Honeywell

Honeywell FC-TSGASH-1624P Safety Manager Field Termination Assembly

SKU FC-TSGASH-1624P V1.0

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell

  • Product No.: FC-TSGASH-1624P V1.0

  • Country of origin:United States

  • Product Type: Field Termination Assembly

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 650g

  • Dimensions: 225 x 109 x 60 mm (L x W x H)

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

The Honeywell FC-TSGASH-1624P V1.0 is a safe gas and flame detector input Field Termination Assembly (FTA) designed as an interface module between 0–20 mA field transmitters and the SAI-1620m safe high-density analog input module within Honeywell Safety Manager systems. Featuring 16 input channels, this assembly supports both safety-related and non-safety-related instrumentation loops in industrial safety instrumented systems (SIS).

Each channel on the FC-TSGASH-1624P V1.0 incorporates a high-precision 500 Ohm resistor to convert input current signals into 0–4 VDC levels for processing by the SAI-1620m module with 0.1% accuracy. To safeguard connected instrumentation and loop wiring, every channel is individually protected by a 500 mA fast-acting fuse. The module routes input signals to single or redundant SAI-1620m modules using standard SICC-0001/Lx system interconnection cables.

In addition to primary signal conversion, the FC-TSGASH-1624P V1.0 features dedicated interfaces for HART communication. By providing direct connection points for multiplexer solutions from MTL or Pepperl+Fuchs (P+F), the module enables online HART diagnostic passthrough without disrupting safety loop integrity. The assembly is built on a DIN EN rail snap-in footprint and powered via a 24 VDC external supply line.

Features

  • 16-Channel Analog Interface: Accommodates up to sixteen 0–20 mA (0–25 mA maximum) gas and flame detector loops with a shared common 0 V connection.
  • Precision Signal Conversion: High-accuracy 500 Ohm onboard resistors convert input current signals to 0–4 VDC output levels for the SAI-1620m module.
  • Individual Channel Fusing: Equipped with 500 mA Schurter fuses (5x20 mm) per channel to protect field power lines and field devices against short-circuit events.
  • Integrated HART Multiplexer Support: Dedicated onboard CN2 and CN3 connectors enable direct integration with Pepperl+Fuchs and MTL HART multiplexer solutions using standard cable assemblies.
  • Dedicated Shield Connections: Features 16 dedicated screw terminals designed for field cable shield grounding, optimizing noise immunity in critical monitoring applications.
  • External Power Supply Voltage Monitoring: Allows Safety Manager software to continuously monitor connected 24 VDC supply voltage levels through the safe high-density analog input chassis.
  • Dual DIN Rail Compatibility: Mounting provision supports both TS32 and TS35 x 7.5 DIN EN rails for flexible cabinet installations.

Applications

  • Safety Instrumented Systems (SIS): Field wiring termination for combustible gas, toxic gas, and optical flame detectors connected to Honeywell Safety Manager systems.
  • Process Safety Management: Analog input signal conditioning and HART diagnostic integration for critical 2-wire and 3-wire field transmitters.
  • HART Asset Management Integration: Passthrough connection point for MTL4850 or Pepperl+Fuchs HART multiplexers to support remote instrument calibration and device health monitoring.

Technical Specifications

General

Parameter Specification
Manufacturer Honeywell
Exact Model Number FC-TSGASH-1624P V1.0
Part Number TSGASH-1624P
Product Type Safe Gas/Flame Detector Input Field Termination Assembly (FTA)
System Platform Safety Manager
Input Channels 16 Analog Inputs
Accuracy 0.1%

Electrical & Input Ratings

Parameter Specification
Power Supply Requirement 24 VDC external, 2.5 mA (without field loads)
Input Current Range 0–25 mA (0–20 mA nominal)
Input Resistance 500 Ohm (+/- 5%)
Output Voltage to SAI-1620m 0–4 VDC
Output Voltage to HART Multiplexer Max. 11 V peak-to-peak
HART Series Impedance > 2 uF

Protection & Fusing

Parameter Specification
Fuse Rating 500 mA
Fuse Dimensions 5 x 20 mm
Fuse Manufacturer & Part Number Schurter 0001.2501
Fuse Voltage Ratings 250 VAC / 300 VDC
Fuse Derating Curve Linear from 0.5 A at 25 degC to 0.35 A at 70 degC ambient

Mechanical & Environmental

Parameter Specification
Dimensions (L x W x H) 225 x 109 x 60 mm (8.86 x 4.29 x 2.36 in)
Used Rail Length 226 mm (8.90 in)
Compatible DIN EN Rails TS32 / TS35 x 7.5
Screw Terminal Wire Diameter Max. 2.5 mm2 (AWG 14)
Screw Terminal Strip Length 7 mm (0.28 in)
Screw Terminal Tightening Torque 0.5 Nm (0.37 ft-lb)

Connections / Interfaces

Interface / Pin Function
Screw Terminals 1 to 64 Field wiring connections arranged in 16 groups of 4 screw terminals, including dedicated channel ground terminals
Ground Screw Terminals Top left ground connections for earth bonding field cable shields
Power Connector (+) Pin 1 connected to +24 VDC bus bar via Weidmuller BVZ 7.62HP/02/180F SN connector
Power Connector (-) Pin 2 connected to 0 VDC bus bar via Weidmuller BVZ 7.62HP/02/180F SN connector
CN1 Connector Interface for SICC-0001/Lx cable to SAI-1620m analog input module
CN2 Connector Dedicated interface for Pepperl+Fuchs HART multiplexer units (KFD0-HMS-16 or KFD2-HMM-16 via K-MH26 cable)
CN3 Connector Dedicated interface for MTL HART multiplexer units (MTL4850 via MTL FLAT20-2.2 cable)

Installation Guidelines

  1. Pre-Installation Inspection: Verify physical integrity and check that all 16 channel fuses (500 mA, 5x20 mm) are fully seated in their respective holders before mounting.
  2. DIN Rail Mounting: Snap the assembly securely onto a standard TS32 or TS35 x 7.5 DIN rail within the control cabinet, allowing at least 226 mm of clear rail width.
  3. Power Wiring Connection: Strip external 24 VDC power conductors to 8 mm (0.28 in). Connect the supply lines to the included keyed Weidmuller BVZ 7.62HP 2-pole plug, ensuring proper polarity (+ to Pin 1, - to Pin 2), and engage the red locking slides.
  4. Field Signal Wiring: Connect 2-wire or 3-wire gas and flame detectors to screw terminal groups 1 through 64. Strip wires to 7 mm (0.28 in) and tighten terminal screws to a torque of 0.5 Nm.
  5. Shield Grounding: Connect individual field cable shield drain wires to the dedicated shield terminal on each channel group and bond cabinet earth ground to the top-left ground screw connections.
  6. System Interconnection: Connect the SICC-0001/Lx cable from connector CN1 on the FTA to the primary (or redundant pair) SAI-1620m module in the Safety Manager chassis.

Commissioning & Maintenance Recommendations

  • External Power Verification: Confirm that Safety Manager software detects normal external supply voltage levels across the assembly via the SAI-1620m module diagnostic interface.
  • Fuse Replacement: If a transmitter loop fails, check the corresponding channel fuse (F1 to F16). Replace blown fuses exclusively with Schurter 0001.2501 (500 mA, 5x20 mm, 250 VAC / 300 VDC) fuses to maintain safety compliance.
  • HART Integration Check: When using external HART multiplexers, verify that the dedicated CN2 (P+F) or CN3 (MTL) ribbon cables are fully seated and that loop communications function without signal attenuation.

Compliance and Certifications

  • CE Mark: European Conformity
  • TUV: Safety Approved for High-Integrity Applications
  • UL Listed: Underwriters Laboratories Standard Compliance
  • CSA Certified: Canadian Standards Association Certified

FAQ

What primary function does the Honeywell FC-TSGASH-1624P V1.0 serve in a Safety Manager system?

The Honeywell FC-TSGASH-1624P V1.0 acts as a field termination assembly that interfaces 16 field-mounted 0–20 mA gas or flame detectors with the SAI-1620m safe high-density analog input module, providing signal conditioning, power distribution, and channel fusing.

How does the Honeywell FC-TSGASH-1624P V1.0 handle HART protocol communications?

The assembly features dedicated onboard connectors CN2 and CN3 to interface directly with HART multiplexer units from Pepperl+Fuchs (KFD0-HMS-16 / KFD2-HMM-16) or MTL (MTL4850), allowing HART diagnostic data pass-through without interrupting safety inputs.

What type of fuses are required for channel protection on the Honeywell FC-TSGASH-1624P V1.0?

Each channel on the assembly utilizes a 500 mA fast-acting fuse. The manufacturer specified replacement is a Schurter 0001.2501 fuse measuring 5x20 mm with ratings of 250 VAC and 300 VDC.

How connects power to the Honeywell FC-TSGASH-1624P V1.0 module?

External 24 VDC power connects through a 2-pole keyed Weidmuller BVZ 7.62HP/02/180F SN connector, where Pin 1 connects to the +24 VDC bus bar and Pin 2 connects to the 0 VDC bus bar.

View all FAQs →

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell FC-TSGASH-1624P Safety Manager Field Termination Assembly

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 4
Only 8 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Dots
Country of origin
United States

Technical knowledge

Diagnosing DeltaV SE5009 Power Problems Before Replacement

A field checklist for separating 24 VDC input, carrier bus, output derating and alarm-contact faults before replacing an Emerson SE5009.

Commissioning Quantum Inputs with the 140XSM00200 Simulator

A controlled commissioning method for using the 140XSM00200 simulator to verify Modicon Quantum input mapping and interlocks before reconnecting field wiring.

Commissioning PLX32-EIP-MBTCP: Subnets, Registers, and RPI

A commissioning checklist for the ProSoft PLX32-EIP-MBTCP covering subnet separation, register contracts, EtherNet/IP timing, failure tests and replacement records.

Diagnosing IC693MDL916 Relay Outputs Before Module Replacement

A field checklist for IC693MDL916 relay commands, terminal blocks, load current, switching rate and contact-side measurements.

Troubleshooting Beckhoff KL1512 Counter Inputs and Mapping

A field checklist for KL1512 signal thresholds, counter direction, process data and the KL1512-to-KS1512 wiring difference.

Troubleshooting Beckhoff EPP2008-0001 Output Faults

A field checklist for EPP2008-0001 current limits, supply voltage, channel LEDs, connector coding and load-related output faults.