1 de 1

Honeywell 05701-A-0325 System 57 DC Input Card

Honeywell 05701-A-0325 System 57 DC Input Card

Only 7 item(s) left in stock
  • Manufacturer: Honeywell

  • Product No.: 05701-A-0325

  • Country of origin:Estados Unidos

  • Product Type: Power Distribution Modules

  • Payment: T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

Quantidade
Ver informações completas

Description

The 05701-A-0325 functions as a dedicated power distribution interface module developed for the System 57 sub-rack architecture. This device provides the primary electrical entry point for external nominal 24V dc power entering the control system rack, routing the supply directly through the Engineering Card and the sub-rack backplane to deliver stable power to all fitted monitoring or control cards.

The card incorporates an onboard fuse protection mechanism alongside low-pass RFI filtering and high-integrity reverse polarity protection circuits to shield the internal backplane logic from upstream power electrical anomalies. It features dual-diode isolation paths that facilitate the concurrent connection of a primary power supply unit (PSU) and an auxiliary standby backup battery system, guaranteeing uninterrupted safety operation during primary utility outages. The interface utilizes a detachable two-part terminal block (TB1) to allow prompt mechanical hot-swapping or card replacement without necessitating discrete field wire disconnections.

Features

  • Built with a pluggable, two-part terminal block (TB1) to facilitate quick hardware removal and maintenance actions without disturbing active field wiring connections.
  • Incorporates dual-path diode isolation separating the main power supply unit (PSU) input and the auxiliary standby battery (AUX) input terminal lines.
  • Equipped with integrated high-efficiency RFI filtering components to attenuate high-frequency radio frequency interference along incoming power cables.
  • Integrates a dedicated, hardware-level reverse polarity protection circuit to safeguard backplane-connected electronics from incorrect installation wiring.
  • Features integrated overcurrent fuse protection directly situated on the main DC distribution trace to intercept power surges before backplane transmission.

Applications

  • Main sub-rack DC power filtering and safety distribution for Honeywell System 57 combustible and toxic gas detection racks.
  • Dual-source redundant power termination interface configurations utilizing standby industrial battery banks in high-integrity control rooms.
  • Large-scale industrial gas marshaling systems requiring segmented power infrastructure to prevent backplane overcurrent propagation.

Technical Specifications

Parameter Specifications
Manufacturer Honeywell
Model Number 05701-A-0325
Product Type DC Input Card
Product Series System 57 / 5701 Series Control System
Nominal Input Voltage 24V dc
Interface Connector Two-part terminal block TB1
Protection Type Fuse, Reverse Polarity, and RFI Filtering
Isolation Mechanism Diode isolated PSU and AUX paths
Shipping Weight 2 Kg

Connections/Interfaces

Connector Pin Function
TB1 - PSU (+) Primary External 24V DC Power Supply Positive Input
TB1 - PSU (-) Primary External 24V DC Power Supply Negative Common
TB1 - AUX (+) Standby Backup Battery Supply Positive Input
TB1 - AUX (-) Standby Backup Battery Supply Negative Common
TB1 - GND Instrumentation Clean Earth Shield Connection

Installation Guidelines

  • Sub-Rack Power Balancing: In system installations embedding more than eight 5704 Catalytic Control Cards, power the control cards through their associated Quad Relay Interface Cards instead, utilizing this input card exclusively to feed the main Engineering Card.
  • Terminal Wiring Safety: Ensure all stranded power supply conductors are terminated into the removable block TB1 using appropriate crimped wire ferrules to eliminate loose thread tracking or arc faults.
  • Redundant Path Wiring: Connect independent, isolated power paths when deploying both PSU and AUX configurations, ensuring that backup batteries conform to nominal 24V dc operating metrics.
  • Polarity Verification: double-check input lead configurations prior to energizing primary lines; although reverse polarity protection is built into the card, sustained incorrect polarity can cause localized fuse failure.

FAQ

  • What is the exact purpose of the two-part terminal block on this card?

    The two-part terminal block TB1 allows the upper wiring assembly to be disconnected from the card as a single physical piece, allowing technicians to slide out the card for maintenance or replacement without labeling and unscrewing individual power conductors.

  • Can this input card handle the power distribution for an entirely filled rack of catalytic cards?

    If a sub-rack contains more than eight 5704 Catalytic Cards, distributing full sensor drive power over the shared backplane can lead to high current loads. In this scenario, it is standard practice to power the control cards locally via Quad Relay Interfaces and use this card to run the Engineering Card.

  • How does the module manage a simultaneous drop in primary power when a battery is connected?

    The onboard PSU and AUX distribution paths are structurally isolated from each other using power blocking diodes. If the primary power supply source drops below the potential of the backup battery, the diode path shifts conduction seamlessly without causing line drops or voltage dips on the backplane logic.

  • Does this module provide isolated outputs for different control cards?

    No, this card acts as a centralized parallel bus distribution point, filtering and routing the unified 24V DC rail across the common backplane infrastructure to all slot locations.

Product Documentation

Technical Datasheet (PDF) Complete specifications and technical drawings.

Technical Datasheet

Honeywell 05701-A-0325 System 57 DC Input Card

正在加载 PDF,请稍候…

Global Express Shipping

  • Standard Delivery: 4-6 Business Days via DHL, FedEx, and UPS.
  • Express Dispatch: Same-day dispatch for in-stock orders placed before 2:00 PM (GMT+8).
  • Worldwide Coverage: Serving over 150 countries, including rapid delivery to Saudi Arabia and UAE.

Returns & Warranty

  • 30-Day Guarantee: Returns accepted for in-stock products in original, factory-sealed packaging.
  • 12-Month Warranty: Every industrial component is backed by our professional technical warranty.

Orders are processed and delivered Monday-Friday (excluding public holidays).


For full eligibility, restocking fees, and international return details, please view our official Refund & Return Policy .

TECHNICAL SPECIFICATIONS

Color pattern
Verde
Country of origin
Estados Unidos

Recently Viewed Products

Technical knowledge

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...

Programando Ciclos de Movimento de Eixo Único em um Servo Drive CMZ

Este tutorial examina como a funcionalidade PLC integrada dentro de um servo drive CMZ SBD pode executar programas de movimento autônomos, incluindo lógica de referência, controle de posição e...

Configuração de Controle de Movimento de Eixo Único com Drives Servo CMZ

Este tutorial explora a comissionamento de um sistema de movimento servo de eixo único usando um drive CMZ SBD, abrangendo a configuração de hardware, escala do eixo, configuração de homing e...