1 of 1

Mitsubishi Electric Q64TCRTBW MELSEC Q Series Temperature Control Unit

Mitsubishi Electric Q64TCRTBW MELSEC Q Series Temperature Control Unit

Only 10 item(s) left in stock
  • Manufacturer: Mitsubishi Electric

  • Product No.: Q64TCRTBW

  • Country of origin:United States

  • Product Type: Temperature Control Modules

  • Payment: T/T, Western Union

  • Weight: 1300g

  • Dimensions: 98 mm x 55.2 mm x 112 mm

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantity
View full details

Description

Integrating high-accuracy thermal loops directly into the MELSEC Q control architecture, the Mitsubishi Electric Q64TCRTBW temperature control module delivers hardware-based PID processing across four independent channels. This specialized module interfaces directly with Pt100 and JPt100 platinum resistance temperature detectors (RTDs), executing high-speed 500 ms sampling cycles to guarantee thermal stability in precision processes. By offloading PID calculations and heater monitoring from the host PLC CPU, the Q64TCRTBW ensures deterministic control and fast response times, outputting pulse signals via transistor outputs to drive external solid-state relays (SSRs).

Features

  • Four-Channel Control: Manages up to four independent temperature loops per module.
  • RTD Compatibility: Supports standard Pt100 and JPt100 resistance temperature detectors.
  • Heater Disconnection Detection: Supports real-time current monitoring using CTL-series external current sensors to detect element burnout.
  • Autotuning PID: Integrated tuning algorithms automatically calculate optimal proportional, integral, and derivative constants.
  • Transistor Outputs: Built-in transistor pulse outputs (10 to 30 VDC, 0.1 A per point) optimized for solid-state relay driving.
  • Galvanic Isolation: Complete transformer insulation between input channels and ground, and between individual channels to prevent cross-talk and common-mode noise.

Applications

  • Semiconductor manufacturing wafer heating panels and oxidation furnaces.
  • Plastic injection molding, extrusion barrels, and die temperature control.
  • Food processing ovens, packaging sealing bars, and hot-melt systems.
  • Environmental simulation chambers, laboratory incubators, and industrial autoclaves.

Technical Specifications

Parameter Specification Value
Manufacturer Mitsubishi Electric
Model Number Q64TCRTBW
Control Input Channels 4 channels
Sensor Input Type Pt100, JPt100 (3-wire RTD)
Sampling Cycle 500 ms for all 4 channels
Control Output Transistor output (ON/OFF pulse)
Rated Load Voltage 10 to 30 VDC
Maximum Load Current 0.1 A per point, 0.4 A per common
Input Impedance 1 M-Ohm
Accuracy (at 25 +/- 5 degC) Full scale x (+/- 0.3%)
Accuracy (0 to 55 degC) Full scale x (+/- 0.7%)
Isolation Method Transformer isolation between inputs and ground, and between input channels
Withstand Voltage 500 VAC for 1 minute
I/O Slot Allocation 32 points (16 free points + 16 intelligent points)
Internal Current Consumption (5 VDC) 0.64 A
External Connections Two 18-point M3 screw terminal blocks
Dimensions (H x W x D) 98 mm x 55.2 mm x 112 mm
Module Weight 0.30 kg
Shipping Weight (Calculated) 1.3 kg

Empirical Engineering Insights

Alternative Models & Compatibility

The "BW" suffix indicates integrated heater disconnection detection capabilities. When replacing a standard Q64TCRT module with a Q64TCRTBW, confirm that the I/O allocation parameters in GX Works2 or GX Works3 are updated. Although it physically occupies only one slot on the MELSEC Q base unit, the system reserves 32 I/O points (the equivalent of two standard slots) to handle control variables and the additional current-sensor inputs.

Application Pitfalls & Engineering Notes

Executing auto-tuning on systems with extremely high thermal dynamics or rapid heat dissipation can lead to PID overshoot or loop calculation timeouts. In highly dynamic thermal processes, manually tuning the proportional band (P) from 0.0% (which defaults to 2-position/ON-OFF control) to a conservative initial value is recommended to prevent thermal stress on solid-state devices. Additionally, ensure the external current sensor (CTL-6-P, CTL-6-PH, or CTL-12-S36-8) is matched to the specific heater load to avoid false disconnection alarms.

Commissioning & Wiring Tips

Platinum RTDs (Pt100/JPt100) are highly vulnerable to induced electromagnetic noise. Always run 3-wire RTD cabling in dedicated instrument trays separate from high-voltage AC lines. Shielded cables must be grounded exclusively at a single point on the control cabinet ground bar to prevent ground loops. Note that any resistance mismatch among the three RTD wires will cause direct measurement drift; ensure all three connections are of identical length and wire gauge.

Installation Guidelines

CRITICAL SAFETY WARNING

Before attempting to mount, wire, or remove the module, ensure that all external power sources feeding the PLC rack and the heater circuits are completely de-energized. Failure to isolate power can result in electrical shock, hardware destruction, or unpredictable output behavior.

1

Hook the upper mounting tab of the module into the MELSEC Q base unit slot guide and press the module firmly down into the backplane connector. Tighten the module fixing screw to 0.36 to 0.48 N-m.

2

Perform wiring of the RTD inputs and transistor outputs onto the 18-point terminal block. Tighten the terminal block screws to a torque of 0.42 to 0.58 N-m using M3 crimp terminals.

3

Route CT sensor cables through the dedicated current sensor input terminals on the module if heater burnout monitoring is utilized.

4

Power up the PLC base unit, download the I/O configurations, and execute an initial autotune cycle to establish base PID control loops.

Loading product navigation…

What is the primary function of the Q64TCRTBW module?

It provides 4 channels of independent PID temperature loop control on the MELSEC Q PLC backplane, interfacing with Pt100/JPt100 RTDs and outputting transistor pulses to drive solid-state relays.

How is the heater disconnection feature wired on this module?

Heater current is monitored through external CT sensors (like CTL-6-P or CTL-12-S36-8) wired to the dedicated CT input terminals on the dual 18-point terminal blocks.

Can I use 2-wire RTDs directly with the Q64TCRTBW?

No, the module is designed specifically for 3-wire Pt100/JPt100 sensors to compensate for cable resistance. Using 2-wire sensors will lead to significant measurement inaccuracy.

How many I/O points does the Q64TCRTBW occupy in the PLC parameters?

It occupies 32 points. It requires an allocation in parameters consisting of 16 free points and 16 intelligent points.

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
United States

Recently Viewed Products

Technical knowledge

Math Operations Using OpenPLC for Industrial Automation Applications

This article explains how PLC systems perform core mathematical operations such as addition, subtraction, multiplication, division, modulo, and exponentiation within industrial automation. It shows...

Advanced Boolean Logic with FBD PLC Programming: Practical Industrial Applications Beyond Basic Logic

The article explains several advanced Boolean logic functions used in PLC programming beyond basic AND, OR, and NOT operations. It covers how tools like truth tables, multiplexers, pulse generators,...

Boolean Logic in PLC Programming: Understanding FBD Logic Gates

Boolean logic is the foundation of every PLC program. From simple machine controls to complex industrial automation systems, logic gates determine how controllers respond to changing inputs and...

Deep-Dive Guide to Industrial Firewalls and OT Network Segmentation

Industrial firewalls play a critical role in OT cybersecurity, protecting PLC, DCS, and SCADA networks through segmentation, ingress/egress control, and IDS/IPS integration aligned with IEC 62443...

Guide to Robotic Grippers: From Delicate Handling to Heavy-Duty Automation

Modern robotic grippers are evolving beyond traditional mechanical jaws. From gecko-inspired adhesive systems and soft food-grade grippers to AI-powered warehouse tools, advanced gripping...

Throwback: How Early Electric Motors Changed Underground Mining

From rope-driven DC compressors to battery-powered mine carts, early mining operations marked a turning point in industrial electrification. This article explores how electric motors transformed...