Omron

Omron CJ1W-DA042V CJ1 Series Analog Output Unit

SKU CJ1W-DA042V

In stock
  • 12-month warranty
  • Free returns within 30 days
  • Manufacturer: Omron

  • Product No.: CJ1W-DA042V

  • Country of origin:Japan

  • Product Type: Analog Output Modules

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Description

High-speed, high-accuracy analog control is delivered by the Omron CJ1W-DA042V, a specialized 4-channel analog output module engineered for the Omron CJ-Series PLC platform. This module converts digital values inside the PLC into analog voltage signals, providing high-speed direct conversion capabilities to interface with variable speed drives, actuators, control valves, and other analog field instruments.

Featuring individual channel configuration, the CJ1W-DA042V supports independent signal range selection for each of its four outputs. The system's ultra-fast conversion cycle, scaling down to 20 microseconds for a single point, makes it exceptionally suited for dynamic motion control and high-speed process modulation where real-time accuracy is critical.

Features

  • Four independent, high-precision analog output channels.
  • Supports wide signal ranges: 1 to 5 V, 0 to 10 V, and -10 to 10 V.
  • Adjustable resolution up to 1/40,000 for high-precision control requirements.
  • Ultra-fast direct conversion mode with conversion times as fast as 20 microseconds.
  • Independently configurable output signal ranges per channel.
  • Equipped with a removable terminal block for simplified installation and maintenance.
  • Occupies a single unit number allocation on the PLC backplane.

Applications

  • High-speed positioning and servo drive speed control.
  • Precision process control loop modulation (valves, dampers, actuators).
  • Dynamic test bench and laboratory automation systems.
  • Industrial manufacturing and packaging line automation.

Technical Specifications

Manufacturer Omron
Model/Part Number CJ1W-DA042V
Series CJ-Series / CJ1
Module Type Analog Output Unit (High-speed type)
Number of Outputs 4 points
Signal Range (Resolution) 1 to 5 V (1/10,000)
0 to 10 V (1/20,000)
-10 to 10 V (1/40,000)
Conversion Period 1 point: 20 us
2 points: 25 us
3 points: 30 us
4 points: 35 us (Direct conversion provided)
Accuracy (at 25 degC) ±0.3% of F.S.
External Connection Removable terminal block
Allocated Unit Numbers 1
Current Consumption 0.40 A at 5 VDC
Shipping Weight 2.0 kg

Installation Guidelines

Mounting: Securely mount the module onto the CJ-series CPU rack or expansion rack. Ensure the locking levers at the top and bottom of the unit are fully engaged to guarantee proper connection to the backplane.

Wiring: Use shielded twisted-pair cables for analog output connections to minimize electromagnetic interference. Route signal lines away from high-voltage power cables or motor lines.

Grounding: Connect the shield wire of the output cables to the ground terminal of the PLC system or control panel. Ensure a single-point ground is maintained to avoid ground loop currents.

System Maintenance: Always power down the PLC system before removing or attaching the terminal block or the module itself to protect sensitive internal CMOS components from ESD and voltage surges.

FAQ

What is the conversion speed of the CJ1W-DA042V?

The conversion period depends on the number of active points configured: 20 us for 1 point, 25 us for 2 points, 30 us for 3 points, and 35 us for 4 points.

Can I configure different voltage ranges for each output channel?

Yes, the signal range selection can be configured separately for each of the four output channels.

What analog output resolutions does the Omron CJ1W-DA042V support?

It supports a resolution of 1/10,000 for the 1 to 5 V range, 1/20,000 for the 0 to 10 V range, and 1/40,000 for the -10 to 10 V range.

Does the module feature a removable terminal block?

Yes, the module is designed with a removable terminal block, simplifying installation, testing, and maintenance procedures.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 2 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Technical knowledge

IC693CPU313 Memory Retention and Expansion Limits Before Replacement

A practical replacement guide for the GE Fanuc IC693CPU313, covering its embedded five-slot architecture, memory backup, firmware-dependent capacity and why it cannot use Series 90-30 expansion racks.

Bently Nevada 3500/40M vs 3500/42M: I/O and Channel Checks Before Replacement

A field-focused comparison of Bently Nevada 3500/40M and 3500/42M monitor inputs, channel-pair configuration, rear I/O options, external termination hardware and firmware checks before replacement.

Allen-Bradley 1746-NR4 RTD Faults: Wiring, Excitation, and Filter Checks

A field checklist for diagnosing Allen-Bradley 1746-NR4 RTD and resistance inputs, including sensor curves, lead compensation, excitation current, filter timing and channel diagnostics.

Replacing an Allen-Bradley 1785-L40B: PLC-5/40 Checks Before Migration

A field-focused checklist for replacing an Allen-Bradley 1785-L40B or planning a PLC-5/40 migration, covering backups, 1771 I/O mapping, DH+/RIO channels, revision risks and commissioning.

Allen-Bradley 1747-SN: RIO Mapping and Link Fault Checks

Replacing an Allen-Bradley 1747-SN scanner? Check SLC 500 logical rack and G-file mapping, link speed, cable termination, COMM/FAULT LEDs and hardware series before blaming the module or changing the...

Allen-Bradley 1771-IG: TTL Logic and 5 V Wiring Checks

Check 1771-IG TTL HIGH/LOW logic thresholds, field supply ripple and 1771-WC wiring before replacing an input module.