BECKHOFF

EL4021 | BECKHOFF | EtherCAT Terminal Analog Output Module

SKU EL4021

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: EL4021

  • Country of origin:Germany

  • Product Type: EtherCAT Terminal

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The EL4021 is a high-precision EtherCAT Terminal from Beckhoff, featuring a 1-channel analog output capable of generating a 4…20 mA current signal. Designed for industrial control systems, this module utilizes 12-bit resolution to provide accurate output control with a conversion time of approximately 100 µs. The EL4021 supports Distributed Clocks (DC), enabling highly precise synchronization across an EtherCAT network with a precision of << 1 µs.

Features

  • 1-channel analog output (4…20 mA current)
  • 12-bit resolution for precise signal control
  • Distributed Clocks (DC) support for sub-microsecond synchronization
  • Short-circuit proof design with < 500 Ω load capacity
  • Electrical isolation of 500 V between E-bus and signal voltage
  • Compact terminal housing with integrated signal LEDs for status monitoring
  • Optional watchdog function for user-specific output values with ramp control

Technical Specifications

Feature Specification
Manufacturer Beckhoff
Model EL4021
Number of Outputs 1
Signal Current 4…20 mA
Resolution 12 bit
Conversion Time ~ 100 µs
Load < 500 Ω
Electrical Isolation 500 V (E-bus/signal voltage)
Power Supply 24 V DC via power contacts
Current Consumption 25 mA (power contacts), 140 mA (E-bus)
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Operating Temperature -25 to +60 degC
Storage Temperature -40 to +85 degC

Installation Guidelines

  • Mounting: The EL4021 is designed for installation on a standard 35 mm DIN rail (EN 60715). Use the double slot and key connection for secure side-by-side mounting.
  • Wiring: The terminal supports solid, stranded, and flexible conductors (with ferrules). Use a screwdriver for spring actuation.
  • Connection Cross-sections: 0.08…2.5 mm² (solid/stranded) or 0.14…1.5 mm² (flexible). Strip wires to a length of 8…9 mm.
  • Environmental: Ensure the module is installed in an IP20-rated environment. The unit operates in variable installation positions.
  • Safety: Adhere to ATEX requirements (II 3 G Ex nA IIC T4 Gc) when installing in hazardous areas.

Compliance and Certifications

  • CE
  • UL
  • ATEX: II 3 G Ex nA IIC T4 Gc
  • EMC immunity/emission: Conforms to EN 61000-6-2/EN 61000-6-4
  • Vibration/shock: Conforms to EN 60068-2-6/EN 60068-2-27

FAQ

What is the primary output signal range of the EL4021?

The EL4021 provides a 1-channel analog current output ranging from 4 to 20 mA.

Does the EL4021 support Distributed Clocks?

Yes, the module supports Distributed Clocks (DC) with a precision of less than 1 µs, allowing for tight synchronization within an EtherCAT network.

What is the resolution of this analog output terminal?

The module features a 12-bit resolution.

What kind of protection does the output have?

The output is short-circuit proof with a load capacity of less than 500 Ω.

View all FAQs →

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Dots
Country of origin
Germany

Technical knowledge

IC693CPU313 Memory Retention and Expansion Limits Before Replacement

A practical replacement guide for the GE Fanuc IC693CPU313, covering its embedded five-slot architecture, memory backup, firmware-dependent capacity and why it cannot use Series 90-30 expansion racks.

Bently Nevada 3500/40M vs 3500/42M: I/O and Channel Checks Before Replacement

A field-focused comparison of Bently Nevada 3500/40M and 3500/42M monitor inputs, channel-pair configuration, rear I/O options, external termination hardware and firmware checks before replacement.

Allen-Bradley 1746-NR4 RTD Faults: Wiring, Excitation, and Filter Checks

A field checklist for diagnosing Allen-Bradley 1746-NR4 RTD and resistance inputs, including sensor curves, lead compensation, excitation current, filter timing and channel diagnostics.

Replacing an Allen-Bradley 1785-L40B: PLC-5/40 Checks Before Migration

A field-focused checklist for replacing an Allen-Bradley 1785-L40B or planning a PLC-5/40 migration, covering backups, 1771 I/O mapping, DH+/RIO channels, revision risks and commissioning.

Allen-Bradley 1747-SN: RIO Mapping and Link Fault Checks

Replacing an Allen-Bradley 1747-SN scanner? Check SLC 500 logical rack and G-file mapping, link speed, cable termination, COMM/FAULT LEDs and hardware series before blaming the module or changing the...

Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks

Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.