Decentralized industrial systems requiring high-speed pulse acquisition utilize the IP1502-B200 for reliable signal processing directly in the field. This high-performance Fieldbus Box serves as a dual-channel digital input counter module designed to interface seamlessly with Beckhoff Lightbus networks. It processes incoming pulse trains and binary signals up to a maximum frequency of 100 kHz, making it highly effective for positioning, frequency measurement, and rapid counting applications.
Constructed within a rugged, moisture-resistant housing, this module carries an IP67 protection rating, allowing direct machine mounting without the protection of a control cabinet. The integration of standard M12 connectors ensures quick installation and excellent resistance to mechanical vibration and environmental stress.
Features
- Two independent high-speed digital counter channels.
- Lightbus fieldbus interface for rapid deterministic communication.
- Maximum input frequency of 100 kHz for precise pulse capture.
- Industrial M12 screw connection technology for reliable signal routing.
- IP67-rated enclosure suitable for harsh industrial field environments.
- Direct machine installation eliminates localized terminal boxes and reduces cabling costs.
Applications
- Flow meter pulse monitoring and liquid volume calculation.
- Rotational speed measurement and shaft encoder integration.
- High-speed parts counting in packaging and bottling plants.
- Material handling systems requiring localized high-frequency sensor inputs.
Technical Specifications
Parameter
Value
| Manufacturer |
Beckhoff |
| Part Number / Model |
IP1502-B200 |
| Product Type |
Fieldbus Box (Counter Module) |
| Fieldbus Protocol |
Lightbus |
| Number of Channels |
2 |
| Nominal Voltage |
24 V DC |
| Maximum Frequency |
100 kHz |
| Connection Interface |
M12 screw connectors |
| Protection Class |
IP67 |
| Shipping Weight |
2.0 kg (including typical export packaging) |
Installation Guidelines
For optimal operation and to maintain the physical protection of the device, follow these installation procedures:
- Mount the module directly onto a flat machine surface or mounting profile using appropriate fastening screws.
- Ensure all unused M12 mating ports are sealed with protective caps to preserve the IP67 environmental rating.
- Route high-frequency signal lines separate from high-voltage power cables to minimize electromagnetic interference.
- Establish a low-impedance ground connection from the module's ground terminal to the machine frame.
Compliance and Certifications