1 из 3

Emerson DeltaV VE3008 KJ2005X1-MQ1 12P6381X032 MQ Controller

Emerson DeltaV VE3008 KJ2005X1-MQ1 12P6381X032 MQ Controller

Остался в наличии только 3 товар(ы)
  • Производитель: Emerson

  • Номер продукта: VE3008 KJ2005X1-MQ1 12P6381X032

  • Страна происхождения:Соединённые Штаты

  • Тип продукта: Controller Module

  • Штрихкод: 8537101190

  • Оплата: Т/Т, Western Union

  • Вес: 1200г

  • Размеры: 4.1cm x 15.9cm x 10.8cm

  • Порт отправления: Сямынь

  • Гарантия: 12 месяцев

Количество
Просмотреть полные детали

Description

The Emerson VE3008 is an MQ Controller designed for the DeltaV Distributed Control System (DCS). This hardware component provides communication and control between field devices and other nodes on the control network. It executes local control strategies with execution speeds up to every 100 ms. The VE3008 offers identical configurable memory and execution capabilities to the legacy MD Plus Controller, supporting seamless system scalability and legacy migrations. Online operational updates are automatically captured to ensure data integrity within the plant architecture.

Features

  • Seamlessly executes control strategies with configurable update loops as fast as 100 ms.
  • Retains entire active control strategies within internal non-volatile random-access memory (NVM RAM) to enable completely autonomous cold restarts following a supply power loss.
  • Integrates full-duplex Ethernet communication ports capable of reaching up to 100 MB/s maximum throughput.
  • Performs automated system identification and network addressing immediately upon initial system power-up.
  • Detects physical subsystem I/O interfaces automatically to identify distinct connected channel attributes.
  • Built-in visual identification function allows operators to flash specific faceplate LEDs via user interface software commands.
  • Facilitates data pass-through capabilities to securely route smart HART device variables directly to engineering workstations.
  • Provides functional compatibility for assignments to CHARM I/O Cards (CIOC) for electronic marshalling schemes when operating on supported software environments.

Applications

  • Chemical processing facilities and distillation column control networks.
  • Power generation utility oversight and distributed node monitoring.
  • Continuous batch execution and process loop regulations in oil and gas refineries.
  • Legacy automation platform migrations including PROVOX and RS3 structures.

Ordering Information

Description Model Number
MQ Controller VE3008 
Controller Module Hold-down Screw; box of 20 KJ4010X1-BP3 

Technical Specifications

Parameter Specification
Manufacturer Emerson
Model Type MQ Controller 
Hardware Assembly / Part Number KJ2005X1-MQ1
Component Layout Print Reference 12P6381X022 REV B
Manufacturing Origin Made in Malaysia
User Memory Capacity 48 MB 
Device Signal Tag (DST) Range 50 to 750 DSTs 
Power Supply Source Requirement Supplied by System Power Supply through 2-wide Power/Controller Carrier 
Power Dissipation 5.0 W typical, 7.0 W maximum 
Internal Overcurrent Protection 3.0 A, non-replaceable fuses 
Primary Network Interface 8-pin RJ-45 connector 
Redundant Network Interface 8-pin RJ-45 connector 
Module Width 4.18 cm (1.65 in.) 
Module Depth 13.91 cm (5.48 in.) 
Module Height 16.06 cm (6.32 in.) 
Operating Temperature Limit -40 to 70 degC (-40 to 158 degF) 
Storage Temperature Limit -40 to 85 degC (-40 to 185 degF) 
Relative Humidity Bounds 5 to 95%, non-condensing 
Environmental Gaseous Protection ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating 
Operational Shock Resistance 10 g 2-sine wave for 11 ms 
Operational Vibration Limit 1 mm peak-to-peak from 5 Hz to 16 Hz; 0.5 g from 16 Hz to 150 Hz 

Connections/Interfaces

LED Indicator Status Functional Meaning
Green - Power Indicates DC power is applied 
Red - Error Indicates an error condition 
Green - Active Indicates that the controller is operating as the primary controller 
Green - Standby Indicates that the controller is operating as a backup controller (reserved for future use) 
Yellow Flashing - Pri. CN Indicates valid primary control network communication 
Yellow Flashing - Sec. CN Indicates valid secondary control network communication 
All except Power flashing Visual identification of controller initiated from user interface software by ping command 
All except Power flashing, alternating Firmware upgrade in progress 

Installation Guidelines

  • Carrier Mounting: The module must be positioned and installed securely on the right slot of a compatible M-series Power/Controller Carrier.
  • Power Provision: Each controller node demands an independent, dedicated system power supply unit tied to the carrier backplane.
  • Software Version Dependencies: Baseline operation requires DeltaV software version v10.3.1 or higher. Electronic marshalling or CHARM structural allocation necessitates software version v14.3 or later.
  • Network Isolation: For implementations utilizing Electronic Marshalling, dedicated DeltaV Smart Switches must be installed to bridge data paths between controllers and CHARM I/O Cards (CIOC).

Compliance and Certifications

  • CE Compliance: Certified 
  • EMC Standards: EN 61326-1 
  • FM Certification (USA): Class I, Division 2, Groups A, B, C, D, T4 hazardous locations 
  • cFM Certification (Canada): Class I, Division 2, Groups A, B, C, D, T4 hazardous locations 
  • ATEX Classification: II 3G Ex ec IIC T4 Gc (Zone 2 installation environments) 
  • IEC Ex Classification: II 3G Ex ec IIC T4 Gc 
  • Marine Appraisals: Compliant with IACS E10 guidelines; holds ABS Certificate of Design Assessment and DNV Type Approval Certificate 
  • Industrial Cybersecurity: Certified to Achilles Communications Certification Level 2 requirements 
Loading product navigation…

What software version is required to use the module?

The device requires a baseline of DeltaV system software version v10.3.1 or later. If you need to assign CHARMs for electronic marshalling functions, software version v14.3 or later must be installed.

Can the device be used in hazardous environmental areas?

Yes, the module is certified for installation within hazardous areas under FM/cFM Class I, Division 2, Groups A, B, C, D (T4 temperature rating) as well as ATEX/IECEx Zone 2 setups.

What is the function of the internal non-volatile memory?

The internal NVM RAM fully retains the active control strategies configuration. In the event of an unexpected power failure, this memory ensures the device can execute a completely autonomous cold restart once power returns.

Where should the module be mounted on its carrier?

The module must be explicitly installed on the designated right slot position of an M-series 2-wide Power/Controller Carrier.

Глобальная экспресс-доставка

  • Стандартная доставка: 4-6 рабочих дней через DHL, FedEx и UPS.
  • Экспресс-отправка: Отправка в тот же день для заказов со склада, сделанных до 14:00 (GMT+8).
  • Мировое покрытие: Обслуживаем более 150 стран, включая быструю доставку в Саудовскую Аравию и ОАЭ.

Возвраты и гарантия

  • 30-дневная гарантия: Принимаются возвраты товаров со склада в оригинальной, заводской упаковке.
  • 12-месячная гарантия: Каждый промышленный компонент поддерживается нашей профессиональной технической гарантией.

Заказы обрабатываются и доставляются с понедельника по пятницу (кроме государственных праздников).


Для полной информации о праве на возврат, сборах за пополнение запасов и международных возвратах, пожалуйста, ознакомьтесь с нашей официальной Политика возврата и возмещения .

TECHNICAL SPECIFICATIONS

Color pattern
Черный
Country of origin
Соединённые Штаты
Power source
Постоянный ток Питается от сети переменного тока

Недавно просмотренные товары

Технические знания

Электрические приводы для замены жидкостей: практическое руководство

This article explains how integrated electric actuators, such as SMC’s e-Actuator series, are transforming industrial motion control by replacing traditional pneumatic and hydraulic systems. It...

Математические операции с использованием OpenPLC для промышленных автоматизированных систем

В этой статье объясняется, как системы ПЛК выполняют основные математические операции, такие как сложение, вычитание, умножение, деление, взятие остатка и возведение в степень в рамках промышленной...

Продвинутая булева логика в программировании ПЛК с использованием FBD: практические промышленные применения за пределами базовой логики

В статье объясняются несколько продвинутых функций булевой логики, используемых в программировании ПЛК, помимо базовых операций AND, OR и NOT. Рассматривается, как такие инструменты, как таблицы...

Булева логика в программировании ПЛК: понимание логических элементов FBD

Булева логика является основой каждой программы ПЛК. От простого управления машинами до сложных систем промышленной автоматизации, логические элементы определяют, как контроллеры реагируют на...

Подробное руководство по промышленным файрволам и сегментации сетей ОТ

Промышленные межсетевые экраны играют ключевую роль в кибербезопасности операционных технологий, защищая сети ПЛК, ДСК и SCADA посредством сегментации, контроля входящего и исходящего трафика, а...

Руководство по роботизированным захватам: от деликатного обращения до тяжелой автоматизации

Современные роботизированные захваты развиваются дальше традиционных механических челюстей. От систем с клеящими поверхностями, вдохновлёнными гекконами, и мягких захватов пищевого класса до...