Description
The BECKHOFF KL6041 is a high-performance serial interface Bus Terminal designed to connect devices equipped with RS422 or RS485 interfaces directly to K-bus-based automation networks. Acting as an intelligent gateway, the terminal enables the system to transmit and receive serial data streams independently of the underlying fieldbus protocol. This direct integration ensures reliable data exchange with various peripheral devices, such as barcode scanners, serial displays, operating terminals, and specialized sensors.
The terminal operates as an active communication module that handles the physical data transmission using differential signaling. It contains dedicated internal memory buffers to prevent data loss during periods of high bus traffic. By decoupling the serial communication cycle from the fieldbus task cycle, the BECKHOFF KL6041 ensures steady, precise data transmission, which is further aided by integrated galvanic isolation that protects the internal K-bus electronics from field-side interference.
Features
- Dual-interface compatibility supporting both RS422 and RS485 serial communication.
- Full-duplex and half-duplex data transfer modes.
- Differential signal transmission to minimize electromagnetic interference.
- Integrated line impedance of 120 ohms for matching standard communication cables.
- Onboard data buffers, containing a 1024-byte receive buffer and a 128-byte transmit buffer.
- Galvanic isolation rated at 500 V between the internal K-bus and the field signal lines.
- Variable process image width up to 22 bytes of user data.
- Direct power supply via the K-bus, eliminating the need for external power contacts.
Applications
- Integration of legacy serial devices including barcode scanners, scales, and label printers.
- Point-to-point RS422/RS485 serial communication links over long distances up to approximately 1000 meters.
- Connection of operator interface panels and industrial serial displays.
- Interfacing with proprietary serial controllers and third-party instrumentation.
Technical Specifications
General
| Parameter |
Specification |
| Manufacturer |
BECKHOFF |
| Model |
KL6041 |
| Product Type |
Bus Terminal |
| Technology |
RS422/RS485 serial interface |
| Number of Channels |
1 serial channel (TxD and RxD) |
| Operation Modes |
Full-duplex, half-duplex |
| Data Transfer Rates |
4800 to 115,200 baud (Default: 9600 baud, 8 data bits, no parity, 1 stop bit) |
| Line Impedance |
120 ohms |
| Maximum Cable Length |
Approx. 1000 m twisted pair |
Electrical and Buffer Specifications
| Parameter |
Specification |
| Power Supply |
Via the K-bus |
| Current Consumption K-bus |
Typ. 65 mA |
| Current Consumption Power Contacts |
None (no power contacts) |
| Electrical Isolation |
500 V (K-bus / signal voltage) |
| Receive Buffer |
1024 bytes |
| Transmit Buffer |
128 bytes |
| Process Image Bit Width |
Input/output: 22 x 8 bit user data, 2 x 8 bit control/status (up to 22 bytes user data possible) |
| Configuration |
No address setting required; configured via Bus Coupler or controller |
Mechanical and Environmental
| Parameter |
Specification |
| Weight |
Approx. 60 g |
| Operating Temperature |
-25 degC to +60 degC |
| Storage Temperature |
-40 degC to +85 degC |
| Relative Humidity |
95%, non-condensing |
| Vibration / Shock Resistance |
Conforms to EN 60068-2-6 / EN 60068-2-27 |
| EMC Immunity / Emission |
Conforms to EN 61000-6-2 / EN 61000-6-4 |
| Protection Class |
IP20 |
| Installation Position |
Variable |
Compliance and Certifications
| Parameter |
Specification |
| Approvals |
CE, UL, ATEX, DNV GL |
| Ex Marking |
II 3 G Ex nA IIC T4 Gc |
Installation Guidelines
- Ensure the system is completely de-energized and all power supplies are switched off before proceeding with installation.
- Verify that the model number matches KL6041 and inspect the terminal housing for visual signs of shipping damage.
- Mount the terminal onto a standard 35 mm DIN rail by snapping it into place, ensuring the interlocking side grooves align correctly with the neighboring terminals.
- Ensure secure mechanical locking and proper K-bus contact connection with adjacent terminals on the rail.
- Connect the RS422 or RS485 serial signals to the terminal points using twisted-pair communication cabling. Ensure proper termination using the internal 120-ohm impedance if required by the network topology.
- Ground any cable shields appropriately to prevent electrical noise and signal degradation.
- Re-energize the K-bus system and configure the serial communication parameters (baud rate, parity, stop bits) using TwinCAT or your standard controller configuration software.
Replacement Recommendations
When replacing an existing BECKHOFF KL6041, first isolate the power supply to the entire station. Note and document the terminal configuration and physical wiring connections before removing the faulty unit. The replacement unit does not require any hardware address settings, as configuration parameters are written automatically by the Bus Coupler or controller during initialization.