Overview
The General Electric IC660BBA105 is a Genius I/O current-source analog output block. It provides six independent 4–20 mA outputs. Channels 5 and 6 also support configured voltage output. The block uses a 115 VAC supply and provides loop power.
Features
- Six independent 4 to 20 mA analog output circuits with integrated loop power
- Channels 5 and 6 configurable for voltage output applications
- Software-configurable parameters including scaling, fault reporting, and hold-last-state behavior
- Advanced diagnostics including overrange, underrange, and output feedback error detection
- Dedicated digital output control for Bus Switching Modules (BSM)
- No hardware calibration required for operation
- Unit OK and I/O Enabled status LEDs for immediate visual diagnostics
Technical Specifications
| Parameter |
Specification |
| Manufacturer |
General Electric |
| Catalog Number / SKU |
IC660BBA105 |
| Product Type |
Current-Source Analog Output Block |
| Series |
Genius I/O |
| Nominal Block Power |
115 VAC (98 to 132 VAC, 47 to 63 Hz) |
| Maximum Current |
250 mA |
| Power Supply Dropout Time |
1 cycle min. |
| Number of Outputs |
6 analog output circuits |
| Output Range |
4 to 20 mA (Overrange capacity up to 24 mA) |
| Output Accuracy at 25 Celsius |
0.15 percent of full scale reading |
| Output Resolution |
6 microamps |
| Output Update Frequency |
25 ms |
| Block-to-Block Isolation |
1500V for one minute |
| Heat Dissipation |
12 Watts maximum |
| Operating Temperature |
0 to 60 Celsius (+32 to +140 Fahrenheit) |
| Storage Temperature |
-40 to +100 Celsius (-40 to +212 Fahrenheit) |
| Humidity |
5 percent to 95 percent (non-condensing) |
| Country of Origin |
United States |
Connections / Interfaces
- Terminals 1 to 4: Serial bus connections (Serial 1, Serial 2, Shield In, Shield Out) supporting AWG #12 to #22 wire
- Terminals 5 to 7: Block power (H, N, and safety ground)
- Terminals 9 and 10: Bus Switching Module (BSM) interface connections
- Terminals 11 to 32: Field device connections providing IOUT, RTN, VOUT, JMP, and GND points per channel
Installation Guidelines
The IC660BBA105 Genius I/O block is classified as open equipment and must be installed within a suitable protective electrical enclosure free from airborne contaminants and excessive moisture. Maintain a minimum clearance of 2 inches above and below the module to ensure adequate cooling airflow. Mount the unit securely using 8-32 screws and star washers through the upper and lower flange notches to maintain proper ground integrity. Connect the green ground screw to a reliable plant ground system using a minimum AWG #12 wire. Always ensure power is removed before servicing or replacing the electronics assembly.