Acquisition of analog sensor signals within automated industrial networks is performed efficiently using the BECKHOFF KS3142 analog input terminal. This high-precision Bus Terminal provides dual-channel connection capabilities for field sensors operating with standard 0 to 20 mA signal currents. Utilizing a robust differential input design and a 16-bit analog-to-digital converter, the module delivers highly accurate measurement data directly to the K-bus process image. The distinctive feature of the KS-series housing is its pluggable wiring level, which enables fast assembly and easy replacement of the terminal block without disconnecting the established field-side wire connections.

Features

  • Two-channel analog input module processing 0 to 20 mA field signals.
  • High-resolution 16-bit analog-to-digital conversion with increased measuring accuracy.
  • Configurable conversion time and integral 50 Hz filter to eliminate signal noise.
  • Pluggable connection level allows quick terminal swapping during maintenance operations.
  • Differential inputs with 500 V galvanic isolation between the K-bus and field signals.
  • Integrated surge voltage resistance up to 35 V DC for enhanced field protection.

Applications

  • Machine building and precision assembly equipment
  • Industrial process instrumentation loops
  • Water and wastewater treatment facility monitoring
  • Power generation and thermodynamic plant controls

Technical Specifications

Manufacturer BECKHOFF
Part Number/Model KS3142
Number of Inputs 2
Power Supply Via the K-bus
Signal Current 0 to 20 mA
Technology Differential input
Internal Resistance typ. 100 Ohm shunt
Common-mode Voltage (UCM) max. +/-10 V
Resolution 16 bit
Conversion Time 140 ms (configurable)
Filter 50 Hz (configurable)
Measuring Error < +/-0.05% (relative to full scale value)
Surge Voltage Resistance 35 V DC
Electrical Isolation 500 V (K-bus / signal voltage)
Current Consumption K-bus typ. 85 mA
Bit Width in Process Image Input: 2 x 16-bit data (2 x 8-bit control/status optional)
Operating Temperature 0 to +55 degC
Storage Temperature -25 to +85 degC
Relative Humidity 95%, no condensation
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP20
Installation Position Variable
Wiring Type Spring actuation by screwdriver (pluggable connector)
Connection Cross-section Solid/stranded: 0.08 to 1.5 mm², Fine-wire: 0.14 to 1.5 mm²
Connection Cross-section AWG Solid/stranded: AWG 28 to 16, Fine-wire: AWG 26 to 16
Stripping Length 9 to 10 mm
Current Load Power Contacts Imax: 10 A
Dimensions (L x W x H) 6.8 cm x 1.2 cm x 10.0 cm
Weight 0.07 kg

Installation Guidelines

  • Mounting: Snap directly onto a standard 35 mm DIN rail conforming to EN 60715. Ensure the locking latch engages securely.
  • Wiring: Insert a small screwdriver into the clamp spring release slot to open the connection point, insert the stripped conductor (9 to 10 mm stripping length), and release the spring clamp.
  • Pluggable Block: Ensure the power supply is completely switched off before engaging or disengaging the pluggable terminal wiring block.
  • Shielding: Connect analog signal shields to the nearest functional ground bar to prevent environmental electromagnetic interference from affecting signal integrity.

Compliance and Certifications

  • CE
  • UL
  • ATEX
  • Ex Marking: II 3 G Ex nA IIC T4 Gc
Loading product navigation…

What is the key advantage of the KS3142 pluggable wiring design?

The pluggable terminal block on the KS3142 allows the core unit to be unplugged and replaced during maintenance without having to disconnect or tag the individual signal lines.

Can the conversion times and filters of the KS3142 be adjusted?

Yes, both the conversion time (default 140 ms) and the internal 50 Hz filter parameters can be configured through the bus coupler software settings.

Does the KS3142 have standard ATEX ratings for hazardous locations?

Yes, the module is certified under ATEX with the Ex marking: II 3 G Ex nA IIC T4 Gc, making it suitable for Zone 2 hazardous areas.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Recently Viewed Products

Technical knowledge

Electric Actuators Designed to Replace Fluid Power Systems: A Practical Industrial Automation Guide

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...