Engineered to handle complex automation tasks in modern industrial environments, the FX3U-48MR/DS is a high-performance base unit belonging to the renowned MELSEC FX3U series of programmable logic controllers. This compact PLC features a robust configuration of 24 digital inputs and 24 relay outputs, making it highly suitable for applications requiring reliable mechanical switching and high-speed control logic. Operating on a 24V DC power supply, this controller provides exceptional processing speeds and flexible expansion capabilities through its unique dual-bus architecture, allowing seamless integration with additional digital, analog, and network communication adapters.

Features

  • High-speed execution time of 0.065 microseconds per basic instruction.
  • Large internal program memory of up to 64,000 steps for complex control logic.
  • Integrated 24 digital inputs (24V DC, sink or source configurable).
  • Integrated 24 mechanical relay outputs (rated up to 2A per point).
  • Support for high-speed counter inputs (up to 100 kHz) and positioning tasks.
  • Dual-bus system structure allowing simultaneous connection of FX series expansion blocks and high-speed FX3U special adapters.
  • Inherent maintenance-free operation with integrated real-time clock.

Applications

  • Conveyor and material handling systems
  • Packaging and labeling machines
  • Food and beverage processing equipment
  • Water and wastewater pump control
  • HVAC and building automation networks

Technical Specifications

Manufacturer Mitsubishi Electric
Part Number / Model FX3U-48MR/DS
Controller Series MELSEC FX3U
Power Supply Voltage 24V DC (+20% / -15%)
Power Consumption 35W
Integrated Inputs 24 points (24V DC, sink/source)
Integrated Outputs 24 points (Relay, 2A/point, 8A maximum per common terminal)
Total I/O Points 48 points
Execution Speed 0.065 microseconds (basic instruction)
Program Memory 64,000 steps (RAM / Flash memory cassette optional)
Communication Port RS-422 (built-in)
Operating Temperature 0 to 55 degC
Storage Temperature -25 to 75 degC
Mounting Type 35mm DIN Rail or direct screw mounting

Connections and Interfaces

Terminal Block Label Function Assignment
24V / 0V Main DC power supply input terminals
S/S Input signal common terminal (Sink or Source selection)
X0 to X27 Digital input connection points
Y0 to Y27 Relay output connection points
COM0 to COM5 Common reference terminals for relay outputs
Protective Ground (PE) System safety grounding point

Installation Guidelines

  • Ensure all incoming power lines are disconnected before performing installation or wiring work.
  • Mount the unit horizontally on a standard 35mm DIN rail or via direct mounting screws onto a flat panel.
  • Maintain a minimum ventilation clearance of 50mm above, below, and on the sides of the PLC to prevent heat buildup.
  • Keep signal and high-voltage AC cables in separate cable ducts to minimize electromagnetic interference (EMI).
  • Connect the protective ground terminal to a dedicated class D ground (resistance of 100 ohms or less).

Compliance and Certifications

  • CE (EMC and Low Voltage Directive)
  • UL / cUL Listed
  • KC (Korean Certification)

FAQ

What power supply does the FX3U-48MR/DS require?

The FX3U-48MR/DS requires a 24V DC power supply, as indicated by the 'DS' suffix in the model number.

What output type is used in the FX3U-48MR/DS controller?

This model is equipped with mechanical relay outputs, which support up to 2A per point for both AC and DC switching application loads.

Is the digital input configuration of this PLC sink or source?

The 24V DC digital inputs on the FX3U-48MR/DS can be configured as either sink or source depending on the wiring of the S/S terminal.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 10 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Technical knowledge

1746-A7 Chassis Replacement Checks: Slots, Power and Interconnects

An engineering checklist for replacing an Allen-Bradley 1746-A7: verify chassis series, backplane loading, slot plan, interconnect cables, mounting, grounding and receiving condition.

IC200MDL650 Replacement Checks: Logic Polarity, Filters, and Commons

A field replacement guide for GE Fanuc IC200MDL650 covering revision-dependent negative logic, four common groups, 24 VDC thresholds, input filtering, carrier checks and commissioning records.

IC697CPX935 Replacement Checks: Memory, Ports, and Rack Power

A field-focused IC697CPX935 replacement guide covering fast memory, firmware-dependent serial behavior, rack power, cooling, I/O architecture and backup records.

IC693DSM324 Replacement Checks: FSSB, Firmware and Follower Control

A field-focused IC693DSM324 replacement guide covering Series 90-30 host checks, FSSB servo-chain records, 5 V power budget, firmware limits, follower control and commissioning.

HIMA F3430 Replacement Checks: Contact Ratings and Safety Limits

A field-focused HIMA F3430 replacement guide covering relay contact ratings, DC load derating, fusing, F3330/F3331 differences, safety restrictions and commissioning records.

IC697PWR710 Replacement Checks: Load Budget and Dual-Rack Limits

A field-focused IC697PWR710 replacement guide covering 5 V load calculations, dual-rack limits, extension cables, input checks, protection behavior and hardware revision risks.