Description

Designed for direct integration with Omron CP-series PLC architectures, the Omron CP1W-TS002 temperature sensor expansion unit expands system capability by providing dedicated high-accuracy thermocouple measurement channels. This module interfaces directly with CP1H, CP1L, and CP1E CPU units, enabling precise thermal monitoring without requiring external signal transmitters. The unit supports up to four thermocouple inputs, which can be configured for either Type K or Type J sensors to meet specific application requirements. Featuring reliable galvanic isolation via photocouplers between input channels and internal PLC logic, the unit ensures stable operation and high noise immunity in demanding electrical environments.

Key Features

  • Four Dedicated Inputs: Supports up to four thermocouple channels on a single expansion slot.
  • Selectable Sensor Types: Field-switchable between Type K and Type J thermocouple inputs.
  • High-Speed Conversion: Complete sampling conversion cycle of 250 milliseconds for active channels.
  • Electrical Isolation: Integrated photocouplers shield the internal logic from field-side electrical surges and ground loops.
  • 16-Bit Resolution: Converts thermal data into precise 16-bit binary values (4-digit hexadecimal format).

Applications

  • Plastic extrusion and injection molding barrel temperature regulation.
  • Industrial heat treatment furnaces and packaging sealing-jaw control.
  • Environmental chambers and climate control system integration.
  • Food processing and baking oven thermal profile monitoring.

Technical Specifications

Parameter Specification Details
Manufacturer Omron
Model Number CP1W-TS002
Module Type Temperature Sensor Input Unit
Input Type Thermocouple (Type K or Type J, switchable)
Number of Inputs 4 channels
Allocated Input Words 4 words
Conversion Time 250 ms for 2 or 4 points
Data Format 16-bit binary data (4-digit hexadecimal)
Isolation Method Photocouplers between all temperature inputs and internal circuits
Current Consumption 5 VDC at 40 mA maximum; 24 VDC at 59 mA maximum
Country of Origin Japan
Shipping Weight (Calculated) 0.38 kg
Package Dimensions (Calculated) 110 mm x 90 mm x 80 mm

Empirical Engineering Insights

Alternative Models & Compatibility

The CP1W-TS002 replaces the lower-density CP1W-TS001 (which supports only two inputs) in systems requiring scale expansions. It fits seamlessly on the right side of any CP1H, CP1L, or CP1E CPU module. Note that CP-series expansion units are not compatible with older C200H or CJ-series backplanes.

Application Pitfalls & Engineering Notes

All four input channels must use the same thermocouple type (either all Type K or all Type J). Mixing sensor types on a single CP1W-TS002 module is not supported and will result in incorrect conversion values. Unused inputs should be configured or physically wired to avoid open-circuit fault flags in the PLC error log.

Commissioning & Wiring Tips

Sensor type selection is managed via DIP switches located beneath the module's protective terminal cover. These hardware configurations must be set while the PLC system is completely powered down. The CPU will not register DIP switch state modifications made during active run-time operations.

Installation Guidelines

CRITICAL WARNING: Ensure all primary and auxiliary power sources feeding the PLC rack are fully de-energized before mounting, removing, or wiring the CP1W-TS002. Working on live equipment risks severe hardware damage, sensor degradation, or unexpected control system behavior.
1

Configure the DIP switch located under the module cover to choose either Type K or Type J thermocouple matching your physical field sensors.

2

Align and secure the expansion bus connector of the CP1W-TS002 to the expansion port on the CPU unit or preceding expansion module.

3

Connect thermocouple lead wires or compensating cables to the designated screw terminals. Keep sensor wires separate from high-voltage AC cables to minimize electromagnetic interference.

4

Power up the PLC system and verify the allocation status using CX-Programmer software to ensure correct input word reading.

FAQ

Can I mix Type K and Type J thermocouples on the CP1W-TS002?

No, all four channels on the module must be configured to the same sensor type. Mixing Type K and Type J sensors on a single unit will cause measurement errors.

How do I switch between Type K and Type J thermocouple modes?

The input type is selected via hardware DIP switches located beneath the module's terminal cover. This must be set before powering on the PLC CPU.

What is the sampling and conversion rate of the CP1W-TS002?

The module features a fast conversion time of 250 milliseconds for every group of active inputs (2 or 4 points).

Does the CP1W-TS002 require external 24 VDC power?

Yes, it draws 59 mA maximum from the 24 VDC line and 40 mA maximum from the 5 VDC bus via the internal connection connector.

View all FAQs →

Quantity
Shipping & Returns

Global Express Shipping

  • Standard Delivery: 4–6 business days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our technical warranty.
Reviews
1 of 1
Only 6 item(s) left in stock
Quantity
View full details

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Country of origin
Japan

Technical knowledge

1746-OA8 vs 1746-OA16: Output Count and Current Limits

A direct comparison of 1746-OA8 and 1746-OA16 output count, common grouping, backplane current and temperature-derated load limits.

Replacing a 1761-NET-DNI: Capture These Settings First

A field checklist for recording the 1761-NET-DNI hardware series, firmware, EDS file, DF1 settings, DeviceNet address and messaging configuration before replacement.

EL3062 vs EL3062-0030: The Input Range Changes

The EL3062 is a 0–10 V EtherCAT terminal. The EL3062-0030 is a 0–30 V variant. This checklist covers identification, scaling and commissioning.

Replacing a 1769-OW8: Checks Before Moving Relay Loads

A field checklist for replacing Allen-Bradley 1769-OW8 relay output modules without losing load-group, wiring, and commissioning details.

PLC I/O Modules: Wiring, Load, and Isolation Checks

A field checklist for matching PLC digital and analog I/O to sensors, loads, commons, isolation groups, filters, and replacement settings.

Magnetic Flowmeters: Commissioning and Diagnostics

A field-focused checklist for selecting, installing, commissioning, and diagnosing magnetic flowmeters, with emphasis on conductivity, full-pipe conditions, grounding, wiring, zero checks, and PLC...