General Electric

GE Multilin 750-P5-G1-S1-HI-A20-R Feeder Management Relay

SKU 750-P5-G1-S1-HI-A20-R

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: General Electric

  • Product No.: 750-P5-G1-S1-HI-A20-R

  • Country of origin:United States

  • Product Type: 750 Feeder Management Relay

  • Payment: T/T, Western Union

  • Weight: 11000g

  • Dimensions: 225 mm x 275 mm x 210 mm (W x H x D)

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The GE Multilin 750-P5-G1-S1-HI-A20-R is a digital feeder management relay designed for the primary protection, control, and asset management of distribution feeders in solidly grounded, high impedance grounded, or resonant grounded systems. Equipped with a high-performance microprocessor architecture, flash memory for field upgrades, and real-time oscillography, the device provides integrated current, voltage, frequency, power, and energy metering to eliminate auxiliary metering equipment. Communication interface hardware includes a front RS232 port, dual rear RS485/RS422 ports, and supports Modbus RTU, Modbus TCP/IP, and DNP 3.0 Level 2 protocols over serial or optional 10Mbps Ethernet physical layers. The GE Multilin 750-P5-G1-S1-HI-A20-R processes inputs from 5 A phase CTs, 1 A zero sequence CTs, and 1 A sensitive ground CTs, generating output signaling via eight electromechanical output relays, one high-speed solid-state SCR output, and eight isolated 4-20 mA analog outputs.

Features

  • Complete phase, neutral, ground, and sensitive ground time and instantaneous overcurrent protection with 15 standard and custom FlexCurves
  • Directional power, directional overcurrent, reverse power flow detection, and restricted earth fault protection
  • Built-in synchronism check supervising breaker closing via voltage, frequency, and phase angle differentials
  • Under/over voltage and under/over frequency protection with rate-of-change frequency decay tracking
  • Comprehensive circuit breaker monitoring including contact wear calculations, trip counter, and trip/close coil supervision
  • Onboard waveform capture saving up to 256 power frequency cycles, event recorder storing up to 256 events, and 8-channel data logger
  • Draw-out construction design for simplified testing, maintenance, and rapid replacement
  • Harsh chemical environment option featuring conformal coating for corrosive or humid installations

Applications

  • Primary protection and control for distribution feeders in utility and industrial power systems
  • Bus blocking, interlocking, and automatic bus transfer (throw-over) schemes
  • Load shedding systems based on voltage and frequency protection elements
  • Distributed Generation (DG) interconnect protection and reverse power monitoring
  • Back-up protection for transformers, transmission lines, and distribution buses

Ordering Information

Ordering Code Option Description Selection Code
Phase Current Inputs 5 A phase current inputs P5
Ground Current Inputs 1 A zero sequence current inputs G1
Sensitive Ground Current Inputs 1 A sensitive ground current input S1
Power Supply Options 88-300 VDC / 70-265 VAC @ 48-62 Hz HI
Analog Outputs Eight 4-20 mA analog outputs A20
Breaker Status LED Red breaker closed LED R
Environmental Protection Harsh Chemical Environment Option Conformal Coating

Technical Specifications

Parameter Specification
Manufacturer GE Multilin
Phase CT Rating 5 A secondary
Ground CT Rating 1 A secondary
Sensitive Ground CT Rating 1 A secondary
Control Power (HI Range) 88-300 VDC / 70-265 VAC @ 48-62 Hz
Power Consumption 25 VA nominal, 35 VA maximum
Voltage Hold-Up Time 30 ms
Analog Output Signals Eight 4-20 mA channels (Fully isolated)
Electromechanical Output Relays 8 outputs (2 Form A for breaker control, 5 Form C programmable, 1 Form C self-test alarm)
Solid State Output High-speed SCR (Make & carry: 15 A 250 VDC for 500 ms)
Digital Inputs 14 contact inputs (Dry: 132 VDC 2 mA provided; Wet: 30-300 VDC 2 mA)
Analog Input 0-1 mA, 0-5 mA, 0-10 mA, 0-20 mA, or 4-20 mA (375 ohm impedance)
Serial Communications Front RS232 port, Rear dual RS485/RS422 ports (300 to 19,200 baud)
Operating Temperature -40 degC to +60 degC
Storage Temperature -40 degC to +85 degC
Operating Humidity Up to 95% non-condensing @ 55 degC
IP Rating IP40 front, IP20 back

Connections/Interfaces

Terminal Pin / Port Function
G7, H7 / G8, H8 / G9, H9 Phase A, Phase B, Phase C Current Inputs
G3, H3 Ground Current Input
G10, H10 Sensitive Ground Current Input
G5, H5 / G6, H6 Phase Voltage Inputs (Va, Vb, Vc, Vcom)
G4, H4 Sync Voltage Input
H11, H12 Control Power Inputs (+/L, -/N)
G11, G12 Ground / Safety Ground Connections
C1 - C7, C10 - C11 Programmable Logic Inputs & Access Control
D1 - D7 Additional Programmable Logic Inputs
G1, H1 / G2, H2 Coil Monitor 1 / Coil Monitor 2 Inputs
E1, F1 Solid State Trip Output
E2, F2 / E3, F3 Output Relays 1 (Trip) / 2 (Close)
E4-F4, E5-F5, E6-F6, E7-F7, E8-F8, E9-F9, E10-F10 Output Relays 3 to 7 (Auxiliary Form C)
E11, F11, E12, F12 Output Relay 8 (Self-Test Warning Alarm)
A1, A2 Analog Input (+/-)
A3, A4 to A11, A12 Analog Outputs 1 through 8
B1, B2, B3 / B4, B5, B6 COM1 RS485/RS422 Port Connections
B7, B8 COM2 RS485 Port Connections
Front Panel RJ-45 / RS232 Local Computer Programming Port

Installation Guidelines

  • Ensure the relay unit safety ground terminal is directly wired to the panel protective earth before applying auxiliary control voltage.
  • Connect all current transformer wiring using shorting-type terminal connections to prevent open-circuit CT high-voltage hazards.
  • Route communication cabling using shielded twisted-pair cables, grounding the cable shields exclusively at the PLC/computer host side.
  • Verify that the auxiliary power supply rating matches the HI control power voltage ranges (88-300 VDC or 70-265 VAC) prior to energization.
  • Maintain clean, unblocked ventilation pathways around the draw-out chassis to adhere to environmental operating limits from -40 degC to +60 degC.

Compliance and Certifications

  • cULus (UL508, UL1053, C22.2 No 14)
  • CE (EN60255-5, EN50263)
  • IEC Standards (IEC 61000-4 series, IEC 60255 series, IEC 60529, IEC 60068 series)
  • IEEE / ANSI Standards (IEEE/ANSI C37.90.1, C37.90.2, C37.90.3)

FAQ

What power supply voltage range does the relay module accept?

The module operates from an internal high-range power supply supporting 88 to 300 VDC or 70 to 265 VAC at 48 to 62 Hz.

What current transformer ratings are specified for the AC inputs?

The device processes 5 A secondary inputs on the phase CT channels alongside 1 A secondary inputs on both ground and sensitive ground CT channels.

How many analog outputs are available on this model?

The relay includes eight fully isolated 4-20 mA analog output channels programmable to transmit any of thirty-one internal measured parameters.

Does the unit include environmental protection against corrosive gases?

The device features factory-applied conformal coating designed to protect internal circuit assemblies in harsh chemical and high-humidity operational environments.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

GE Multilin 750-P5-G1-S1-HI-A20-R Feeder Management Relay

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 2 item(s) left in stock
Quantity (1 in cart)
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

Technical knowledge

1746-A7 Chassis Replacement Checks: Slots, Power and Interconnects

An engineering checklist for replacing an Allen-Bradley 1746-A7: verify chassis series, backplane loading, slot plan, interconnect cables, mounting, grounding and receiving condition.

IC200MDL650 Replacement Checks: Logic Polarity, Filters, and Commons

A field replacement guide for GE Fanuc IC200MDL650 covering revision-dependent negative logic, four common groups, 24 VDC thresholds, input filtering, carrier checks and commissioning records.

IC697CPX935 Replacement Checks: Memory, Ports, and Rack Power

A field-focused IC697CPX935 replacement guide covering fast memory, firmware-dependent serial behavior, rack power, cooling, I/O architecture and backup records.

IC693DSM324 Replacement Checks: FSSB, Firmware and Follower Control

A field-focused IC693DSM324 replacement guide covering Series 90-30 host checks, FSSB servo-chain records, 5 V power budget, firmware limits, follower control and commissioning.

HIMA F3430 Replacement Checks: Contact Ratings and Safety Limits

A field-focused HIMA F3430 replacement guide covering relay contact ratings, DC load derating, fusing, F3330/F3331 differences, safety restrictions and commissioning records.

IC697PWR710 Replacement Checks: Load Budget and Dual-Rack Limits

A field-focused IC697PWR710 replacement guide covering 5 V load calculations, dual-rack limits, extension cables, input checks, protection behavior and hardware revision risks.