1 de 1

Beckhoff EPP1518-0002 EtherCAT P Box

Beckhoff EPP1518-0002 EtherCAT P Box

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: BECKHOFF

  • Nº do Produto: EPP1518-0002

  • País de origem:Alemanha

  • Tipo de Produto: EtherCAT P I/O Modules

  • Pagamento: T/T, Western Union

  • Peso: 500g

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

Facilitating direct sensor integration within decentralized control architectures, the BECKHOFF EPP1518-0002 industrial interface module provides eight digital inputs inside an IP67-rated enclosure. This EtherCAT P Box integrates communication and power (Us and Up) into a single, compact P-coded M8 connector system, minimizing on-site cabling complexity. Constructed with rugged encapsulation technology, the device is designed for direct machine mounting without an electrical cabinet, ensuring fast data transmission and high-precision time synchronization via integrated Distributed Clocks (DC).

Features

  • 8 Digital Inputs: Supports direct connection of 24 V DC sensors with flexible filter configuration options.
  • High-Speed Counting: Includes 2 inputs that can be configured as 32-bit up/down counters operating at frequencies up to 1 kHz.
  • Single-Cable Automation: Uses M8 P-coded EtherCAT P technology to combine system/sensor power, peripheral voltage, and EtherCAT telemetry.
  • Industrial-Grade Protection: Sealed housing rated at IP65, IP66, and IP67 for reliable operation in wet, dusty, and high-vibration environments.
  • TwinCAT Integration: Fully compatible with TwinCAT engineering systems for diagnostics, state-monitoring, and parameter configuration.

Applications

  • Decentralized Assembly Lines: Standardized on-machine mounting close to pneumatic valves and proximity sensors.
  • Material Handling & Conveyors: Reliable high-speed input capture for sorting and tracking sensors under high vibration.
  • Automotive Test Benches: Multi-sensor signal acquisition with microsecond-level synchronization using Distributed Clocks.

Technical Specifications Table

Parameter Specification Value
Manufacturer Beckhoff
Model Number EPP1518-0002
Product Protocol EtherCAT P
Number of Inputs 8 (2 configurable as 32-bit up/down counters)
Bus Interface Connection 2 x M8 socket, shielded, screw-type, P-coded
Input Port Type M12 x 1, 5-pin, A-coded
Nominal Input Voltage 24 V DC (-15% / +20%)
Logic "0" Signal Voltage -3 to +5 V DC (EN 61131-2, type 3)
Logic "1" Signal Voltage 11 to 30 V DC (EN 61131-2, type 3)
Input Current Rating Typ. 3 mA (EN 61131-2, type 3)
Input Filter Config Range Adjustable, 0 to 100 ms
Sensor Power Supply From Us control voltage, max. 0.5 A per 4 sensors (short-circuit proof)
Current Consumption (Us) Typ. 100 mA
Electrical Isolation 500 V RMS
Operating Temperature Range -25 to +60 degC
Storage Temperature Range -40 to +85 degC
Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Weight Approx. 165 g
Shipping Weight (Calculated) 0.45 kg

Connections and Interfaces

Connector Port Terminal Pin Signal Assignment
M8 P-coded (Power & EtherCAT) Pin 1 Us (System and Sensor Power +24 V DC)
Pin 2 Up (Actuator / Peripheral Power +24 V DC)
Pin 3 GNDs (System/Sensor Ground)
Pin 4 GNDp (Actuator/Peripheral Ground)
M12 A-coded (Digital Input Ports) Pin 1 Sensor Supply +24 V DC (Us)
Pin 2 Input Signal B (Channels 2, 4, 6, 8)
Pin 3 GNDs (Sensor Ground)
Pin 4 Input Signal A (Channels 1, 3, 5, 7)
Pin 5 Functional Earth (FE) / Shield

Empirical Engineering Insights

Alternative Models & Compatibility

The EPP1518-0002 belongs specifically to the EtherCAT P family. It is physically incompatible with standard EtherCAT EP-series boxes that use standard M8 Ethernet keying. If you are converting a system from standard EtherCAT to EtherCAT P, you must use an integration splitter such as the EP9224-0037 to transition power and standard network nodes safely onto the P-coded network infrastructure.

Application Pitfalls & Engineering Notes

When daisy-chaining multiple EPP modules, calculate cumulative current drop across both Us (system) and Up (peripheral) buses. While each local sensor supply channel is short-circuit proof up to 0.5 A, overloading the primary M8 feed lines will cause internal bus drops, triggering undervoltage fault states logged in the TwinCAT Master. Use the TwinCAT System Manager software to calculate voltage curves before site commissioning.

Commissioning & Wiring Tips

Ensure that all unused M12 and M8 connections are sealed using correct protective IP67 plastic caps. Leaving ports open in wet or humid processing environments compromises the sealing of the entire module block and can result in intermittent short-circuits between the sensor supply and ground pins.

Installation Guidelines

CRITICAL WARNING: Verify that all upstream and field power supplies are fully de-energized prior to connecting or disconnecting any M8 or M12 cables. Hot-plugging P-coded power lines can cause electrical arc damage to contact pins, degrading communication and risking module failure.
1

Mount the device directly to your machine frame or profiles using two M3 screws. Ensure the mounting surface is clean and level to avoid twisting stresses on the IP67 housing.

2

Connect the incoming EtherCAT P cable to the upper P-coded M8 socket, locking the coupling ring securely to maintain seal integrity.

3

Wire digital sensors to the M12 input sockets. Program appropriate digital input filter parameters within TwinCAT (0 to 100 ms) depending on sensor type to prevent mechanical contact bounce issues.

Loading product navigation…

Can I connect standard EtherCAT devices directly to the EPP1518-0002?

No. The module uses M8 P-coded EtherCAT P connectors, which combine power and Tx/Rx data. Standard EtherCAT uses different pinouts and keying. You must use an EtherCAT P junction or splitter module like the EP9224 to transition from standard EtherCAT to EtherCAT P.

What is the maximum limit for the integrated 32-bit up/down counters?

The two configurable counter inputs support a maximum counting frequency of 1 kHz. They can be read and evaluated directly within the TwinCAT environment as 32-bit values.

How does the module handle short circuits on the sensor supply?

The sensor supply is derived from the Us control voltage and is short-circuit proof. It allows a maximum current draw of 0.5 A per group of 4 sensors, preventing a local wiring fault from disabling the entire module.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação dentro da automação industrial. Ele mostra como...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crucial na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das tradicionais mandíbulas mecânicas. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...