EL3002 | BECKHOFF | EtherCAT Terminal Analog Input Module
SKU EL3002
In stock
No reviews
12-month warranty
Free returns within 30 days
Manufacturer:
BECKHOFF
Product No.:
EL3002
Country of origin:Germany
Product Type:
EtherCAT Terminal
Payment:
T/T, Western Union
Weight:
2000g
Dimensions:
12 mm x 100 mm x 68 mm
Shipping port:
Xiamen
Warranty:
12 months
Description
The EL3002 is a 2-channel analog input terminal manufactured by Beckhoff, designed for high-precision voltage measurement within EtherCAT automation systems. It processes signals in the ±10 V range with 12-bit resolution, providing reliable data for industrial monitoring and control. The module utilizes a single-ended input technology and features configurable filtering options, including FIR and IIR filters, to ensure signal integrity.
Integrated limit value monitoring and overload status indication
Electrical isolation of 500 V between E-bus and field potential
Compact housing with signal LEDs for diagnostic feedback
Technical Specifications
Feature
Specification
Manufacturer
Beckhoff
Model
EL3002
Number of Inputs
2 (single-ended)
Signal Voltage
-10 to +10 V
Resolution
12 bit
Conversion Time
0.625 ms (configurable)
Input Filter Frequency
1 kHz
Internal Resistance
> 130 kΩ
Dielectric Strength
Max. 30 V
Current Consumption (E-bus)
Typ. 130 mA
Dimensions (W x H x D)
12 mm x 100 mm x 68 mm
Operating Temperature
-25 to +60 degC
Storage Temperature
-40 to +85 degC
Installation Guidelines
DIN Rail Mounting: Secure the EL3002 onto a 35 mm DIN rail (EN 60715). Use the integrated double slot and key connection for reliable side-by-side assembly.
Wiring: The terminal accepts solid (0.08–2.5 mm²) and flexible (0.14–1.5 mm²) conductors. Use a screwdriver for spring-loaded terminal actuation. Strip wires to a length of 8–9 mm.
Environmental: The unit is IP20 rated. Ensure installation in a clean, temperature-controlled environment within the specified -25 to +60 degC range.
Hazardous Areas: Complies with ATEX (II 3 G Ex nA IIC T4 Gc). Ensure all local safety regulations are followed when integrating into potentially explosive atmospheres.
Compliance and Certifications
CE
UL
ATEX: II 3 G Ex nA IIC T4 Gc
EMC Immunity/Emission: Conforms to EN 61000-6-2 / EN 61000-6-4
Vibration/Shock: Conforms to EN 60068-2-6 / EN 60068-2-27
FAQ
What is the voltage input range of the EL3002?
The EL3002 supports a signal voltage range of -10 V to +10 V.
Does the EL3002 require manual address configuration?
No, this EtherCAT terminal does not require any manual address or configuration settings.
What is the conversion time for the input signals?
The default conversion time is 0.625 ms, which is configurable by the user.
What kind of signal filtering is available?
The module features activatable FIR/IIR filters to help manage signal noise and improve measurement accuracy.
A practical replacement guide for the GE Fanuc IC693CPU313, covering its embedded five-slot architecture, memory backup, firmware-dependent capacity and why it cannot use Series 90-30 expansion racks.
A field-focused comparison of Bently Nevada 3500/40M and 3500/42M monitor inputs, channel-pair configuration, rear I/O options, external termination hardware and firmware checks before replacement.
A field checklist for diagnosing Allen-Bradley 1746-NR4 RTD and resistance inputs, including sensor curves, lead compensation, excitation current, filter timing and channel diagnostics.
A field-focused checklist for replacing an Allen-Bradley 1785-L40B or planning a PLC-5/40 migration, covering backups, 1771 I/O mapping, DH+/RIO channels, revision risks and commissioning.
Replacing an Allen-Bradley 1747-SN scanner? Check SLC 500 logical rack and G-file mapping, link speed, cable termination, COMM/FAULT LEDs and hardware series before blaming the module or changing the...