Beckhoff EP2028-0032 EtherCAT Box 8-channel Digital Output Module

Beckhoff EP2028-0032 EtherCAT Box 8-channel Digital Output Module

Остался в наличии только 10 товар(ы)
  • Производитель: BECKHOFF

  • Номер продукта: EP2028-0032

  • Страна происхождения:Германия

  • Тип продукта: EtherCAT Box Modules

  • Оплата: Т/Т, Western Union

  • Вес: 500г

  • Порт отправления: Сямынь

  • Гарантия: 12 месяцев

Количество
Просмотреть полные детали

Description

Designed for decentralized automation without control cabinet enclosures, the Beckhoff EP2028-0032 EtherCAT Box provides high-capacity control over eight digital actuator channels directly within harsh operating environments. This rugged IP67-rated device processes binary control signals from the automation controller to actuate heavy industrial loads such as solenoid valves, DC contactors, and signaling lamps. Equipped with high-power M12 output interfaces and a robust 7/8-inch power system, this module is engineered to handle up to 2.8 A per channel with a combined sum current of 16 A, making it an excellent choice for demanding field installations where high electrical load density and extreme reliability are required.

Features

  • Rugged Enclosure: Fully encapsulated IP65/66/67 construction enables direct machine mounting without protective enclosures.
  • High Output Current: Individual channels support loads up to 2.8 A, optimized for heavy-duty ohmic, inductive, and lamp loads.
  • Comprehensive Diagnostics: Individually short-circuit proof outputs with quick-response current limiting (typical 15 A short-circuit current).
  • Industrial Power Distribution: Features a high-capacity 5-pin 7/8-inch power configuration for feed and downstream loop-through connections.
  • Standardized Fieldbus Connection: Shielded screw-type M8 interfaces ensure reliable, high-speed EtherCAT communication.

Applications

  • Direct control of high-current hydraulic and pneumatic valve manifolds.
  • Decentralized tooling and actuator control on robotic end-effectors.
  • Automobile assembly lines and press shops with high electromagnetic and vibration levels.
  • Conveyor systems, sorting machinery, and automated material handling equipment.

Technical Specifications Table

Parameter Specification Value
Manufacturer Beckhoff Automation
Model Number EP2028-0032
Protocol EtherCAT
Number of Outputs 8 digital outputs (1 output per M12 connector)
Nominal Output Voltage 24 V DC (-15% / +20%)
Max. Output Current 2.8 A per channel (Sum current limit: 16 A)
Load Compatibility Ohmic, inductive, lamp load
Bus Interface Connection 2 x M8 socket, shielded, screw-type
Output Connections M12 x 1, 5-pin, A-coded
Power Feed / Downstream Connectors 1 x 7/8" plug (5-pin) / 1 x 7/8" socket (5-pin)
Current Consumption (from US) Typically 130 mA
Auxiliary Power Current (UP) Typically 20 mA + connected load
Electrical Isolation 500 V
Switching Response Times Typical TON: 200 us, TOFF: 200 us
Operating Temperature Range -25 to +60 degC
Storage Temperature Range -40 to +85 degC
Vibration/Shock Resistance Conforms to EN 60068-2-6 / EN 60068-2-27
EMC Immunity/Emission Conforms to EN 61000-6-2 / EN 61000-6-4
Protection Rating IP65/66/67 (conforms to EN 60529)
Shipping Weight (Calculated) 2.0 kg

Connections and Interfaces

Interface Type Pin / Terminal Assignment Circuit Description
M8 EtherCAT Ports (IN/OUT) 4-pin, shielded, screw connection Transmit/Receive pairs for high-speed network integration.
M12 Output Ports (1-8) 5-pin, A-coded (1 active output per connector) Switched 24 V DC output signal to actuator, earth ground, and common return.
7/8" Power Input Feed 5-pin male connection Primary feed for control electronics (US) and auxiliary load supply voltage (UP).
7/8" Power Downstream Link 5-pin female connection Daisy-chain output to downstream modules (maximum 16 A total current loop).

Empirical Engineering Insights

Alternative Models & Compatibility

The EP2028-0032 variant is functionally distinct from standard low-current EtherCAT boxes (such as the EP2028-0002). While the -0002 variant utilizes M8 power cabling and supports up to 0.5 A per channel, the -0032 utilizes a heavy-duty 7/8-inch power system to deliver up to 2.8 A per channel. These two variants are not directly drop-in compatible in terms of physical wiring systems. Upgrading to the -0032 requires transitioning to 7/8-inch power cables to support the higher current capacities.

Application Pitfalls & Engineering Notes

When switching inductive loads close to the 2.8 A channel maximum, the accumulated heat within the encapsulated housing must be closely monitored. In high-density installations, avoid placing adjacent high-duty cycle modules within dead air spaces. Although the continuous sum current rating is robustly set at 16 A, continuous duty near this threshold in elevated ambient temperatures can trigger localized thermal monitoring faults.

Commissioning & Wiring Tips

Ensure that all M12 and M8 connector interfaces are torqued exactly to OEM torque requirements (0.6 Nm for M12, 0.4 Nm for M8) using a calibrated torque wrench. Undertightening compromises the IP67 sealing, permitting ingress of moisture or coolant, whereas overtightening will fracture the internal plastic threads. To avoid communication drops, always use dual-shielded industrial Ethernet cables for the M8 EtherCAT connections to isolate high-frequency noise from adjacent high-power switching conductors.

Installation Guidelines

CRITICAL WARNING: De-energize all primary (US) and auxiliary (UP) power supplies before performing installation, wiring, or maintenance on this EtherCAT Box. Failure to completely isolate the power supply can result in terminal damage, severe electrical shock, or permanent destruction of connected downstream modules.
  1. 1 Mount the module on a flat, vibration-resistant surface using two M4 bolts inserted through the designated mounting holes.
  2. 2 Connect the shielded M8 EtherCAT network cables to the IN and OUT ports, ensuring correct key alignment.
  3. 3 Secure the A-coded M12 cables to the output ports, ensuring that unused ports are sealed with IP67 protective caps.
  4. 4 Attach the 5-pin 7/8-inch power feed, tighten the coupling ring, and verify the ground connection back to the central machine busbar.
Loading product navigation…

What is the maximum output current rating for the EP2028-0032?

Each of the 8 digital output channels supports up to 2.8 A individually. The continuous sum current rating across all channels combined is 16 A, utilizing the robust 7/8-inch power feed.

Can this EtherCAT Box be used with standard M8 power connectors?

No, this specific high-current variant uses a 5-pin 7/8-inch plug for the power feed and a 5-pin 7/8-inch socket for downstream power distribution, differing from standard M8 modules.

How does the module handle short circuits?

Each of the 8 channels is individually short-circuit proof. If a short circuit occurs, it is limited to a typical current of 15 A and can be diagnosed via the TwinCAT control software.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашей официальной Политика возврата и возмещения .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Недавно просмотренные товары

Технические знания

Электрические приводы, разработанные для замены гидравлических систем: практическое руководство по промышленной автоматизации

В этой статье объясняется, как интегрированные электрические приводы, такие как серия e-Actuator от SMC, преобразуют промышленное управление движением, заменяя традиционные пневматические и...

Математические операции с использованием OpenPLC для промышленных автоматизированных систем

В этой статье объясняется, как системы ПЛК выполняют основные математические операции, такие как сложение, вычитание, умножение, деление, взятие остатка и возведение в степень в рамках промышленной...

Продвинутая булева логика в программировании ПЛК с использованием FBD: практические промышленные применения за пределами базовой логики

В статье объясняются несколько продвинутых функций булевой логики, используемых в программировании ПЛК, помимо базовых операций AND, OR и NOT. Рассматривается, как такие инструменты, как таблицы...

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий, защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От систем с клеящими поверхностями, вдохновлёнными гекконами, и мягких захватов пищевого класса до...