Temperature Range (Ni sensors) |
-60 to +250 degC |
| Resolution |
16 bit (up to 0.01 degC per digit; preset: 0.1 degC per digit) |
| Measuring Current |
< 1 mA (depending on sensor and measuring range) |
| Measuring Error |
< +-0.3% (relative to full scale value) |
| Internal Resistance |
typ. >= 10 kOhm (differential) |
| Input Filter Limit Frequency |
typ. 1 kHz |
| Conversion Time |
10 to 3300 ms (adjustable, default: 270 ms) |
Mechanical, Environmental, and Connection
| Parameter |
Specification |
| Dimensions (W x H x D) |
12 mm x 100 mm x 68 mm |
| Weight |
approx. 60 g |
| Installation |
On 35 mm DIN rail (EN 60715) with lock |
| Wiring Technology |
Spring actuation by screwdriver |
| Connection Cross-Section (Solid/Stranded) |
0.08 to 2.5 mm² (AWG 28 to 14) |
| Connection Cross-Section (with Ferrule) |
0.14 to 1.5 mm² (AWG 26 to 16) |
| Stripping Length |
8 to 9 mm |
| Operating Temperature |
-25 to +60 degC |
| Storage Temperature |
-40 to +85 degC |
| Relative Humidity |
95 %, non-condensing |
| Protection Rating |
IP20 |
Compliance and Certifications
| Parameter |
Specification |
| Approvals and Markings |
CE, UL, ATEX, IECEx, cFMus, CCC |
| ATEX Protection Class |
II 3(1)G Ex ec [ia Ga] IIC T4 Gc, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I |
| IECEx Protection Class |
Ex ec [ia Ga] IIC T4 Gc, [Ex ia Da] IIIC, [Ex ia Ma] I |
Installation Guidelines
- Ensure the entire automation system and the mounting rack are de-energized before mounting the module.
- Verify that the terminal is correctly mounted on a standard 35 mm DIN rail (EN 60715) using the integrated double slot and key connection.
- Ensure standard Ex i safety spacing and isolation distances are strictly maintained between intrinsically safe and non-intrinsically safe cabling.
- Use a dedicated BECKHOFF ELX9560 power supply terminal to provide compliant E-bus power and safety segregation to the ELX segment.
- Connect the RTD sensors using the designated 2-wire configuration, maintaining appropriate shielding and grounding practices for hazardous locations.
- Confirm that the terminal block is securely locked on the DIN rail and that status LEDs operate correctly upon system initialization.