BECKHOFF

EL9515 BECKHOFF 15 V DC Power Supply Terminal with Diagnostics

SKU EL9515

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: BECKHOFF

  • Product No.: EL9515

  • Country of origin:Germany

  • Product Type: Power supply terminal 15 V DC

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Dimensions: 12 mm x 100 mm x 68 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Product Overview

The EL9515 (EL9515) is a high-precision power supply terminal designed to convert a standard 24 V DC input into a stabilized 15 V DC output within the EtherCAT terminal system. This module is specifically engineered to provide clean, low-noise power to specialized field devices—such as high-end analog sensors, encoders, or transducers—that require a 15 V potential. Equipped with integrated diagnostics and an overcurrent LED, the EL9515 ensures the integrity of the secondary power circuit. Its compact 12 mm design and ATEX certification make it an essential component for B2B industrial applications in hazardous areas, laboratory automation, and precision instrumentation where voltage stability is critical.

Technical Configuration (Deep Dive)

The EL9515 functions as a DC/DC converter, drawing power from the 24 V DC power contacts and providing a regulated 15 V DC output at a maximum current of 0.5 A. The output is exceptionally stable, boasting a ±1 % tolerance and a residual ripple of < 5 mV, which is vital for preventing signal jitter in sensitive analog measurements.

Safety and system uptime are prioritized through short-circuit proof circuitry and comprehensive diagnostics. The terminal reports its operational status—including overcurrent or fault conditions—directly into the EtherCAT process image. This allows the master controller to monitor the health of the 15 V supply in real-time. For visual inspection, a dedicated diagnostic LED provides immediate feedback on the module’s status without requiring a software connection.

Technical Specifications

Attribute Specification Details
Model EL9515
Brand BECKHOFF
Input Voltage 24 V DC (-15 % / +20 %)
Output Voltage 15 V DC (±1 %)
Output Current 0.5 A
Residual Ripple < 5 mV
Short-Circuit Proof Yes
Diagnostics Yes (Process image + Overcurrent LED)
Electrical Isolation 500 V (E-bus / Field potential)
Current Consumption (E-bus) Typically 90 mA
Operating Temperature 0 to +55 Celsius
Protection Rating IP20
Approvals CE, UL, ATEX (Ex nA IIC T4 Gc)

Technical FAQs

How do I access the diagnostics for the EL9515?

The diagnostics are mapped into the EtherCAT process image. You can link these variables in TwinCAT to monitor for "Under Voltage" or "Overcurrent" states. Additionally, the red LED on the front of the terminal will illuminate if the 0.5 A current threshold is exceeded.

Does the EL9515 provide power to the next terminal via power contacts?

The 15 V output is provided via the terminal connection points for field wiring. The internal power contacts (blades) typically carry the primary 24 V DC supply to downstream modules. Always verify the current path in your specific hardware configuration to ensure the 15 V potential is routed only where intended.

Is this terminal suitable for use in explosive atmospheres?

Yes. The EL9515 carries the ATEX marking (II 3 G Ex nA IIC T4 Gc), making it suitable for installation in Zone 2 hazardous areas when housed in an appropriately rated enclosure.


Engineering & Installation Guide

  • Voltage Sensitivity: Due to the low residual ripple (< 5 mV), this module is ideal for supplying power to high-resolution analog-to-digital converters (ADCs). To maintain this performance, keep the 15 V supply leads as short as possible and separate them from high-interference AC lines.

  • Wiring and Termination: The terminal features ES series pluggable wiring, allowing for the removal of the wiring level without disconnecting individual leads. Use a screwdriver to actuate the spring clamps, ensuring a stripping length of 8 to 9 mm for a secure, vibration-resistant connection.

  • Thermal Considerations: While the module is rated for 0.5 A, ensure the 24 V DC input supply is robust. The conversion process generates a small amount of heat; ensure the 12 mm terminal has sufficient vertical clearance (30 mm) for convective cooling within the cabinet.

Engineering Advantages

The EL9515 excels by eliminating the need for bulky, external 15 V power supplies, thereby saving significant DIN rail space. Its 500 V galvanic isolation protects the EtherCAT backplane from potential field-side electrical anomalies. Conforming to EN 61000-6-2/4 for EMC, it is built to operate reliably in electrically noisy industrial environments. For B2B machine builders, the integrated diagnostic feedback simplifies the creation of sophisticated HMI alerts, ensuring that power supply issues are identified and resolved before they lead to broader system failures.

 

Quantity
Shipping &amp; Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
White
Country of origin
Germany

Technical knowledge

Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks

Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.

AKS 33 vs AKS 3000: Checks Before Replacing a Pressure Transmitter

A field checklist for distinguishing Danfoss 060G2105, 060G1323 and 060G2109 by pressure range, fitting, loop signal and controller scaling.

Diagnosing DeltaV SE5009 Power Problems Before Replacement

A field checklist for separating 24 VDC input, carrier bus, output derating and alarm-contact faults before replacing an Emerson SE5009.

Commissioning Quantum Inputs with the 140XSM00200 Simulator

A controlled commissioning method for using the 140XSM00200 simulator to verify Modicon Quantum input mapping and interlocks before reconnecting field wiring.

Commissioning PLX32-EIP-MBTCP: Subnets, Registers, and RPI

A commissioning checklist for the ProSoft PLX32-EIP-MBTCP covering subnet separation, register contracts, EtherNet/IP timing, failure tests and replacement records.

Diagnosing IC693MDL916 Relay Outputs Before Module Replacement

A field checklist for IC693MDL916 relay commands, terminal blocks, load current, switching rate and contact-side measurements.