1 de 1

Weidmuller 8965360000 ACT20X-HDI-SDO-S Isolating Switch Amplifier

Weidmuller 8965360000 ACT20X-HDI-SDO-S Isolating Switch Amplifier

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: Weidmuller

  • Nº do Produto: 8965360000

  • País de origem:Alemanha

  • Tipo de Produto: Isolating Switch Amplifiers

  • Pagamento: T/T, Western Union

  • Peso: 1200g

  • Dimensões: 117.2 mm x 22.5 mm x 113.6 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver informações completas

Processing digital signals from hazardous areas requires robust galvanic isolation, which the Weidmuller 8965360000 ACT20X-HDI-SDO-S delivers as a high-performance, 2-channel isolating switch amplifier. This device safely transmits switching states from NAMUR sensors or mechanical contacts located in Zone 0, 1, or 2 hazardous areas to the safe area control system, providing complete electrical separation and signal conditioning in a compact form factor.

Key Features

  • Dual-channel intrinsically safe input for NAMUR sensors or dry mechanical contacts.
  • Galvanic 4-way isolation between input, output, power supply, and status output.
  • Integrated line fault detection (LFD) for continuous wire-break and short-circuit monitoring.
  • FDT/DTM software-configurable parameters for custom application tuning and diagnostics.
  • Relay outputs (1 changeover contact per channel) for robust load switching.
  • Compact 22.5 mm DIN-rail housing to optimize cabinet space.

Applications

  • Intrinsically safe signal isolation in chemical and petrochemical processing plants.
  • Oil and gas pipeline monitoring systems requiring Zone 0/1 sensor deployment.
  • Water and wastewater treatment facility telemetry and pump control.
  • Hazardous area valve position feedback and limit switch integration.

Technical Specifications

Parameter Value
Manufacturer Weidmuller
Article Number 8965360000
Model ACT20X-HDI-SDO-S
Number of Channels 2
Input Type NAMUR sensor (DIN EN 60947-5-6) or mechanical switch
Output Type Relay (1 changeover contact per channel)
Nominal Switching Voltage 250 V AC / 30 V DC
Supply Voltage 19.2 to 31.2 V DC
Power Consumption <= 1.1 W
Isolation Voltage 2.6 kV AC (input / output / power)
Connection Technology Screw connection
Clamping Range 0.5 to 2.5 mm2
Flammability Rating UL 94 V-0
Protection Degree IP20
Operating Temperature -20 to +60 degC
Dimensions (H x W x D) 117.2 mm x 22.5 mm x 113.6 mm
Net Weight 0.170 kg

Connections and Interfaces

Terminal Pin Function / Circuit Assignment
11 / 12 Channel 1 Input (NAMUR Sensor / Mechanical Switch)
21 / 22 Channel 2 Input (NAMUR Sensor / Mechanical Switch)
51 / 52 / 53 Channel 1 Relay Output (NC / COM / NO)
61 / 62 / 63 Channel 2 Relay Output (NC / COM / NO)
91 / 92 Power Supply (19.2 to 31.2 V DC: + / -)

Alternative Models & Compatibility

The ACT20X-HDI-SDO-S is part of Weidmuller's premium ACT20X signal converter family. It serves as a direct replacement or upgrade path for legacy ACT20 series modules. When migrating from older systems, verify that your configuration files are updated in the FDT/DTM frame to match the specific firmware revision of the 8965360000 module.

Application Pitfalls & Engineering Notes

When utilizing standard mechanical switches instead of NAMUR sensors, the Line Fault Detection (LFD) circuit must be configured correctly. If LFD is enabled without external resistors, the module will interpret an open switch as a wire break and a closed switch as a short circuit. To prevent false diagnostics, either disable LFD via the DTM software or wire a resistor network (typically 1k Ohm in series and 10k Ohm in parallel) directly at the switch contacts.

Commissioning & Wiring Tips

Configuration is performed using the Weidmuller WI-Manager software via the front-panel service jack. Ensure the CBX200 USB interface cable is used for connection. For field wiring, maintain a minimum physical separation of 50 mm between the intrinsically safe (Ex i) blue terminals on the left side and the non-intrinsically safe terminals on the right side to comply with international hazardous area installation standards.

Installation Guidelines

CRITICAL WARNING

De-energize all power sources before mounting, wiring, or configuring the device. Failure to isolate power can result in electrical shock or spark generation in hazardous areas, compromising explosion protection safety.

1
Snap the module vertically onto a standard TS 35 DIN rail, ensuring the metal grounding spring on the back makes secure contact with the rail.
2
Connect the intrinsically safe field sensors to the blue terminals (11/12 and 21/22), ensuring proper cable routing away from power lines.
3
Wire the relay outputs and the 24 V DC power supply to the black terminals on the opposite side of the module.
4
Connect the configuration interface to set the desired input/output logic and LFD parameters using the FDT/DTM software before commissioning.
Loading product navigation…

How do I configure the Line Fault Detection (LFD) for a standard mechanical switch?

To use LFD with a mechanical switch, you must wire an external resistor network at the switch contacts: a 1k Ohm resistor in series and a 10k Ohm resistor in parallel. Alternatively, you can disable LFD entirely using the Weidmuller FDT/DTM software.

What software is required to configure the ACT20X-HDI-SDO-S?

Configuration requires the Weidmuller WI-Manager software (FDT frame) along with the device-specific ACT20X DTM package and a CBX200 USB interface cable.

Can this isolating amplifier be installed directly in Zone 0?

No, the module itself must be installed in a safe area or Zone 2 (inside a suitable protective enclosure). However, its input circuits are certified intrinsically safe for direct connection to devices located in Zone 0, 1, or 2.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reabastecimento e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...

Programando Ciclos de Movimento de Eixo Único em um Servo Drive CMZ

Este tutorial examina como a funcionalidade PLC integrada dentro de um servo drive CMZ SBD pode executar programas de movimento autônomos, incluindo lógica de referência, controle de posição e...