Bently Nevada 330881-16-08-095-06-02 PROXPAC XL Proximity Transducer

Bently Nevada 330881-16-08-095-06-02 PROXPAC XL Proximity Transducer

Apenas 2 item(ns) restante(s) em estoque
  • Fabricante: Bently Nevada

  • Nº do Produto: 330881-16-08-095-06-02

  • País de origem:Estados Unidos

  • Tipo de Produto: PROXPAC XL Proximity Transducer

  • Código de barras: 8537101190

  • Pagamento: T/T, Western Union

  • Peso: 250g

  • Dimensões: 60 mm x 110 mm x 110 mm (H x W x D)

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver detalhes completos

Description

330881-16-08-095-06-02: PROXPAC XL Proximity Transducer, Metric configuration with a 3300 XL 8 mm probe without approvals, an 80 mm standoff adapter, a 95 mm probe penetration, a specialized 3/4-14 NPT fitting with SST reducer, and a 3/4-14 NPT outer sleeve mounting thread.

This integrated assembly brings the 3300 XL 8 mm probe and Proximitor sensor into a unified, self-contained unit, eliminating the need for an external extension cable and reducing overall field wiring complexity. Unlike variants that omit probe sensors or feature North American/European multi-approvals, this specific transducer includes a 3300 XL 8 mm probe (Option 16) with standard non-approved ratings, combined with a robust Polyphenylene Sulfide (PPS) thermoplastic housing for Type 4X and IP66 severe environment protection.

Features

  • Integrated 3300 XL 8 mm proximity probe (Option 16) with standard non-approved rating.
  • Pre-installed 80 mm metric standoff adapter (Option 08) for specialized mounting offsets.
  • Sleeve penetration length of 95 mm (Option 095) for deep machine casing access.
  • Premium fittings kit featuring one 3/4-14 NPT fitting, one 3/4-14 NPT to 1/2-14 NPT SST reducer, and two plugs (Option 06).
  • Outer sleeve mounting with 3/4-14 NPT threads (Option 02) to secure the standoff adapter assembly.
  • Advanced PPS thermoplastic housing incorporating glass and conductive fibers to dissipate electrostatic charges.

Applications

  • Radial vibration and axial position measurements on rotating machinery.
  • Fluid-film bearing monitoring in severe industrial environments.
  • Heavy-duty machinery protection where separate Proximitor sensor cabinets are impractical.

Ordering Information

Option / Segment Code on This SKU Meaning / Description
Orderable Part Number 330881-16-08-095-06-02 PROXPAC XL Proximity Transducer (Metric)
A - Probe and Approvals Option 16 3300 XL 8 mm probe without approvals
B - Standoff Adapter Option 08 80 mm standoff adapter (B dimension)
C - Probe Penetration Option 095 95 mm probe penetration (C dimension)
D - Fittings Option 06 One 3/4-14 NPT fitting, one 3/4-14 NPT to 1/2-14 NPT SST reducer, and two plugs
E - Mounting Thread Option 02 3/4-14 NPT (required for Standoff Adapter Option)

Technical Specifications

Manufacturer Bently Nevada (Baker Hughes)
Part Number 330881-16-08-095-06-02
Product Series PROXPAC XL
Sensor Input 3300 XL 8 mm Proximity Probe with a 1-meter cable length pre-installed in the probe sleeve
Power Requirements -17.5 Vdc to -26 Vdc at 12 mA maximum without barriers
Linear Range 2.0 mm (80 mils)
Scale Factor 7.87 V/mm (200 mV/mil) nominal
Frequency Response 0 to 10 kHz: +0, -3 dB with up to 305 meters (1000 feet) of field wiring
Housing Material Glass-reinforced and conductive fiber-reinforced Polyphenylene Sulfide (PPS) thermoplastic (UV resistant)
Sleeve & Retaining Chain Material AISI 304 Stainless Steel
Outer Sleeve and Retaining Screws AISI 303 Stainless Steel
O-Ring Material Neoprene (sleeve O-ring), Viton (internal probe seal)
Operating Temperature (Probe) -52 degC to +177 degC (-62 degF to +351 degF)
Operating Temperature (Housing/Sensor) -52 degC to +100 degC (-62 degF to +212 degF)
Storage Temperature -52 degC to +105 degC (-62 degF to +221 degF)
Environmental Rating Type 4X and IP66 (verified by BASEEFA)
Relative Humidity 100% condensing, non-submersible when connectors are protected
Torque Limits Retaining Nut: 29.5 N-m (260 in-lb); Probe Sleeve Locknut: 39.3 N-m (350 in-lb)

Installation Guidelines

  • Environmental Sealing: Ensure all field wiring conduit entries are properly sealed. While the PPS housing is rated for IP66 and Type 4X, moisture must be prevented from migrating through conduit paths.
  • Standoff Alignment: Secure the 3/4-14 NPT outer sleeve threads (Option 02) tightly to lock the 80 mm standoff adapter in place before fine-tuning probe position.
  • Probe Air Gap Adjustment: Adjust the probe sleeve gap with the machine shaft static. Standard linear range center is ideally located at a voltage reading corresponding to the target calibration.
  • Torque Limits: Never exceed 29.5 N-m (260 in-lb) on the housing retaining nut or 39.3 N-m (350 in-lb) on the probe sleeve locknut to prevent damage to the composite housing.

Compliance and Certifications

  • CE Mark: Complies with European Community Directives
  • EMC Directive: EN 61000-6-2 (Immunity) and EN 61000-6-4 (Emissions) for industrial environments
  • RoHS Directive: 2011/65/EU compliance
  • Mechanical Protection: IP66 housing rating verified by BASEEFA

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Bently Nevada 330881-16-08-095-06-02 PROXPAC XL Proximity Transducer

What does option 16 represent for this PROXPAC XL assembly?

Option 16 indicates that this unit is configured with an integrated 3300 XL 8 mm proximity probe and standard, non-approved sensor options.

What is the purpose of the 80 mm standoff adapter and 95 mm penetration?

The 80 mm standoff (Option 08) offsets the probe housing from the machine case, while the 95 mm penetration (Option 095) allows the probe sleeve to properly access the target shaft.

What fitting option is provided with this specific transducer configuration?

This configuration comes with Option 06, which includes one 3/4-14 NPT fitting, one 3/4-14 NPT to 1/2-14 NPT stainless steel reducer, and two blanking plugs.

Can this transducer be used in severe outdoor environments?

Yes. The housing is molded from glass-reinforced polyphenylene sulfide (PPS) and is rated for Type 4X and IP66 environments, providing excellent resistance to severe conditions and electrostatic charges.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendemos mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Aceitamos devoluções de produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reposição e detalhes de devolução internacional, por favor, consulte nosso site oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Estados Unidos

Produtos Visualizados Recentemente

Conhecimento técnico

Atuadores Elétricos Projetados para Substituir Sistemas Hidráulicos: Um Guia Prático de Automação Industrial

Este artigo explica como os atuadores elétricos integrados, como a série e-Actuator da SMC, estão transformando o controle de movimento industrial ao substituir os sistemas pneumáticos e hidráulicos...

Operações Matemáticas Usando OpenPLC para Aplicações de Automação Industrial

Este artigo explica como os sistemas PLC realizam operações matemáticas básicas, como adição, subtração, multiplicação, divisão, módulo e exponenciação, dentro da automação industrial. Ele mostra...

Lógica Booleana Avançada com Programação FBD em CLP: Aplicações Industriais Práticas Além da Lógica Básica

O artigo explica várias funções avançadas de lógica Booleana usadas na programação de CLPs além das operações básicas AND, OR e NOT. Ele aborda como ferramentas como tabelas verdade, multiplexadores,...

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas em FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem às...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel fundamental na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Do Manuseio Delicado à Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...