BECKHOFF

BECKHOFF KS4022 Bus Terminal

SKU KS4022

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: KS4022

  • Country of origin:Germany

  • Product Type: Bus Terminals

  • Payment: T/T, Western Union

  • Weight: 80g

  • Dimensions: 6.8 cm x 1.2 cm x 10.0 cm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The BECKHOFF KS4022 is a two-channel analog output bus terminal designed for the generation of industrial control signals within a modular Bus Terminal system. Utilizing single-ended technology, the terminal converts binary control values from the automation controller into standardized analog process signals. It integrates seamlessly into standard Beckhoff Bus Terminal configurations via the K-bus, communicating process data while providing galvanic isolation between the field level and the internal system bus.

Equipped with pluggable wiring levels, the KS4022 facilitates efficient installation and maintenance by allowing terminal blocks to be disconnected without disturbing the field wiring. This design supports industrial control architectures requiring reliable analog actuation, standard 35 mm DIN rail mounting, and dependable signal conditioning in decentralized automation environments.

Features

  • Two independent analog output channels with single-ended technology
  • Standardized 4 to 20 mA signal current generation for industrial actuators
  • 12-bit native resolution for precise process control
  • Pluggable wiring level for all KSxxxx series bus terminals
  • K-bus communication interface for data exchange with bus couplers or embedded controllers
  • Electrical isolation rated at 500 V between the K-bus and signal voltage
  • Compact terminal housing designed for standard 35 mm DIN rail installation

Applications

  • Industrial process control systems requiring analog current actuators
  • Valve positioning and proportional control loops
  • Speed and frequency inverter reference value generation
  • Decentralized machine automation utilizing Beckhoff Bus Terminal nodes

Technical Specifications

General

Parameter Specification
Manufacturer BECKHOFF
Exact Model KS4022
Product Type Bus Terminal
Design Form Terminal housing with pluggable wiring level
Housing Material Polycarbonate
Country of Origin Germany

Signal and I/O

Parameter Specification
Number of Outputs 2
Technology Single-ended
Signal Current 4 to 20 mA
Load Impedance < 500 ohm
Resolution 12 bit
Conversion Time ~ 1.5 ms
Output Error < ±0.1 % (relative to end value)
Process Image Bit Width Output: 2 x 16-bit data (2 x 8-bit control/status optional)

Electrical

Parameter Specification
Power Supply 24 V DC via power contacts (alternative 15 V DC with power supply terminal KL9515)
Current Consumption Power Contacts Typ. 50 mA + load
Current Consumption K-Bus Typ. 60 mA
Current Load Power Contacts Imax: 10 A
Electrical Isolation 500 V (K-bus / signal voltage)

Connection Technology

Parameter Specification
Connection Type Spring actuation by screwdriver (pluggable wiring)
Conductor Cross-Section (Solid / Stranded) 0.08 to 1.5 mm²
Conductor Cross-Section (Fine-Stranded) 0.14 to 1.5 mm²
Conductor Cross-Section AWG AWG 28 to 16
Stripping Length 9 to 10 mm

Mechanical and Environmental

Parameter Specification
Dimensions (L x W x H) 6.8 cm x 1.2 cm x 10.0 cm
Net Weight 0.08 kg
Mounting On 35 mm DIN rail conforming to EN 60715 with lock
Protection Rating IP20
Operating Temperature Range -25 to +60 °C
Storage Temperature Range -40 to +85 °C
Relative Humidity 95 %, no condensation
Vibration / Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity / Emission Conforms to EN 61000-6-2 / EN 61000-6-4

Approvals and Certifications

Parameter Specification
Approvals / Markings CE, UL, ATEX, DNV GL
Ex Marking II 3 G Ex nA IIC T4 Gc

Installation Guidelines

  1. Ensure the entire control system is de-energized before performing any mechanical or electrical installation work.
  2. Verify that the mounting rail is a standard 35 mm DIN rail conforming to EN 60715 and is securely grounded.
  3. Click the BECKHOFF KS4022 onto the DIN rail next to an appropriate bus coupler, embedded PC, or preceding terminal, utilizing the double slot and key connection for side-by-side alignment.
  4. Connect field wiring to the pluggable spring-actuated terminals using a suitable screwdriver, ensuring correct conductor stripping lengths of 9 to 10 mm.
  5. Verify that the 24 V DC power supply to the power contacts and the K-bus connection are correctly established before applying system power.
  6. Perform a functional check of the analog output signals and process data mapping via the controller engineering software during system commissioning.

FAQ

What is the BECKHOFF KS4022 and how does it function in an automation system?

The BECKHOFF KS4022 is a two-channel analog output bus terminal designed for generating standardized control signals in industrial environments. It converts binary control values from the automation controller into precise 4 to 20 mA analog process signals using single-ended technology. The unit integrates smoothly into modular Bus Terminal configurations via the K-bus while providing 500 V electrical isolation.

What are the core electrical and signal specifications of the KS4022?

The BECKHOFF KS4022 features two independent output channels delivering a 4 to 20 mA signal current with a native 12-bit resolution. It operates with a conversion time of approximately 1.5 ms and supports a load impedance of less than 500 ohms. Power is supplied via 24 V DC power contacts, drawing a typical current of 50 mA plus the connected field load.

How is the BECKHOFF KS4022 installed and wired in a control cabinet?

The BECKHOFF KS4022 is designed for standard 35 mm DIN rail mounting in compliance with EN 60715 guidelines. It utilizes pluggable wiring levels with spring-actuated terminals that accept solid or fine-stranded conductors ranging from AWG 28 to 16. This pluggable design allows technicians to disconnect terminal blocks easily without disturbing existing field wiring during maintenance.

What environmental conditions and safety ratings are supported by this terminal?

The BECKHOFF KS4022 features an IP20 protection rating and operates reliably within a temperature range of -25 to +60 °C. It meets rigorous industrial standards for vibration, shock resistance, and electromagnetic compatibility. Additionally, it holds multiple hazardous location approvals, including ATEX certification for Zone 2 explosive atmospheres.

View all FAQs →

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Germany

Technical knowledge

ABB PM891K01 Replacement: Check Redundancy Before Ordering

ABB PM891K01 article 3BSE053241R1 is the non-redundant AC 800M processor kit. Use this field checklist before replacement.

ABB TP853 Replacement Checks for CI853/CI855/CI857/CI861

Replacement checks for ABB TP853 3BSE018126R1: identify the installed CI853, CI855, CI857, or CI861 interface, record wiring, and verify communication after installation.

5069-L330ERMS2 Startup Checks: RTBs, I/O, and Motion Limits

Engineering checks for the Allen-Bradley 5069-L330ERMS2: controller capacity, separate RTB kits, local I/O limits, network-node limits, and motion-axis count.

Replacing ABB DSQC 351: Controller and Network Checks

Checks to record before replacing ABB 3HNE 00006-1 DSQC 351: controller generation, X3/X5/X20/X21 wiring, DeviceNet settings, INTERBUS mapping, and LED states.

IC693CPU360 vs IC693CPU364: Ethernet and Power Budget

Compare the IC693CPU360 and IC693CPU364 by Ethernet interface, +5 VDC load, memory, rack limits, and replacement checks.

1756-OF4 Output Wrong? Check Mode, RTB, and Scaling First

A field-first diagnostic sequence for 1756-OF4 analog output problems: channel mode, removable terminal block, scaling, and controlled electrical checks.