Description
The Siemens 6ES7314-6CH04-0AB0 is a SIMATIC S7-300 CPU 314C-2 DP Compact CPU module, engineered for advanced automation tasks within industrial environments. This versatile CPU integrates essential control functionalities, including a built-in Multi-Point Interface (MPI) and a PROFIBUS DP (Decentralized Periphery) interface, facilitating flexible communication across various devices and networks. It features comprehensive integrated I/O capabilities, supporting 24 digital inputs, 16 digital outputs, 4 analog inputs, 2 analog outputs, and a dedicated Pt100 temperature sensor input. Four high-speed counters, capable of operating up to 60 kHz, enable precise processing of rapid signals. An integrated 24 V DC power supply and 192 KB of work memory ensure reliable performance for demanding production processes. The module requires a Micro Memory Card and two 40-pole front connectors for full operation and is compatible with firmware versions V3.3.1, V3.3.7, V3.3.8, V3.3.10, and V3.3.11.
Features
- Integrated CPU with MPI and PROFIBUS DP interface
- 24 Digital Inputs / 16 Digital Outputs
- 4 Analog Inputs / 2 Analog Outputs
- 1 Pt100 Temperature Sensor Input
- 4 High-Speed Counters (up to 60 kHz)
- Integrated 24 V DC Power Supply
- 192 KB Work Memory
- Supports multiple firmware versions (V3.3.1, V3.3.7, V3.3.8, V3.3.10, V3.3.11)
Applications
The Siemens 6ES7314-6CH04-0AB0 CPU module is suitable for a broad spectrum of industrial automation applications requiring compact and integrated control solutions. Typical deployments include:
- Small to medium-sized manufacturing and processing plants
- Machine control for packaging, assembly, and material handling systems
- Building automation and infrastructure control
- Distributed control systems with PROFIBUS DP communication
- Applications requiring precise high-speed counting and temperature monitoring
Technical Specifications
| Manufacturer |
Siemens |
| Brand |
Siemens |
| Series |
SIMATIC S7-300 |
| Model |
CPU 314C-2 DP Compact CPU |
| Part Number |
6ES7314-6CH04-0AB0 |
| Product Type |
CPU Module |
| Supply Voltage Range |
19.2-28.8 V DC |
| Integrated Power Supply |
24 V DC |
| Digital Inputs |
24 |
| Digital Outputs |
16 |
| Analog Inputs |
4 (plus 1 Pt100) |
| Analog Outputs |
2 |
| High-Speed Counters |
4 (up to 60 kHz) |
| Work Memory |
192 KB |
| Communication Interfaces |
MPI, PROFIBUS DP |
| Firmware Versions Supported |
V3.3.1, V3.3.7, V3.3.8, V3.3.10, V3.3.11 |
| Product Phase |
Phase-Out |
| Predecessor |
6ES7314-6CG03-0AB0 |
| Country of Origin |
Germany |
| Package Dimensions (Calculated) |
12.00 x 13.00 x 12.50 cm |
| Shipping Weight |
0.50 kg |
| Commodity Code |
85371091 |
| Export Control Regulations (ECCN) |
EAR99 |
Connections / Interfaces
The 6ES7314-6CH04-0AB0 CPU module is designed for robust industrial connectivity:
-
MPI Interface: For communication with programming devices, HMIs, and other SIMATIC S7 components.
-
PROFIBUS DP Interface: For connecting to decentralized I/O devices and other PROFIBUS-enabled systems.
-
Front Connectors: Requires two 40-pole front connectors for wiring integrated digital and analog I/O.
Installation Guidelines
Proper installation ensures optimal performance and longevity of the Siemens 6ES7314-6CH04-0AB0 CPU module:
-
De-energize System: Ensure all power to the control cabinet is disconnected before installation or removal of modules.
-
Mounting: Securely mount the CPU module onto a compatible SIMATIC S7-300 DIN rail.
-
Memory Card Insertion: Insert the required Micro Memory Card into the designated slot on the CPU.
-
Front Connector Installation: Attach the two 40-pole front connectors to the module's interface, ensuring proper alignment and secure latching.
-
Wiring: Connect the 24 V DC power supply to the module's integrated power supply terminals. Wire digital inputs/outputs, analog inputs/outputs, and the Pt100 sensor to the respective terminals on the front connectors, observing correct polarity and shielding guidelines.
-
Grounding: Ensure proper grounding of the module and the entire system to minimize electrical noise and ensure safety.
-
Cable Routing: Route signal and power cables separately to prevent interference.
-
Power Up: After all connections are verified, re-energize the system and observe status indicators for proper operation.