1 de 1

Weidmuller 8965380000 ACT20X ACT20X-2HDI-2SDO-RNC-S Isolating Switch Amplifier

Weidmuller 8965380000 ACT20X ACT20X-2HDI-2SDO-RNC-S Isolating Switch Amplifier

Apenas 10 item(ns) restante(s) em estoque
  • Fabricante: Weidmuller

  • Nº do Produto: 8965380000

  • País de origem:Alemanha

  • Tipo de Produto: Isolating Switch Amplifiers

  • Pagamento: T/T, Western Union

  • Peso: 192g

  • Dimensões: 119.2 mm x 22.5 mm x 113.6 mm

  • Porto de embarque: Xiamen

  • Garantia: 12 meses

Quantidade
Ver informações completas

Weidmuller 8965380000 ACT20X ACT20X-2HDI-2SDO-RNC-S Isolating Switch Amplifier

Description

Designed for intrinsic safety applications, the **Weidmuller 8965380000** functions as a highly reliable 2-channel **isolating switch amplifier**. This device transmits digital signals from hazardous areas (Zone 0, 1, 2) to safe areas, providing complete galvanic isolation between the input, output, and power supply. It is specifically engineered to interface with NAMUR sensors and mechanical contacts, converting their states into digital relay outputs.

The **ACT20X-2HDI-2SDO-RNC-S** features integrated line fault detection (LFD) capable of identifying line interruptions or short circuits at the input. Diagnostic status and device errors are signaled via an integrated alarm contact, ensuring high system availability and simplified troubleshooting. Configuration is easily performed using standard FDT/DTM software, allowing for precise adjustment of input types, output behavior, and diagnostic parameters.

Features

  • Dual-channel design for space-saving installation on standard DIN rails.
  • Complete 3-way galvanic isolation between input, output, and power supply.
  • Supports both NAMUR sensors and mechanical contact inputs.
  • Integrated line fault detection (LFD) for short-circuit and wire-break monitoring.
  • Dedicated alarm relay output for system diagnostics and error reporting.
  • Simple configuration and parameterization via FDT/DTM software.
  • Secure screw connection terminals for reliable field wiring.

Applications

  • Chemical and petrochemical processing plants.
  • Oil and gas extraction, refining, and distribution.
  • Water and wastewater treatment facilities.
  • Hazardous area signal isolation and safety-instrumented systems.

Technical Specifications

Manufacturer Weidmuller
Part Number / Model 8965380000 / ACT20X-2HDI-2SDO-RNC-S
Product Type Isolating Switch Amplifier
Number of Channels 2
Supply Voltage 19.2 to 31.2 V DC
Power Consumption <= 1.9 W
Input Type NAMUR sensor (DIN EN 60947-5-6), switch contact
NAMUR Supply 8 V DC / 8 mA
Output Type Relay (2 NO contacts)
Nominal Switching Voltage <= 125 V AC / 110 V DC
Continuous Current <= 0.5 A AC / 0.3 A DC
Alarm Function Line interruption at input, short circuit at input, no supply voltage, device error
Configuration FDT/DTM software
Connection Type Screw connection
Protection Degree IP20
Ambient Humidity 0 to 95% (non-condensing)
Operating Temperature -20 to +60 Celsius
Dimensions (H x W x D) 119.2 mm x 22.5 mm x 113.6 mm
Weight 0.192 kg

Connections and Interfaces

Terminal Pin Function
11, 12 Input Channel 1 (Hazardous Area)
13, 14 Input Channel 2 (Hazardous Area)
51, 52 Output Channel 1 Relay (Safe Area)
53, 54 Output Channel 2 Relay (Safe Area)
41, 42 Power Supply (19.2 to 31.2 V DC)
43, 44 Alarm Output Relay

Installation Guidelines

  • Mounting: Install vertically on a standard TS 35 DIN rail. Ensure the module is securely locked into place.
  • Wiring Separation: Maintain strict physical separation (at least 50 mm) between intrinsically safe (blue terminals) and non-intrinsically safe wiring to comply with safety standards.
  • Grounding: Ensure the DIN rail is connected to a low-impedance functional earth ground.
  • Ventilation: Provide sufficient clearance above and below the device to allow natural convection cooling and prevent heat accumulation.

Compliance and Certifications

  • CE
  • ATEX
  • IECEx
  • cULus
Loading product navigation…

What is the primary function of the Weidmuller 8965380000?

It is a 2-channel isolating switch amplifier designed to transmit digital signals (such as NAMUR sensors or mechanical contacts) from hazardous areas to safe areas with complete galvanic isolation.

How is the ACT20X-2HDI-2SDO-RNC-S configured?

The module is configured using standard FDT/DTM software, allowing users to customize input types, output behaviors, and line fault detection settings.

What alarm functions are supported by this device?

The device features diagnostics for line interruption at the input, short circuits at the input, loss of supply voltage, and internal device errors.

What is the protection rating and mounting style of this module?

The module has an IP20 protection rating and is designed for standard TS 35 DIN rail mounting.

Envio Expresso Global

  • Entrega Padrão: 4-6 dias úteis via DHL, FedEx e UPS.
  • Despacho Expresso: Envio no mesmo dia para pedidos em estoque realizados antes das 14:00 (GMT+8).
  • Cobertura Mundial: Atendendo mais de 150 países, incluindo entrega rápida para Arábia Saudita e Emirados Árabes Unidos.

Devoluções e Garantia

  • Garantia de 30 Dias: Devoluções aceitas para produtos em estoque na embalagem original, lacrada de fábrica.
  • Garantia de 12 Meses: Cada componente industrial é coberto pela nossa garantia técnica profissional.

Os pedidos são processados e entregues de segunda a sexta-feira (exceto feriados).


Para elegibilidade completa, taxas de reabastecimento e detalhes de devolução internacional, por favor, consulte nosso oficial Política de Reembolso e Devolução .

TECHNICAL SPECIFICATIONS

Country of origin
Alemanha

Produtos Visualizados Recentemente

Conhecimento técnico

Lógica Booleana na Programação de CLP: Entendendo Portas Lógicas FBD

A lógica booleana é a base de todo programa PLC. Desde controles simples de máquinas até sistemas complexos de automação industrial, as portas lógicas determinam como os controladores respondem a...

Guia Completo sobre Firewalls Industriais e Segmentação de Redes OT

Firewalls industriais desempenham um papel crítico na cibersegurança OT, protegendo redes PLC, DCS e SCADA por meio de segmentação, controle de entrada/saída e integração IDS/IPS alinhada aos...

Guia de Garras Robóticas: Desde o Manuseio Delicado até a Automação Pesada

As garras robóticas modernas estão evoluindo além das mandíbulas mecânicas tradicionais. De sistemas adesivos inspirados em lagartos-gecko e garras macias de grau alimentício a ferramentas de armazém...

Retrospectiva: Como os Primeiros Motores Elétricos Mudaram a Mineração Subterrânea

De compressores CC acionados por corda a carrinhos de mina movidos a bateria, as operações de mineração iniciais marcaram um ponto de virada na eletrificação industrial. Este artigo explora como os...

Factory I/O: Uma Ferramenta Moderna de Simulação de CLP para Treinamento em Automação Industrial

Factory I/O está transformando a educação em CLP ao oferecer simulações industriais 3D imersivas para estudantes, engenheiros e equipes de manutenção. A plataforma reduz a distância entre a teoria e...

Programando Ciclos de Movimento de Eixo Único em um Servo Drive CMZ

Este tutorial examina como a funcionalidade PLC integrada dentro de um servo drive CMZ SBD pode executar programas de movimento autônomos, incluindo lógica de referência, controle de posição e...