Danfoss 136N8927 FC-051PK75T4E20HXXXCXXXSXXX VLT Micro Drive FC 51
SKU 136N8927
In stock
No reviews
12-month warranty
Free returns within 30 days
Manufacturer:
Danfoss
Product No.:
136N8927
Country of origin:United States
Product Type:
VLT Micro Drive
Payment:
T/T, Western Union
Weight:
5000g
Shipping port:
Xiamen
Warranty:
12 months
Product Overview
The Danfoss 136N8927 (FC-051PK75T4E20HXXXCXXXSXXX) VLT Micro Drive FC 51 is a high-efficiency variable frequency drive engineered for seamless motor speed control in diverse industrial settings. This 0.75 kW (1.0 HP) unit is designed for three-phase 380-480 VAC power systems, providing reliable performance in applications such as centrifugal pumps, conveyor belts, and HVAC fan systems. By utilizing advanced VVC plus (Voltage Vector Control) technology, the 136N8927 ensures precise motor operation, contributing to significant energy savings and decreased mechanical wear, ultimately extending the operational lifespan of connected rotating equipment.
Technical Configuration
The ordering code FC-051PK75T4E20HXXXCXXXSXXX delineates the specific build and functional attributes of this drive:
FC-051: Identifies the compact VLT Micro Drive FC 51 series.
PK75: Indicates a power output capacity of 0.75 kW / 1.0 HP.
T4: Configured for 380-480 VAC three-phase supply.
E20: IP20 / Chassis design for installation within standard electrical enclosures.
HX: No internal RFI filter, prioritizing cost-efficiency for non-regulated environments.
X: No integrated brake chopper; suitable for standard speed control applications.
C: PCB coating provided for protection against humidity and corrosive atmospheres.
SXXX: Equipped with the latest standard software release for full compatibility with Danfoss control logic.
Technical Specifications
Feature
Specification
Model
136N8927 (FC-051PK75T4E20HXXXCXXXSXXX)
Brand
Danfoss
Power Rating
0.75 kW (1.0 HP)
Mains Voltage
380 - 480 VAC (+/- 10 percent)
Supply Frequency
50 / 60 Hz
Enclosure
IP20 / Chassis
Analog Inputs
2
Analog Outputs
1 (max 17 V)
Ramp Times
0.05 - 3600 s
Logic Compatibility
PNP or NPN (0 - 24 VDC)
PCB Protection
Coated
Shipping Weight
5 kg
FAQs
How does the PK75 power rating affect installation requirements compared to smaller models?
While the frame size for the 0.75 kW model remains compact, ensure your input circuit protection (fuses or circuit breakers) is sized specifically for the rated current of this drive to maintain safety compliance.
Does this drive support braking resistor connection?
No, the X-suffix in the braking position confirms this unit does not feature an integrated brake chopper, meaning it is not designed for heavy regenerative braking applications.
Can the drive be configured via a local interface?
This model is delivered without an LCP (Local Control Panel). Configuration is typically performed via the RS-485 port using Danfoss MCT 10 software or by installing a snap-on LCP module separately.
Installation and Operational Guidelines
Heat Dissipation: Although the drive is small, it generates heat during operation. Maintain at least 100 mm of clearance above and below the unit to allow for convective cooling. If mounting multiple drives side-by-side, ensure the total cabinet cooling capacity accounts for the cumulative heat dissipation.
Wiring Standards: Use shielded motor cables to prevent electromagnetic noise from impacting other control signals. The cable shield should be properly terminated at the drive's chassis grounding point using a 360-degree metallic clamp to ensure low-impedance high-frequency grounding.
Environmental Protection: While the PCB is coated, the IP20 enclosure does not protect against conductive dust or liquids. Always install the unit within a clean, dry, and climate-controlled electrical cabinet to ensure the longevity of the power electronics.
A practical guide to segmenting, documenting, and testing industrial Ethernet networks so plant teams can isolate faults quickly, control change, and expand without creating fragile dependencies.
Commission IO-Link systematically from master addressing and port modes through IODD selection, PLC byte mapping, parameter backups, device validation, and failure-injection tests.
An industrial joystick is only the first element in a safe motion command chain. This guide covers sensing choices, wiring, signal validation, PLC logic, restart behavior, and commissioning for...
PID tuning becomes safer when engineers can see how proportional, integral, and derivative actions reshape error, output, and response over time. This guide turns live trends into a disciplined...
A linear axis should be proven mechanically before aggressive tuning begins. This commissioning workflow covers scaling, direction, limits, homing, STO, low-speed tests, and evidence-based tuning for...
Choosing a selection results in a full page refresh.