Honeywell

Honeywell MC-TAIH14 51305887-150 Experion PKS High Level Analog Input HART FTA Module

SKU MC-TAIH14 51305887-150

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Honeywell
  • Product No.: MC-TAIH14 51305887-150
  • Origin United States
  • Product Type: Analog Input FTA
  • Barcode: 8537101190
  • Payment: T/T, Western Union
  • Weight: 0.85 kg
  • Dimensions: 310 x 125 x 60 mm
  • Shipping port: Xiamen
  • Warranty: 12 months

Tags

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell MC-TAIH14 51305887-150 Experion PKS High Level Analog Input HART FTA Module

Quantity

Product Description

Description

The Honeywell MC-TAIH14 (Part Number: 51305887-150) is a High Level Analog Input HART Field Termination Assembly (HLAIHART FTA) designed for integration within Honeywell Process Manager (PM), Advanced Process Manager (APM), High Performance Process Manager (HPM), and Experion Process Knowledge System (PKS) I/O architectures. Acting as the direct physical interface between field-mounted process transmitters and system Input/Output Processors (IOPs), the assembly channels 16 analog input signals while facilitating pass-through Highway Addressable Remote Transducer (HART) digital communication.

Featuring a 16-channel architecture with compression-style terminal blocks, the MC-TAIH14 enables clean termination of 4-20 mA field loops from transmitters measuring pressure, flow, level, and temperature. The board is built on Honeywell Size B mounting dimensions, providing physical layout compatibility for standard cabinet channel mounting alongside adjacent process termination assemblies.

The MC-TAIH14 assembly (51305887-150) establishes reliable signal paths for real-time regulatory control loops and asset management functions. By interfacing high-level analog signals directly to system I/O modules, it simplifies cabinet wiring, shields control room electronics from field-side interference, and provides access points for HART hand-held communicators and asset management software suites.

Designed for high-density control environments, the board functions seamlessly across redundant and non-redundant system hardware layouts. Its structured terminal arrangement reduces field installation time and ensures long-term operational continuity across continuous process automation plants.

Features

  • 16-Channel Capacity: Supports up to 16 individual high-level analog input channels for high-density field signal processing.
  • HART Protocol Support: Facilitates simultaneous transmission of standard 4-20 mA analog signals and HART digital communications for smart field instrument diagnostics.
  • Compression Terminal Blocks: Equipped with reliable compression-type (C) wiring terminals to simplify field instrument loop connections.
  • Size B Mounting Form Factor: Designed in standard Honeywell Size B dimensions for uniform cabinet layout and channel mounting integration.
  • System IOP Compatibility: Integrates directly with Honeywell High Level Analog Input (HLAI) Processors via standard pre-fabricated I/O interface cables.

Applications

  • Smart Field Transmitter Interfacing: Terminating 4-20 mA HART-enabled pressure, temperature, differential pressure, and level transmitters in process control loops.
  • Asset Management Routing: Routing digital HART variables and field device diagnostic parameters to maintenance software systems without interrupting control loops.
  • DCS Cabinets Integration: Structuring high-density analog signal wiring within standard Honeywell TPS and Experion Process Knowledge System (PKS) enclosures.

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Exact Model / Order Code MC-TAIH14
Part Number 51305887-150
Function / Subtype High Level Analog Input HART FTA (HLAIHART)
Channel Count 16 Channels
Terminal Type Compression Terminals (C)
Mounting Size Size B
Signal Type 4-20 mA DC / HART Digital Communication
Compatibility Honeywell Process Manager (PM / APM / HPM / Experion)

Connections / Interfaces

Interface / Connection Point Function
Field Compression Terminals Secure connection points for 16 individual 4-20 mA HART analog input field loops
System Interface Connector Multi-pin header for standard pre-fabricated cable connection to system I/O Processors

Installation Guidelines

  1. Pre-Installation Verification: Inspect the assembly part number (MC-TAIH14 / 51305887-150) to verify matching model specifications and physical integrity prior to mounting.
  2. Mounting: Snap or latch the Size B assembly into the dedicated FTA mounting channel inside the cabinet enclosure.
  3. Power Isolation: De-energize loop power and field-side circuits before wiring to prevent arc flash or electrical damage.
  4. Field Loop Connection: Connect field instrument wiring to the compression terminals, adhering to polarity markings for each of the 16 analog channels.
  5. System Interface Cable: Connect the pre-fabricated Honeywell I/O interface cable between the FTA board connector and the designated IOP slot in the cardfile.
  6. Shield Bonding: Ensure field cable shields are properly grounded according to plant EMC and Honeywell system installation rules.
  7. Commissioning Checks: Measure loop current on active channels, confirm analog-to-digital signal scaling at the controller, and test HART pass-through communication using a HART communicator.
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
FAQ
What is the primary function of the Honeywell MC-TAIH14 FTA?
The Honeywell MC-TAIH14 is a 16-channel High Level Analog Input HART Field Termination Assembly (HLAIHART FTA) that connects 4-20 mA smart field transmitters to Honeywell I/O Processors while supporting HART digital communications.
What terminal style is used on the MC-TAIH14 51305887-150 assembly?
The MC-TAIH14 (51305887-150) uses compression-style (C) terminal blocks for direct and secure field instrument wiring connections.
What mounting frame size does the MC-TAIH14 occupy?
The MC-TAIH14 module is built to Honeywell Size B physical dimensions, fitting standard Size B mounting channels within DCS enclosures.
Does the MC-TAIH14 support HART communication pass-through?
Yes, as an HLAIHART Field Termination Assembly, it allows HART digital signals to pass through the 4-20 mA analog loops for device diagnostics and configuration.
Reviews

MC-TAIH14 51305887-150

Stock & lead time on request

Call
1 of 3

Honeywell MC-TAIH14 51305887-150 Experion PKS High Level Analog Input HART FTA Module

Only 5 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: MC-TAIH14 51305887-150

  • Country of origin:United States

  • Product Type: Analog Input FTA

  • Barcode: 8537101190

  • Payment: T/T, Western Union

  • Weight: 850g

  • Dimensions: 310 x 125 x 60 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Product Description

Description

The Honeywell MC-TAIH14 (Part Number: 51305887-150) is a High Level Analog Input HART Field Termination Assembly (HLAIHART FTA) designed for integration within Honeywell Process Manager (PM), Advanced Process Manager (APM), High Performance Process Manager (HPM), and Experion Process Knowledge System (PKS) I/O architectures. Acting as the direct physical interface between field-mounted process transmitters and system Input/Output Processors (IOPs), the assembly channels 16 analog input signals while facilitating pass-through Highway Addressable Remote Transducer (HART) digital communication.

Featuring a 16-channel architecture with compression-style terminal blocks, the MC-TAIH14 enables clean termination of 4-20 mA field loops from transmitters measuring pressure, flow, level, and temperature. The board is built on Honeywell Size B mounting dimensions, providing physical layout compatibility for standard cabinet channel mounting alongside adjacent process termination assemblies.

The MC-TAIH14 assembly (51305887-150) establishes reliable signal paths for real-time regulatory control loops and asset management functions. By interfacing high-level analog signals directly to system I/O modules, it simplifies cabinet wiring, shields control room electronics from field-side interference, and provides access points for HART hand-held communicators and asset management software suites.

Designed for high-density control environments, the board functions seamlessly across redundant and non-redundant system hardware layouts. Its structured terminal arrangement reduces field installation time and ensures long-term operational continuity across continuous process automation plants.

Features

  • 16-Channel Capacity: Supports up to 16 individual high-level analog input channels for high-density field signal processing.
  • HART Protocol Support: Facilitates simultaneous transmission of standard 4-20 mA analog signals and HART digital communications for smart field instrument diagnostics.
  • Compression Terminal Blocks: Equipped with reliable compression-type (C) wiring terminals to simplify field instrument loop connections.
  • Size B Mounting Form Factor: Designed in standard Honeywell Size B dimensions for uniform cabinet layout and channel mounting integration.
  • System IOP Compatibility: Integrates directly with Honeywell High Level Analog Input (HLAI) Processors via standard pre-fabricated I/O interface cables.

Applications

  • Smart Field Transmitter Interfacing: Terminating 4-20 mA HART-enabled pressure, temperature, differential pressure, and level transmitters in process control loops.
  • Asset Management Routing: Routing digital HART variables and field device diagnostic parameters to maintenance software systems without interrupting control loops.
  • DCS Cabinets Integration: Structuring high-density analog signal wiring within standard Honeywell TPS and Experion Process Knowledge System (PKS) enclosures.

Technical Specifications

Parameter Specification
Manufacturer Honeywell
Exact Model / Order Code MC-TAIH14
Part Number 51305887-150
Function / Subtype High Level Analog Input HART FTA (HLAIHART)
Channel Count 16 Channels
Terminal Type Compression Terminals (C)
Mounting Size Size B
Signal Type 4-20 mA DC / HART Digital Communication
Compatibility Honeywell Process Manager (PM / APM / HPM / Experion)

Connections / Interfaces

Interface / Connection Point Function
Field Compression Terminals Secure connection points for 16 individual 4-20 mA HART analog input field loops
System Interface Connector Multi-pin header for standard pre-fabricated cable connection to system I/O Processors

Installation Guidelines

  1. Pre-Installation Verification: Inspect the assembly part number (MC-TAIH14 / 51305887-150) to verify matching model specifications and physical integrity prior to mounting.
  2. Mounting: Snap or latch the Size B assembly into the dedicated FTA mounting channel inside the cabinet enclosure.
  3. Power Isolation: De-energize loop power and field-side circuits before wiring to prevent arc flash or electrical damage.
  4. Field Loop Connection: Connect field instrument wiring to the compression terminals, adhering to polarity markings for each of the 16 analog channels.
  5. System Interface Cable: Connect the pre-fabricated Honeywell I/O interface cable between the FTA board connector and the designated IOP slot in the cardfile.
  6. Shield Bonding: Ensure field cable shields are properly grounded according to plant EMC and Honeywell system installation rules.
  7. Commissioning Checks: Measure loop current on active channels, confirm analog-to-digital signal scaling at the controller, and test HART pass-through communication using a HART communicator.
Loading product navigation…

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell MC-TAIH14 51305887-150 Experion PKS High Level Analog Input HART FTA Module

What is the primary function of the Honeywell MC-TAIH14 FTA?

The Honeywell MC-TAIH14 is a 16-channel High Level Analog Input HART Field Termination Assembly (HLAIHART FTA) that connects 4-20 mA smart field transmitters to Honeywell I/O Processors while supporting HART digital communications.

What terminal style is used on the MC-TAIH14 51305887-150 assembly?

The MC-TAIH14 (51305887-150) uses compression-style (C) terminal blocks for direct and secure field instrument wiring connections.

What mounting frame size does the MC-TAIH14 occupy?

The MC-TAIH14 module is built to Honeywell Size B physical dimensions, fitting standard Size B mounting channels within DCS enclosures.

Does the MC-TAIH14 support HART communication pass-through?

Yes, as an HLAIHART Field Termination Assembly, it allows HART digital signals to pass through the 4-20 mA analog loops for device diagnostics and configuration.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

1756-L73 Firmware Upgrade Guide: v19 vs v21/v31 Decision

Replacing a 1756-L73 does not automatically mean upgrading its firmware. This guide compares v19.013, v21.011 and v31.011, focusing on project compatibility, HMI communications, legacy networks and...

Implementing 3-Switch XOR Ladder Logic with Internal Bit

Implement a 3-SPST switch XOR light circuit in LogixPro or RSLogix 500 using an internal relay bit. Includes truth tables, boolean equations, and verified.

Building a Modbus RTU Network with CompactLogix and DeltaV

Integrate Allen-Bradley CompactLogix, Caterpillar ATS, and generators into DeltaV DCS over Modbus RTU. Covers ProSoft MVI69-MCM, Miille DIN266 gateways.

ONS Instruction Not Energizing OTE in Studio 5000 Ladder Logic

ONS instruction fires but the OTE coil never latches in Studio 5000 because the one-shot is only true for one scan. Use OTL/OTU or seal-in logic instead.

Kinetix 5500 EtherNet/IP Network Switch Requirements and Topology

Configure Allen-Bradley Kinetix 5500 servo drives on EtherNet/IP. Covers CIP Sync, IEEE 1588 V2 timing, Stratix selection, DLR topology, and HMI.

Moving Average Filtering in DCS and PLC Analog Control

A moving-average filter is the sliding-window smoother most instrument engineers drop into DCS and PLC analog paths. Here is how the window works, how N and sample time set lag, and when a...