Description
The Siemens 6ES7134-4JB00-0AB0 is a high-precision analog input electronics module for the SIMATIC ET 200S distributed I/O system. This module is specifically designed for temperature measurement, providing two thermocouple input channels in a compact 15 mm width housing. It supports nine standard thermocouple types and converts their low-level voltage signals with a resolution of 15 bits plus sign over a ±80 mV range. With integrated signal conditioning and automatic linearization, the module delivers accurate, ready-to-use temperature data directly to the control system, making it suitable for demanding process control applications.
Features
- Two independent analog input channels for thermocouple sensors.
- Supports nine thermocouple types: B, E, J, K, L, N, R, S, and T.
- High measurement resolution of 15 bits plus sign.
- Fast signal acquisition with a cycle time of 65 ms per channel.
- Integrated automatic linearization for direct temperature value processing.
- Compact 15 mm module width for high-density I/O configurations.
- Onboard SF (Group Fault) LED for immediate diagnostic feedback.
- Seamless integration into SIMATIC DP systems via PROFIBUS networks.
Applications
- Process temperature monitoring in chemical and pharmaceutical manufacturing.
- Temperature control loops in food and beverage production.
- High and low-temperature monitoring in industrial furnaces and cryogenic systems.
- Machine and equipment thermal protection.
- Quality control systems requiring precise temperature data.
Technical Specifications
| Specification |
Value |
| Manufacturer |
Siemens |
| Model Number |
6ES7134-4JB00-0AB0 |
| Product Series |
SIMATIC ET 200S |
| Module Type |
Analog Input, Thermocouple |
| Number of Inputs |
2 |
| Input Range (Voltage) |
±80 mV |
| Supported Thermocouple Types |
B, E, J, K, L, N, R, S, T |
| Resolution |
15 bits + sign |
| Cycle Time per Channel |
65 ms |
| Module Width |
15 mm |
| Diagnostic Indicator |
SF (Group Fault) LED |
| Shipping Weight |
0.24 kg |
| Package Dimensions (Calculated) |
10.5 x 12.5 x 4 cm |
| Country of Origin |
Germany |
Installation Guidelines
CRITICAL WARNING: Electrical hazard. Disconnect all power sources and implement Lockout/Tagout (LOTO) procedures before installation or removal. Failure to de-energize the system can result in severe injury or death.
-
1
Ensure the ET 200S backplane or terminal module is correctly installed on the DIN rail and properly grounded according to system specifications.
-
2
Align the 6ES7134-4JB00-0AB0 electronics module with the corresponding terminal module, ensuring the coding elements match, and press firmly until it clicks securely into place.
-
3
Connect thermocouple sensor wiring to the designated terminals. Use the correct type of thermocouple extension wire that matches the sensor type to avoid measurement inaccuracies.
-
4
Use shielded, twisted-pair cable for all thermocouple signals. Terminate the cable shield to a clean, low-impedance ground point at the cabinet entry or terminal module to minimize electromagnetic interference.
-
5
After all modules are installed and wired, remove LOTO devices and restore power. Verify module status via the SF LED and confirm correct temperature readings in the PLC programming software.