1 из 1

Beckhoff IP1002-B810 Fieldbus Box 8-channel Digital Input Module

Beckhoff IP1002-B810 Fieldbus Box 8-channel Digital Input Module

Остался в наличии только 10 товар(ы)
  • Производитель: BECKHOFF

  • Номер продукта: IP1002-B810

  • Страна происхождения:Германия

  • Тип продукта: Fieldbus Box Modules

  • Оплата: Т/Т, Western Union

  • Вес: 2000г

  • Размеры: 30 mm x 175 mm x 26.5 mm

  • Порт отправления: Сямынь

  • Гарантия: 12 месяцев

Количество
Просмотреть полные детали

Description

Decentralized signal acquisition on machine frames and production lines is executed reliably by the Beckhoff IP1002-B810 Fieldbus Box. This device gathers binary control signals from up to eight digital sensors and transmits them over a point-to-point RS232 interface to the master controller. Housed in a robust, fully-sealed polyamide shell, the IP1002-B810 does not require a protective sub-cabinet, enabling direct machine-mount installation in heavy industrial settings. Key features include an integrated 3.0 ms input filter to prevent contact bounce and standard M12 screw-type connection points for rugged sensor field-wiring.

Features

  • 8 Digital Inputs: Supports direct connection of standard 24 V DC binary sensors.
  • RS232 Serial Interface: Peer-to-peer communication protocol with selectable data transfer rates up to 38.4 kbaud.
  • Rugged Sealed Housing: Highly durable PA6 polyamide design conforms to IP65, IP66, and IP67 protection classes.
  • Input Filtering: Integrated 3.0 ms hardware filter to suppress signal noise and contact chatter.
  • Flexible Mounting: Two pre-drilled 3.5 mm structural fixing holes for direct M3 screw attachment to machinery.

Applications

  • Distributed packaging machine automation systems.
  • Conveyor and material handling control networks.
  • Wet process areas requiring high ingress protection ratings.
  • Dedicated serial peer-to-peer data logging configurations.

Technical Specifications Table

Parameter Specification
Manufacturer Beckhoff Automation
Model Reference IP1002-B810
Product Type Fieldbus Box Digital Input Module
Number of Inputs 8 digital inputs
Interface Protocol RS232 (open, documented protocol)
Data Transfer Rates 9.6 kbaud, 19.2 kbaud, 38.4 kbaud (default)
Nominal Input Voltage 24 V DC (-15% / +20%)
"0" Signal Voltage -3 to +5 V (EN 61131-2, type 2)
"1" Signal Voltage 11 to 30 V (EN 61131-2, type 2)
Input Filter Time 3.0 ms
Box Current Consumption 45 mA + sensor current (max 0.5 A total)
Power Supply Connections Feed: 1 x M8 male, 4-pin; Downstream: 1 x M8 female, 4-pin
Bus Interface Connection 1 x M12 socket, 5-pin, B-coded
Sensor Connections M12, screw-type connection
Housing Material PA6 (Polyamide)
Ingress Protection Rating IP65, IP66, IP67 (conforms to EN 60529)
Operating Temperature Range 0 to +55 degC
Storage Temperature Range -25 to +85 degC
Approvals CE, UL
Dimensions (W x H x D) 30 mm x 175 mm x 26.5 mm
Net Weight Approx. 210 g
Shipping Weight (Calculated) 2.0 kg

Connections and Interfaces

Connector/Terminal Function / Pin Assignment
M8 Power Feed (Male) Pin 1: +24 V DC Control Voltage (US), Pin 2: +24 V DC Load Voltage (UP), Pin 3: GND (US), Pin 4: GND (UP)
M8 Downstream (Female) Daisy-chain connection to downstream modules (US, UP, GND US, GND UP)
M12 Bus Interface (B-coded) RS232 Serial communication lines (RXD, TXD, GND interface connections)

Empirical Engineering Insights

Alternative Models & Compatibility

The IP1002-B810 model relies on a standard RS232 peer-to-peer connection, which is distinct from the fieldbus-specific IP1002 network modules (such as CANopen or PROFIBUS variants). When configuring the serial link, ensure the controller's serial port parameters match the module's default baud rate of 38.4 kbaud. Standard configuration tasks can be managed directly using Beckhoff's KS2000 software interface via the specified programming adapters.

Application Pitfalls & Engineering Notes

Because RS232 is an unbalanced communication interface, the maximum length of the serial connection cable is strictly limited to 15 meters. Exceeding this distance or using low-grade unshielded cables in high-interference environments (e.g., adjacent to variable frequency drives) will lead to transmission errors and module timeouts. Ensure that the total current draw of connected sensors does not exceed the short-circuit protected limit of 0.5 A across the module.

Commissioning & Wiring Tips

When routing the control cables, use shielded copper wiring (2 x 0.25 mm²) specifically rated for RS232 transmissions. Ensure the shield is grounded properly on the host controller side. For the M8 power distribution daisy chain, verify that the cumulative control voltage (US) draw of all downstream modules does not exceed the contact rating of the feed connectors, which is typically capped at 4 A.

Installation Guidelines

CRITICAL WARNING: Prior to mounting or performing any wiring work on the Fieldbus Box, ensure all power sources—both control voltage (US) and auxiliary load voltage (UP)—are fully de-energized. Failure to isolate power can result in terminal damage, sensor damage, or unexpected system state transitions.
1
Mechanical Mounting: Secure the IP1002-B810 to a flat machine surface using two M3 screws through the 3.5 mm diameter mounting holes. Tighten to the recommended torque spec for your mounting substrate.
2
RS232 Bus Connection: Insert the B-coded 5-pin M12 bus cable into the communication port. Hand-tighten the screw coupling to secure the IP67-rated seal.
3
Power Feed Integration: Connect the incoming 24 V DC power source to the 4-pin M8 male connector. If daisy-chaining, run an M8 cable from the female downstream port to the next fieldbus module.
4
I/O Sensor Termination: Connect the 8 digital sensors to the respective M12 peripheral connections. Seal all unused ports with M12 protective caps to prevent fluid ingress and maintain the IP67 rating.
Loading product navigation…

What is the primary communication protocol used by the IP1002-B810?

This module utilizes a point-to-point RS232 serial interface with selectable baud rates of 9.6 kbaud, 19.2 kbaud, and 38.4 kbaud (default).

What is the maximum allowed cable distance for the RS232 connection?

The maximum recommended transmission cable length for the RS232 connection is 15 meters using high-quality shielded copper cable.

How do you configure the configuration parameters of this Fieldbus Box?

Configuration parameters and communication settings for the module can be adjusted through the Beckhoff KS2000 software environment.

Does the module require a separate protective electrical enclosure?

No, the IP1002-B810 features an IP65/66/67-rated polyamide housing that is fully sealed against moisture, dust, and direct liquid washdowns.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашей официальной Политика возврата и возмещения .

TECHNICAL SPECIFICATIONS

Country of origin
Германия

Недавно просмотренные товары

Технические знания

Электрические приводы, разработанные для замены гидравлических систем: практическое руководство по промышленной автоматизации

В этой статье объясняется, как интегрированные электрические приводы, такие как серия e-Actuator от SMC, преобразуют промышленное управление движением, заменяя традиционные пневматические и...

Математические операции с использованием OpenPLC для промышленных автоматизированных систем

В этой статье объясняется, как системы ПЛК выполняют основные математические операции, такие как сложение, вычитание, умножение, деление, взятие остатка и возведение в степень в рамках промышленной...

Продвинутая булева логика в программировании ПЛК с использованием FBD: практические промышленные применения за пределами базовой логики

В статье объясняются несколько продвинутых функций булевой логики, используемых в программировании ПЛК, помимо базовых операций AND, OR и NOT. Рассматривается, как такие инструменты, как таблицы...

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий, защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От систем с клеящими поверхностями, вдохновлёнными гекконами, и мягких захватов пищевого класса до...